Ahead of the Sept 28 hearing on school repairs at the Council, I requested every open work order the DC Department of General Services has for Ward 6 DCPS schools that is more than 30 days old.
I'm sharing the full list (472!) of items so Ward 6 neighbors can see what's happening at their school and others as I prepare to question DGS leadership later.
Building Name | Work Order No | Problem Type | Room/ Location - Affected Area | Assignment Description |
AMIDON ELEMENTARY SCHOOL | 660154 | Interior Painting & Wall Issue | 106 | Interior Painting & Wall Issue: ? Patching & Painting ? Caulking Assignment Description: Need someone to come out to repair the backsplash for the kids sink |
AMIDON ELEMENTARY SCHOOL | 676706 | Interior Painting & Wall Issue | 106 | Need walls painted in classroom have paint on site |
AMIDON ELEMENTARY SCHOOL | 673949 | Cooling | 107 | Need thermostat replaced or repaired in the room. |
AMIDON ELEMENTARY SCHOOL | 673952 | Cooling | 126 | Need two univents serviced in the room unable to turn them on or off from the thermostat. |
AMIDON ELEMENTARY SCHOOL | 676704 | Interior Painting & Wall Issue | 126 | Need walls painted in classroom have paint on site |
AMIDON ELEMENTARY SCHOOL | 676703 | Interior Painting & Wall Issue | 128 | Need walls painted in classroom have paint on site |
AMIDON ELEMENTARY SCHOOL | 681897 | Pipe | 133 | Need rail heater removed and capped off in the room. |
AMIDON ELEMENTARY SCHOOL | 676691 | Interior Painting & Wall Issue | 202 | Need walls painted in classroom have paint on site |
AMIDON ELEMENTARY SCHOOL | 676693 | Interior Painting & Wall Issue | 205 | Need walls painted in room have paint on site |
AMIDON ELEMENTARY SCHOOL | 676694 | Interior Painting & Wall Issue | 212 | Need walls painted in classroom have paint on site |
AMIDON ELEMENTARY SCHOOL | 676696 | Interior Painting & Wall Issue | 223 | Need walls painted in classroom have paint on site |
AMIDON ELEMENTARY SCHOOL | 676698 | Interior Painting & Wall Issue | 225 | Need walls painted in classroom have paint on site |
AMIDON ELEMENTARY SCHOOL | 676701 | Interior Painting & Wall Issue | 227 | Need purple wall painted in classroom have paint on site |
AMIDON ELEMENTARY SCHOOL | 676697 | Interior Painting & Wall Issue | 230 | Need walls painted in classroom have paint on site |
AMIDON ELEMENTARY SCHOOL | 682579 | Interior Painting & Wall Issue | 231 | Patch and paint walls in classroom 231 |
AMIDON ELEMENTARY SCHOOL | 682580 | Interior Painting & Wall Issue | 232 | Patch and painting needed in room 232 |
AMIDON ELEMENTARY SCHOOL | 676702 | Interior Painting & Wall Issue | 236 | Need walls painted in classroom have paint on site |
AMIDON ELEMENTARY SCHOOL | 682584 | Faucet | 267 in library | Need faucet repaired in room 267 |
AMIDON ELEMENTARY SCHOOL | 669686 | Heating | B129 boiler room | Need heat to be turned on in boiler room for the kids in the classrooms the heat has been completely shutdown for three days. |
AMIDON ELEMENTARY SCHOOL | 674720 | Cooling | Boiler | Repair/replace worn rubber coupling on chill water circulating pump #3. Also the return FNW temp gauge is broken, unable get adequate temp. BPO Wright 202-345-7587 |
AMIDON ELEMENTARY SCHOOL | 682031 | Cooling | Boiler room | Pump 3 - chiller water Coupler needs to be replaced |
AMIDON ELEMENTARY SCHOOL | 682032 | Cooling | Boiler room | Chill water relief valve leaking |
AMIDON ELEMENTARY SCHOOL | 677587 | Interior Painting & Wall Issue | Gym | Need ceiling repaired from roof leak that is still going on |
AMIDON ELEMENTARY SCHOOL | 682191 | Roof | GYM | Roof Issue: ? Roof Damage Assignment Description: Roof leak in the middle of the gym floor |
AMIDON ELEMENTARY SCHOOL | 659388 | Fire Extinguisher | Library & Elevator Room | Fire Extinguisher Issue: ? Fire Code (IFC) Assignment Description: Amidon ES (VAMP Routine Priority III/Routine Repair) IFC 901.6 Inspection, Testing & Maintenance - Fire Extinguishers Library - replace missing service tag. Elevator/Equipment Room -Replace blank service tag or Punch service date on existing service tags. Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust systems, and smoke and heat vents shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. FEMS Lvl-2 |
AMIDON ELEMENTARY SCHOOL | 682660 | Cooling | Library rooftop | Filters needs to be replaced |
AMIDON ELEMENTARY SCHOOL | 662453 | Electronic Security Issue | Main office | Electronic Security Issue: ? Not Working Assignment Description: Problem with the alarm |
AMIDON ELEMENTARY SCHOOL | 672795 | Cooling | Multipurpose Room and Gym | Cooling Issue: ? AC Unit ? Too Hot Assignment Description: Repairs rooftop unit that serves Multipurpose Room and Gym |
AMIDON ELEMENTARY SCHOOL | 682540 | FIRE ALARM | Multi purpose room pull station | Slc loop is damaged between two pullstations in cafeteria area between exit 21 and exit 22, the physical conductor between those two pullstations is compromised, thus needing replaced to get the main FA panel out of ground fault trouble. |
AMIDON ELEMENTARY SCHOOL | 657400 | Playground | Playground | Playground Issue: ? Equipment ? Repair/Remove/Replace Equipment Assignment Description: Need painter's to come out to treat and paint the bleachers for the basketball courts |
AMIDON ELEMENTARY SCHOOL | 676079 | Building Structural | Rooftop gym unit | Need engineer to come out to repair unit on the roof for the gym water is leaking from the unit and coming thru the ceiling of the gym flooding the gym floor. |
AMIDON ELEMENTARY SCHOOL | 682568 | Cooling (HVAC Services) | Rooftop unit | duct installation specialist is needed as the duct on the roof is being filled with water when it rains. - RSC has been dispatch per Gassama |
AMIDON ELEMENTARY SCHOOL | 677535 | Cooling | Rooftop unit | Need rooftop unit for multi purpose room serviced no a/c |
AMIDON ELEMENTARY SCHOOL | 678338 | Lighting | See Description for details | Light Pollution - Parking Lot: There are a few high intensity LED lights that are too bright as they come into my home on the third floor across 4th street. Please let me know if they be adjusted to point down or a guard / filter added at the top of the fixtures so they do not shine directly into my home. Thanks |
BRENT ELEMENTARY SCHOOL | 652091 | Building Structural | 203, 303, 311 | Structural Issue: ? Ceiling Assignment Description: These three rooms leak whenever there's rain, but each room has a leak in different areas. Room 203 leaks from under the univent but we know that the univent is not causing the leak. Room 303 leaks from the cracks in the concrete portion of the ceiling. Room 311 leaks from the ceiling over the window by the mirror on the wall. POC Jason Lawrence 301-706-3387 |
BRENT ELEMENTARY SCHOOL | 634810 | Interior Painting & Wall Issue | 208 | Interior Painting & Wall Issue: ? Patching ? Caulking Assignment Description: There is a large hole in the wall under the sink in room 208. Pest Control has reported that this is an entry point and exit for the mice that are frequenting this room and the 2nd floor. We need the hole to be filled to help alleviate the continuing issue with mice. |
BRENT ELEMENTARY SCHOOL | 614921 | Lock and Door | 311 | The doorknob is not functioning properly in room 311. There have been several instance where teachers and student have not been able to get out of the room because the knob would not function. |
BRENT ELEMENTARY SCHOOL | 662155 | Leak | Chiller | Leak Issue: ? Pipe / Line / Drain Assignment Description: Chiller is leaking a large amount of water. The chiller is not draining either. |
BRENT ELEMENTARY SCHOOL | 682083 | FIRE ALARM | Fire Alarm | Fire Alarm Issue: ? Repair Assignment Description: The fire alarm continued to go off for several hours on Sunday. Security came and could not resolve the issue. The fire alarm was disconnected from power. |
BRENT ELEMENTARY SCHOOL | 682408 | Power | Kitchen | Power Issue: ? Partial Outage ? The emergency lights are working Assignment Description: Our equipment repair vendor TKC were on site to recently and inspected the kitchen exhaust hood system. They found that the exhaust hood is not getting any power. Diagnosed as ? 1 of 3 legs of electrical is missing to the unit on the roof. |
BRENT ELEMENTARY SCHOOL | 668279 | Fire Extinguisher | Kitchen | Fire Extinguisher Issue: ? Fire Code (IFC) Assignment Description: Brent ES (West EC population) VAMP Emergency Priority I/Emergency Repair) IFC 904.11.6/IFC 901.6 Operation and Maintenance (Inspection/Testing) ? Kitchen Suppression system Kitchen - Service, update and re-tag expired (July 2020) Ansul kitchen fire suppression system. Implement service PM plan to update every 6-mos as required bit IFC/ Fems Inspector. ( Note: FLS PM is scheduled for Aug 2022)Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust systems, and smoke and heat vents shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. - FEMS LVL-2 |
BRENT ELEMENTARY SCHOOL | 665122 | Lock and Door | Lobby/Front Door | Lock and Door Issue: ? Door ? Handicap Entrance/Door ? Repair/Replace/Install Door/Door Frame ? null Assignment Description: The front door that is connected to the electrical remote opening system is not functioning properly. The door does not open when the button is pressed and sometimes gets stuck open when it is opened manually. We have turn the switch off which has helped with the door getting stuck open, but we can no longer remotely open the door. A staff member or security guard has to manually open the door whenever someone needs access to the school which only increase face to face contact and does not allow social distancing during the Covid-19 pandemic. A technician is needed to fix this issue. POC Jason Lawrence 301-706-3387 |
BRENT ELEMENTARY SCHOOL | 652081 | Roof | Main Lobby | Roof Issue: ? Water Leak ? Rooftop Also included: RM 302 - There is a significant amount of water falling from the concrete portion of the ceiling in room 302. The section of the ceiling leaking is closest to the teacher's corner; the area by the kidney table, cabinet etc. is where the water is leaking. Work Orders 652081 and 660258 also pertain to roof leaks in other parts of the school. This room is a classroom that will be physically occupied by students and staff members. Roofers are needed to assess and resolves the issues. POC Jason Lawrence 301-706-3387 library - 1st floor library ceiling window glass is cracked in the corner and water is leaking in through the window into the library. Assistance needed. There is a crack in the first skylight on the roof of the library. Water pours into the library whenever we have inclement weather. The skylight is located over top of several computers, which have to be moved when there's inclement weather. Assignment Description: There is a significant leak coming from the roof as soon as you enter the Main Lobby at Brent ES. Whenever we have rain the ceiling tiles get saturated with water and are in danger of falling on students parents and staff. A roofing solution is needed to stop this issue from occurring. POC Jason Lawrence 301-706-3387 |
BRENT ELEMENTARY SCHOOL | 682085 | Building Structural | Room 203 | Structural Issue: ? Wall Assignment Description: A significant amount of water leaks into the classroom from under the HVAC unit after every rain. The building engineer noted that it was a building structural issue. This classroom is an 1st grade classroom. |
BRENT ELEMENTARY SCHOOL | 672485 | Playground | Yellow Top Playground | Playground Issue: ? Equipment ? Repair/Remove/Replace Equipment Assignment Description: The tan colored sliding board on the yellow top playground has been damaged. There is a significantly large hole in the sliding board now that is a cutting hazard. The students are not able to use the sliding board as the jagged edges will injure anyone who attempts to use it. Work Order 662799 was put in on 1/6/2021 but the work order has been closed without the work being completed. When the original work order was put in there were two holes in the sliding board. Since the original work order was put in Salesforce, the holes have now become one larger hole. POC Jason Lawrence 301-706-3387 |
EASTERN HIGH SCHOOL | 675267 | Grounds | 1st floor roof top. | Grounds Issue: ? Grass Assignment Description: Requesting Ms. Utility . |
EASTERN HIGH SCHOOL | 656550 | Roof | 1st floor W-137 court yard . | Roof Issue: ? Water Leak ? Gutters Assignment Description: The down spout leading from the roof need to be repair . |
EASTERN HIGH SCHOOL | 665981 | Lighting | 2nd floor East atrium | Lighting Issue: ? Interior Lights ? Above 8 feet ? Hallway ? null Assignment Description: the 1st light fixture globe need to be replace . |
EASTERN HIGH SCHOOL | 676690 | Window | 3rd floor hallway west wing | Window Issue: ? Below 8 feet /1 story ? Window Glass ? Broken ? null Assignment Description: Hallway glass is broken |
EASTERN HIGH SCHOOL | 631296 | Lighting | Auditorium | Lighting Issue: ? Interior Lights ? Above 8 feet ? Room(s)/Auditorium/Gymnasium ? null Assignment Description: Adjust the stage lights |
EASTERN HIGH SCHOOL | 681362 | Cooling | Auditorium | Cooling Issue: ? AC Unit ? No AC Assignment Description: The A/C unit is not cooling in the auditorium |
EASTERN HIGH SCHOOL | 674098 | Drinking Water Filter (Plumbing Services) | Basketball court | Water Fountain Issue: ? Permanent Water Fountain ? Not Working Assignment Description: Water fountain is missing near the exterior basketball court //please send to contract service for replacement. |
EASTERN HIGH SCHOOL | 658045 | Railing and Step | basketball court / tennis court | Railing and Step Issue: ? Rail Assignment Description: The steps leading to the basket ball court and tennis courts need a railing install for safety . |
EASTERN HIGH SCHOOL | 671982 | Leak (Plumbing Services) | Boiler Room | Cooling Issue: ? AC Unit ? Central Air Assignment Description: Repair/Replace rupture 2? filter canister pvc line. |
EASTERN HIGH SCHOOL | 669428 | Fire Sprinkler | Boiler room | Fire Sprinkler Issue: ? Fire Code (IFC) Assignment Description: Fire sprinkler system in trouble |
EASTERN HIGH SCHOOL | 682418 | Cooling | Chiller / outside of building | Chiller down , possible both circuits down on refrigerant |
EASTERN HIGH SCHOOL | 682260 | Lighting | E-100 B | Lighting Issue: ? Interior Lights ? Below 8 feet ? Hallway ? null Assignment Description: Replace two balances |
EASTERN HIGH SCHOOL | 666536 | Lighting | E-122 | Lighting Issue: ? Interior Lights ? Below 8 feet ? Room(s)/Auditorium/Gymnasium ? null Assignment Description: Requesting to have the light balance change . |
EASTERN HIGH SCHOOL | 681771 | Lock and Door | E-209 | door handle need to be replace . |
EASTERN HIGH SCHOOL | 652521 | Ceiling | e-307 | Ceiling Issue: ? Missing ceiling tile Assignment Description: Missing ceiling tile needs to be replaced. |
EASTERN HIGH SCHOOL | 680212 | Lighting | E-320 | Lighting Issue: ? Interior Lights ? Above 8 feet ? Room(s)/Auditorium/Gymnasium ? null Assignment Description: Replace balance in the light fixture . |
EASTERN HIGH SCHOOL | 677163 | Cooling | E320 ,E114 , E116 , E313 , E412 , W137 , W113 | E320 - Possible bad fan motor, E114 blown fuses, E116 not cooling & low on Freon, E313 need to reassembled, E412 want start , W137 Motor blown , W113 out on low pressure |
EASTERN HIGH SCHOOL | 682453 | Cooling | ERV/ Roof Top | Cooling Issue: ? AC Unit ? Central Air Assignment Description: Control problems and barring are bad |
EASTERN HIGH SCHOOL | 676013 | Building Structural (Interior Services) | Exterior door zone 3 | Lock and Door Issue: ? Lock/Latch & Door ? Standard Door ? Repair/Replace/Install Door Knob/Door Handle ? null Assignment Description: The 15 second egress panic bar is not working . panic bar is electrical need contract service |
EASTERN HIGH SCHOOL | 682766 | Lock and Door | exterior zone doors 7, 9-A, 9-b , zone 10 | Lock and Door Issue: ? Lock/Latch & Door ? Standard Door ? Repair/Replace/Install Door Lock ? null Assignment Description: The exteriors doors are not closing properly |
EASTERN HIGH SCHOOL | 681773 | FIRE ALARM | Fire alarm panel | Fire Alarm Issue: ? Fire Code (IFC) Assignment Description: The fire alarm panel reads RTU in trouble |
EASTERN HIGH SCHOOL | 681343 | Fence and Gate | Football field | Fence and Gate Issue: ? Fence & Pole ? Repair Fence & Pole Assignment Description: fence need to be repair. |
EASTERN HIGH SCHOOL | 682034 | Landscaping | Football field | Landscaping Issue: ? Trees/Leaves ? Cut/Trim Trees ? Entrance/Egress is obstructed ? null Assignment Description: Damage tree . |
EASTERN HIGH SCHOOL | 675806 | Exterior Painting | football field | Exterior Painting Issue: ? Building/Doors Assignment Description: The score board need to be painting |
EASTERN HIGH SCHOOL | 675807 | Exterior Painting | football field | Exterior Painting Issue: ? Building/Doors Assignment Description: Score board need painting |
EASTERN HIGH SCHOOL | 678402 | Lighting | football field | Lighting Issue: ? Exterior Lights ? Above one (1) story ? Athletic Field(s) ? null Assignment Description: The football field stadium has 18 lights out , need to be replace . |
EASTERN HIGH SCHOOL | 679545 | Lighting | football field | Lighting Issue: ? Exterior Lights ? Below one (1) story ? Athletic Field(s) ? null Assignment Description: The two score boards on the football field needs lights on the lower level . |
EASTERN HIGH SCHOOL | 679740 | Pipe | football field | Pipe Issue: ? Water ? Rupture / Burst Assignment Description: Burst pipe |
EASTERN HIGH SCHOOL | 649774 | Lighting | Front Entrance | Lighting Issue: ? Exterior Lights ? Above one (1) story ? Outside/Building/Street/Parking Lot ? null Assignment Description: Requesting the lights to be change, exterior front entrance |
EASTERN HIGH SCHOOL | 667364 | MASONRY | Front entrance | Masonry Issue: ? Ground/Pavement ? Brick Assignment Description: The brick walk way is uneven front the tree root . It's a safety issue . |
EASTERN HIGH SCHOOL | 682577 | Fire Sprinkler | G-07 | Fire Sprinkler Issue: ? Fire Code (IFC) Assignment Description: The fire sprinkler is leaking |
EASTERN HIGH SCHOOL | 682597 | Roof | G-07 | Roof Issue: ? Water Leak ? Rooftop Assignment Description: Roof top drain need to clean , check for leaks . |
EASTERN HIGH SCHOOL | 667811 | Power | greenhouse | Power Issue: ? Partial Outage ? The emergency lights are working Assignment Description: Converting the gas heating to electric , the gas heater pilot keep going out . |
EASTERN HIGH SCHOOL | 671641 | Switch | greenhouse | bulb is out |
EASTERN HIGH SCHOOL | 610690 | Building Structural | Gymnasium | The main north basketball hoop need a bolt in the rim to hold it in place . |
EASTERN HIGH SCHOOL | 662969 | Building Structural | Gymnasium area | Structural Issue: ? Ceiling Assignment Description: The ceiling is dropping |
EASTERN HIGH SCHOOL | 669911 | Lock and Door | Gymnasium exterior doors | Lock and Door Issue: ? Lock/Latch ? Standard Door ? Locksmith ? null Assignment Description: The 15 seconds Egress doors need 9 volt batteries zone 5,6,4. |
EASTERN HIGH SCHOOL | 613649 | Building Structural (Interior Services) | kitchen | THE FLOOR IS A SHEET VLY AND NEED A CONTRACTOR TO PURCHASE THE MATERIALS AND INSTALL the floor is made of a hold sheet of qronlla |
EASTERN HIGH SCHOOL | 680249 | Outlet | Main Office | Outlet Issue: ? Repair Outlet ? The conduit is not exposed Assignment Description: Requesting a designated phone line for main PA- System . |
EASTERN HIGH SCHOOL | 682417 | Cooling | MAU # 1 / Boiler Room | MAU # 1 is down , multiple error code to include safety lockouts and low pressure on compressors |
EASTERN HIGH SCHOOL | 682419 | Cooling | MAU # 3 / Roof | Cooling Issue: ? AC Unit ? No AC Assignment Description: Possibly bad disconnect and also need new motor pulley |
EASTERN HIGH SCHOOL | 629735 | Parking Lot | Parking Lot | Large pot hole in the back parking lot by the trash can. |
EASTERN HIGH SCHOOL | 658041 | Exterior Painting | Parking lot | Exterior Painting Issue: ? Line(s)/Stripe(s) Assignment Description: The parking lot need to be strip and paint . |
EASTERN HIGH SCHOOL | 680885 | Odor | parking lot | Odor Issue: ? Sewage Odor Assignment Description: Requesting trash compactor |
EASTERN HIGH SCHOOL | 675477 | Cooling | Press box/ football field | Cooling Issue: ? AC Unit ? Too Hot Assignment Description: Unit not cooling, bad condenser fan |
EASTERN HIGH SCHOOL | 671123 | Roof | Press box in the football field | Roof Issue: ? Water Leak ? Rooftop Assignment Description: Roof is leaking and ceiling towels needs to be changed |
EASTERN HIGH SCHOOL | 682416 | Cooling | RTU #2 | Possibly bad compressor and bad contractor?.possible bad burner ignition board?also broken condensate line |
EASTERN HIGH SCHOOL | 682415 | Cooling | RTU # 5,6,7,&8 | They have all lost communication with the EMS . They also need multiple repairs such as a bad gas valves, flame sensors , burned contractors ,pulley , and shives ? need new condensate drain lines |
EASTERN HIGH SCHOOL | 668778 | Roof | Second-floor east side atrium | Roof Issue: ? Water Leak ? Rooftop Assignment Description: Second-floor east side atrium Roof is leaking |
EASTERN HIGH SCHOOL | 670233 | Lighting | See Description for details | Tennis court lights: Hi ? one of the light poles at the tennis courts doesn?t light when the rest do. |
EASTERN HIGH SCHOOL | 658817 | Power | The marquee font entrance east lawn | Power Issue: ? Complete Outage ? The emergency lights are working Assignment Description: Requesting to have the marquee electrical wiring repair . |
EASTERN HIGH SCHOOL | 664184 | Building Structural (Interior Services) | W- 108 | Window Issue: ? Below 8 feet /1 story ? Window Glass ? Repair/Replace/Install ? null Assignment Description: The main office first window don't stay up . need CS to have a window contractor to replace the pulleys per size and etc. |
EASTERN HIGH SCHOOL | 669135 | Window(Interior Services) | W-119 | The exterior window in W-119 is broken . It's a double pane window . |
EASTERN HIGH SCHOOL | 682440 | Cooling | W141B and EMT | Cooling Issue: ? AC Unit ? No AC Assignment Description: Unit inoperable, possible low pressure |
EASTERN HIGH SCHOOL | 670528 | Window | W143 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: When it rains water be dripping down it may be the gutters causing this issue. |
EASTERN HIGH SCHOOL | 680505 | Cooling | W415,W412,W410,W409,W408,W307,W312,W314 | W415-unit is frozen, possible low on refrigerant,W412 not cooling,410 - low pressure, W409 - Bad fan motor,W408 W314 & W307-not proper charge, W312 - low pressure |
EASTERN HIGH SCHOOL | 682386 | Building Structural (Interior Services) | Weight Room | Structural Issue: ? Wall Assignment Description: The mirrors on the walls of the weight room are broken and need to be repaired. The broken mirrors represent a hazard to our students as they can possibly cut our students. need contract services to replace broken glass with a contractor |
EASTERN HIGH SCHOOL | 678053 | Building Structural | Weight room | Structural Issue: ? Wall Assignment Description: Remove broken mirrors , and install new mirrors . |
EASTERN HIGH SCHOOL | 680765 | Building Structural | Weight Room | Structural Issue: ? Wall Assignment Description: The mirrors on the walls of the weight room are broken and need to be repaired. The broken mirrors represent a hazard to our students as they can possibly cut our students. |
EASTERN HIGH SCHOOL | 664145 | Roof | west atrium | Roof Issue: ? Water Leak ? Rooftop Assignment Description: west atrium roof is leaking . |
EASTERN HIGH SCHOOL | 666282 | Ceiling | west wing zone 9 | Ceiling Issue: ? Falling (loose) tiles Assignment Description: The ceiling need new brackets install. |
EASTERN HIGH SCHOOL | 666284 | Ceiling | zone 5 & 6 gymnasium area | Ceiling Issue: ? Falling (loose) tiles Assignment Description: The ceiling new bracket need to be install . |
EASTERN HIGH SCHOOL | 681473 | Lighting | Zone 7 | Lighting Issue: ? Exterior Lights ? Below one (1) story ? Outside/Building/Street/Parking Lot ? null Assignment Description: The exterior light is not working in zone 7 |
EASTERN HIGH SCHOOL | 651508 | Interior Painting & Wall Issue | zone 9 ramp | Interior Painting & Wall Issue: ? Painitng ? Paint Peeling Assignment Description: Requesting to have zone 9 ramp floor paint . |
ELIOT-HINE MIDDLE SCHOOL | 680946 | Grounds | 162 B | Grounds Issue: ? Bulk Trash Assignment Description: BULK TRASH FOR STUDIO CAMERA LIGHTS , AND STUDIO POLE GRIDS /525 order #60240 |
ELIOT-HINE MIDDLE SCHOOL | 678122 | Interior Painting & Wall Issue | 236 | Interior Painting & Wall Issue: ? Patching & Painting ? Painting Maintenance Assignment Description: PATCH AND PAINTING NEEDED TO WALLS |
ELIOT-HINE MIDDLE SCHOOL | 676588 | Cooling | 372 , 327 261, Kitchen, Lobby | Cooling Issue: ? Temperature ? Too Cold Assignment Description: ALL ROOMS LISTED NEED A ADJUSTMENT WITH THE TEMPERATURE |
ELIOT-HINE MIDDLE SCHOOL | 681260 | Heating | Boiler Room | Heating Issue: ? Heating Unit ? No Heat Assignment Description: Boilers 1 and 2 have large amounts of scale and need Boiler Maintenance. |
ELIOT-HINE MIDDLE SCHOOL | 682061 | Drain | CAFETERIA | Odor Issue: ? Sewage Odor Assignment Description: FOUL SMELL COMING FROM CLEANOUT FROM FLOOR |
ELIOT-HINE MIDDLE SCHOOL | 682067 | PEST CONTROL | CAFETERIA | Pest Control Issue: ? School ? Flying Insects Assignment Description: PEST CONTROL NEEDED FOR MOSQUITOS IN CAFETERIA. |
ELIOT-HINE MIDDLE SCHOOL | 681554 | Lock and Door | G 10 | Lock and Door Issue: ? Lock/Latch ? Metal Door ? Repair/Replace/Install Door Lock ? null Assignment Description: G10 CLASSROOM EXTERIOR DOOR THAT LEADS OUTSIDE KEYS DONT FIT. |
ELIOT-HINE MIDDLE SCHOOL | 675282 | Window | G67 CUSTODIAN OFFICE | Window Issue: ? Above 8 feet/1 Story ? Window Glass ? Broken ? null Assignment Description: OUTSIDE WINDOW PANE BROKE. |
ELIOT-HINE MIDDLE SCHOOL | 674276 | Power | KITCHEN | Power Issue: ? Complete Outage ? The emergency lights are working Assignment Description: ELECTRICAL ISSUE WITH CIRCUIT CAUSING BREAKER TO TRIP |
ELIOT-HINE MIDDLE SCHOOL | 678076 | Interior Painting & Wall Issue | ROOM 245 | Interior Painting & Wall Issue: ? Patching & Painting ? Painting Maintenance Assignment Description: PATCH JOB NEEDED FOR FRONT WALL |
ELIOT-HINE MIDDLE SCHOOL | 681956 | Cooling | THROUGHOUT | Cooling Issue: ? Temperature ? Too Hot Assignment Description: AIR IS NOT WORKING IN CERTAIN LOCATIONS THROUGHOUT |
J.O. WILSON ELEMENTARY SCHOOL | 658568 | Window | 108 | Window Issue: ? Below 8 feet /1 story ? Window Glass ? Broken ? null Assignment Description: shattered window pane |
J.O. WILSON ELEMENTARY SCHOOL | 679689 | Cooling | 110,211c 1st floor&2nd | a technician is needed to investigate and make repair at following location J.O.Wiso 660 k street N.E Repair or replace defective blower motor bearings, shaft,drive,coupling,pulley, motorize control valve, and microprocessors board on univent in classroom 110,211c room in alarm readings F1,F8, and de temperature sensor failure rooms are without cooling. Assistance is needed. |
J.O. WILSON ELEMENTARY SCHOOL | 682558 | Window | 124 and 123 | Window Issue: ? Below 8 feet /1 story ? Window Glass ? Repair/Replace/Install ? null Assignment Description: Would like to add shades or window treatment to the ECE rooms. |
J.O. WILSON ELEMENTARY SCHOOL | 671797 | Interior Painting & Wall Issue | 1ST, 2ND, & 3RD FLOOR | The walls of J.O. Wilson have not been painted in a number of years. When they were last painted, they were painted a very dull, dingy, institutional gray color that is not kid-friendly. Currently, the walls have a drab look which sends a negative message to both our students and families. As we prepare for a return to school, we are putting a major emphasis on the SEL needs of our students and something as simple as a fresh coat of paint on the walls would send a message of care and love. Having a fresh coat of paint would help us to debunk the broken window theory and send a message to our students that their learning environment is a priority. |
J.O. WILSON ELEMENTARY SCHOOL | 652526 | Interior Painting & Wall Issue | 1ST, 2ND, AND 3RD FLOOR HALLWAYS | Interior Painting & Wall Issue: ? Painitng ? Painting Maintenance Assignment Description: HALLWAY WALLS ARE IN NEED OF A PAINT JOB. |
J.O. WILSON ELEMENTARY SCHOOL | 627172 | Lock and Door | 208 | Window Pane Shattered |
J.O. WILSON ELEMENTARY SCHOOL | 682561 | Leak | 221 | Leak Issue: ? Sink Assignment Description: Sink leaks to second floor when turned on. Student will return to a bathroom with no running water. |
J.O. WILSON ELEMENTARY SCHOOL | 676695 | Interior Painting & Wall Issue | 221 | Interior Painting & Wall Issue: ? Painitng ? Paint Peeling Assignment Description: Paint Walls |
J.O. WILSON ELEMENTARY SCHOOL | 680875 | Window | 308 | Replace door glass Lower panel Shattered glass - Computer Lab 308 |
J.O. WILSON ELEMENTARY SCHOOL | 568027 | GENERAL SRV | 323, 306 | Leak in room 306 in the ceiling coming from the roof. |
J.O. WILSON ELEMENTARY SCHOOL | 682802 | Outlet | 328B | Outlet Issue: ? Repair Outlet ? The conduit is exposed Assignment Description: Exposed electrical box/wires |
J.O. WILSON ELEMENTARY SCHOOL | 682803 | Lighting | 328B | Lighting Issue: ? Interior Lights ? Below 8 feet ? Room(s)/Auditorium/Gymnasium ? null Assignment Description: Lights will not come on bulbs have been changed and switch turned on from electrical panel. |
J.O. WILSON ELEMENTARY SCHOOL | 676470 | Interior Painting & Wall Issue | blue section on 2nd and 3rd floor | Interior Painting & Wall Issue: ? Painitng ? Repaint Assignment Description: Walls Painted 2nd and 3rd floor. |
J.O. WILSON ELEMENTARY SCHOOL | 652527 | Building Structural | commons area 1st floor | Structural Issue: ? Partition Assignment Description: replace wall partitions with the permanent walls. This is a safety issue students are climbing walls and hiding from staff. |
J.O. WILSON ELEMENTARY SCHOOL | 599772 | FLOORING | c stairwells | steps rubber coming off cause students and staff to trip. |
J.O. WILSON ELEMENTARY SCHOOL | 578727 | Flooring (Interior Services) | ECE 109 | The leak that?s causing damage to the floor is still active. Once the leak is fixed the school want the vinyl sheet removed and replaced with new vinyl sheet. Work needs to be completed by C/S. |
J.O. WILSON ELEMENTARY SCHOOL | 671759 | Fire Extinguisher | Kitchen | JO Wilson ES. ***(ABATED AND CORRECTED by DGS Contract Services ; CLOSE OUT WORK ORDER)*** VAMP Emergency Priority I/Emergency Repair) IFC 904.12.6.2 Operation and Maintenance (Inspection/Testing) ? Kitchen Ansul Suppression system Kitchen - Service, update and re-tag expired (July 2020 ) Ansul kitchen fire suppression system. Implement service PM plan to update every 6-mos as required bit IFC/ FEMS Inspector. |
J.O. WILSON ELEMENTARY SCHOOL | 674713 | Grounds | K Street West Ext door Ground | Grounds Issue: ? Grass Assignment Description: Sink Hole - Please fill |
J.O. WILSON ELEMENTARY SCHOOL | 669564 | Heating | Outside/storage room | Technical is needed to investigate and make repair at following location urgent Repair/replace ruptured pipe hot water supply line leaking . You Assistant is needed |
J.O. WILSON ELEMENTARY SCHOOL | 593787 | Playground (Exterior Services) | PLAYGROUND EQUIPMENT | SEVERAL PIECES OF EQUIPMENT NEED TO BE SERVICED ECE Playground: There is a large crack in the slide that is hazardous and there is a missing step on the monkey bars. Has been cited by OSSE inspection. POC Tony Rich @ 2024121713 |
J.O. WILSON ELEMENTARY SCHOOL | 673818 | Window | West Entrance | Window Issue: ? Below 8 feet /1 story ? Window Glass ? Broken ? null Assignment Description: Replace shattered lower panel window |
J.O. WILSON ELEMENTARY SCHOOL | 614486 | Fire Sprinkler | whole bldg | sprinkler inspections |
JEFFERSON MIDDLE SCHOOL | 625821 | Lock and Door | 134, 301, 219, 234, 210, 205 208, 207, | The door glass is cracked in each of these classrooms 134, 301, 219, 234, 210, 205 208, 207, |
JEFFERSON MIDDLE SCHOOL | 631800 | Lock and Door | 143 | Lock and Door Issue: ? Door ? Metal Door ? Repair/Replace/Install Door/Door Frame ? null Assignment Description: The glass in the door is cracked. This is room 143 |
JEFFERSON MIDDLE SCHOOL | 631801 | Lock and Door | 147 | Lock and Door Issue: ? Door ? Metal Door ? Repair/Replace/Install Door/Door Frame ? null Assignment Description: The door glass in from 147 is cracked |
JEFFERSON MIDDLE SCHOOL | 678489 | Outlet | 222 and 320 | Outlet Issue: ? Repair Outlet ? The conduit is not exposed Assignment Description: Need special outlet for Sharp copiers in both rooms. there is a "regular" outlet. we need it switched. They should be near the existing data port to allow for network connectivity. |
JEFFERSON MIDDLE SCHOOL | 621304 | Building Structural (Interior Services) | 225 | This school is still under warranty by the contractor, please forward to capital construction. Glass was broken due to contractor, glass is being order under them. |
JEFFERSON MIDDLE SCHOOL | 626231 | Lock and Door | 228 | the door glass is cracking |
JEFFERSON MIDDLE SCHOOL | 678502 | Lighting | 2nd floor hallway | Lighting Issue: ? Interior Lights ? Above 8 feet ? Hallway ? null Assignment Description: The lcd light is not working. |
JEFFERSON MIDDLE SCHOOL | 657162 | Building Structural (Interior Services) | 302 | Leak Issue: ? Ceiling Assignment Description: Water Leak//water coming in thru window seal |
JEFFERSON MIDDLE SCHOOL | 638426 | Building Structural (Interior Services) | 305 | crack in door glass of classroom 305 building under warranty need to go to capital construction |
JEFFERSON MIDDLE SCHOOL | 681501 | Leak | Boiler room | Leak Issue: ? Pipe / Line / Drain Assignment Description: Leak on the domestic water line. |
JEFFERSON MIDDLE SCHOOL | 678512 | Cooling | building | Cooling Issue: ? Temperature ? Too Cold Assignment Description: it is very cold in the building. staff and students are complaining even with sweaters on. Can the set point be changed to make the building warmer. We were told it is only something that can be done by DGS remotely |
JEFFERSON MIDDLE SCHOOL | 682070 | Interior Painting & Wall Issue | Cafeteria | These Tiles NEed to be changed Fingers cut |
JEFFERSON MIDDLE SCHOOL | 680641 | Environmental | cafeteria | Environmental Issue: ? Air Quality ? Air Filters Assignment Description: We have 6 air purifiers that are not working properly. |
JEFFERSON MIDDLE SCHOOL | 666902 | Heating | Cafeteria and Kitchen | Heating Issue: ? Temperature ? Too Cold Assignment Description: The space are not heating up to temperature. They are cold, making it hard for staff to work, make food for students. |
JEFFERSON MIDDLE SCHOOL | 634664 | Lock and Door | classroom 138 | Lock and Door Issue: ? Door ? Metal Door ? Repair/Replace/Install Door/Door Frame ? null Assignment Description: The door glass of room 138 is cracked |
JEFFERSON MIDDLE SCHOOL | 626840 | Building Structural (Interior Services) | classroom 203 | glass door is crack and need a glass contractor to replace the glass. Door glass is broken |
JEFFERSON MIDDLE SCHOOL | 680952 | Fire Extinguisher | Fire Marshall says all the steamers need t0 be tagged | Fire Marshall says all the steamers need t0 be tagged |
JEFFERSON MIDDLE SCHOOL | 662103 | Interior Painting & Wall Issue | first floor student restrooms | Interior Painting & Wall Issue: ? Patching & Painting ? Caulking Assignment Description: The soap dispensers are broken and we need new ones installed (total of 2) |
JEFFERSON MIDDLE SCHOOL | 643950 | FLOORING | Gym | Flooring Issue: ? Wood ? Repair/Replace -Broken/Cracked/Damaged Assignment Description: The Gym is rented out to local groups within the community and the last group that rented out the gym caused damaged to the floor by removing the volleyball post and caused the wooden floors to lift. Now there is a hazardous hole in the middle that was caused by a user with a building use agreement with Reality (DC Fray) This is a hazard to our students, staff and users from the community. timeline 02/27/2020 |
JEFFERSON MIDDLE SCHOOL | 676513 | Fire Extinguisher | Kitchen | Jefferson MS (VAMP Emergency Priority I/Emergency Repair) IFC 904.12.6.2 Operation and Maintenance (Inspection/Testing) ? Kitchen Ansul Suppression system Kitchen ? Service update and re-tag expired (Aug 2020) Ansul kitchen fire suppression system. Implement service PM plan to update every 6-mos as required bit IFC/ FEMS Inspector. Extinguishing system service: Automatic fire-extinguishing systems shall be serviced at least every six months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. FEMS LVL-2 |
JEFFERSON MIDDLE SCHOOL | 666998 | Fire Extinguisher | L05 Office | Jefferson MS (VAMP Routine Priority III/Routine Repair) IFC 901.6 Inspection, Testing & Maintenance - Fire Extinguishers Room L05 Office - Service, update and re-tag all expired (April 2019) ABC portable fire extinguisher. FEMS Lvl-2 |
JEFFERSON MIDDLE SCHOOL | 627730 | Building Structural (Interior Services) | l24 | The tile on the wall to the left is broken only due to the installation was not install correct. we found that the tile pcs are hollow behind them. this need to go back to CCT |
JEFFERSON MIDDLE SCHOOL | 673199 | Window | Need to be fix | Window Issue: ? Below 8 feet /1 story ? Window Glass ? Broken ? null Assignment Description: |
JEFFERSON MIDDLE SCHOOL | 664792 | Lock and Door | Outside | Lock and Door Issue: ? Lock/Latch ? Automatic Door ? Locksmith ? null Assignment Description: Key card don't work need a locksmith |
JEFFERSON MIDDLE SCHOOL | 628957 | Fence and Gate | parking area | The bollards in front of the staff parking are not secured correctly |
JEFFERSON MIDDLE SCHOOL | 677208 | Parking Lot | Parking Lot | The parking lot gate has a malfunction |
JEFFERSON MIDDLE SCHOOL | 664559 | Heating | Roof | Heating Issue: ? Heating Unit ? Too Cold Assignment Description: Repair/replace inoperable fan on RTU #1. Serves lower level of facility. Level without heat. BPO Wright 202-345-7587 |
JEFFERSON MIDDLE SCHOOL | 642588 | Athletic Field | Tennis Courts | Athletic Facility Issue: ? Tennis Court ? Field Repair Assignment Description: Court crack repair needed. Cracks on the playing surface are starting to get larger in size and will compromise the integrity of the asphalt if not repaired. |
JEFFERSON MIDDLE SCHOOL | 679936 | Athletic Field | Tennis Courts | Athletic Facility Issue: ? Tennis Court ? Grass/Weed Removal Assignment Description: There are giant weeds and shrubs growing across the entry gate to the tennis courts, on the sides of the perimeter fencing, and on the smaller tennis court towards the building there are branches that stick out making it impossible to use the court. See attached pictures. Removal requested please. Thank you |
JEFFERSON MIDDLE SCHOOL | 676514 | Fire Extinguisher | Various | Jefferson MS (VAMP Priority III/Routine Repair) IFC 901.6 Inspection, Testing & Maintenance Maintenance service required - inspect and test portable ABC fire extinguishers in the following locations; . ; . ? Corridor next to room 307 ? Inspect, service and re-tag untagged portable ABC fire extinguishers. ? Corridor near room L42 ? Inspect, service and re-tag untagged portable ABC fire extinguisher. ? Corridor near cafeteria next to room L05 office - Service, inspect and test expired (Aug 2019) portable ABC fire extinguisher. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer?s installation instructions. FEMS Lvl-2 |
LUDLOW-TAYLOR ELEMENTARY SCHOOL | 674620 | Window | 103 | Room 103 on the 1st floor outside window has is cracked. |
LUDLOW-TAYLOR ELEMENTARY SCHOOL | 661177 | Leak | 132,hall,kitchen | Leak Issue: ? Ceiling Assignment Description: Ceiling leaks when it rain across room 132(after care storage),hall,kitchen,to the back door. Think it?s a roof problem. |
LUDLOW-TAYLOR ELEMENTARY SCHOOL | 668011 | Building Structural | 3rd Floor | Structural Issue: ? Wall Assignment Description: Toilet paper dispenser and tile was set on fire |
LUDLOW-TAYLOR ELEMENTARY SCHOOL | 665382 | Building Structural (Interior Services) | Baseball field | Fence and Gate Issue: ? Fence Only ? Repair Fence Assignment Description: Hole in the fence on Morrison Pl. baseball field. |
LUDLOW-TAYLOR ELEMENTARY SCHOOL | 657972 | Playground | Basketball court | Playground Issue: ? Grounds/Fence/Turf ? Turf Assignment Description: The basketball court on the playground has cracks in the ground. |
LUDLOW-TAYLOR ELEMENTARY SCHOOL | 664542 | Pipe | Boiler | Pipe Issue: ? Water ? Leak Assignment Description: Boiler room room pipe is leaking from the ceiling |
LUDLOW-TAYLOR ELEMENTARY SCHOOL | 673626 | Fire Extinguisher | Boiler Room and Kitchen | Ludlow-TaylorES (VAMP Priority III/Routine Repair) IFC 901.6 Inspection, Testing & Maintenance Expired fire extinguishers ? Boiler Room below stairs inside fire extinguisher cabinet ? Service and update expired (June 2019) portable fire extinguisher. Remove the entire fire extinguisher cabinet and re-locate and anchor mount on masonry wall near exterior exit door. IFC 906.7 Hangers and brackets. Mount fire extinguishers in the following locations; ? Kitchen - Provide and mount K-class fire extinguisher on masonry wall as required by the FEMS Inspector. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer?s installation instructions. FEMS Lvl-2 |
LUDLOW-TAYLOR ELEMENTARY SCHOOL | 673625 | Fire Extinguisher | Kitchen | Ludlow-Taylor ES (VAMP Emergency Priority I/Emergency Repair) IFC 904.12.6.2 Operation and Maintenance (Inspection/Testing) ? Kitchen Ansul Suppression system Kitchen ? Service update and re-tag expired (Sept 2020). (Note: Service Tags were scribed ?Lincoln? oppose to Langley.) Ansul kitchen fire suppression system. Implement service PM plan to update every 6-mos as required bit IFC/ FEMS Inspector. Extinguishing system service: Automatic fire-extinguishing systems shall be serviced at least every six months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. FEMS LVL-2 |
LUDLOW-TAYLOR ELEMENTARY SCHOOL | 664911 | Window | Library 310 | Window Issue: ? Above 8 feet/1 Story ? Window Glass ? Repair/Replace/Install ? null Assignment Description: Library window cracked.Room 310 3rd floor |
LUDLOW-TAYLOR ELEMENTARY SCHOOL | 660749 | FIRE ALARM | Lobby | Fire Alarm Issue: ? Panel Assignment Description: Fire alarm panel has trouble signal flashing.. |
LUDLOW-TAYLOR ELEMENTARY SCHOOL | 682650 | Cooling | Room 208 | Cooling Issue: ? AC Unit ? Too Hot Assignment Description: AC is not working. |
LUDLOW-TAYLOR ELEMENTARY SCHOOL | 664899 | Lighting | Several | Lighting Issue: ? Interior Lights ? Below 8 feet ? Room(s)/Auditorium/Gymnasium ? null Assignment Description: Need light covers in classrooms,closets,hallway,and bathrooms. Pictures attached with room numbers and covers. |
MAURY ES | 651697 | Building Structural (Interior Services) | 103B | Window Issue: ? Below 8 feet /1 story ? Window Glass ? Repair/Replace/Install ? null Assignment Description: Broken window need contract services to provide a glass company to install new glass. |
MAURY ES | 662421 | Window | 108 Principals Office | Window Issue: ? Below 8 feet /1 story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Window wont open because handle is broken. Principal is working on site and would like ventilation for covid protection. |
MAURY ES | 673898 | Fire Alarm (Life Safety Services) | 126 | ? Wall Assignment Description: Fire alarm strobe lights cover missing |
MAURY ES | 659577 | Building Structural | 137 Art Room | Structural Issue: ? Ceiling Assignment Description: Same leak from modernization. |
MAURY ES | 631517 | Lock and Door | 138C | Lock and Door Issue: ? Door ? Standard Door ? Repair/Replace/Install Door/Door Frame ? null Assignment Description: Modernization: Kitchen Dry Storage Room never had glass put in the door. |
MAURY ES | 651622 | Lock and Door | 13th Street Entrance | Lock and Door Issue: ? Lock/Latch ? Handicap Entrance/Door ? Repair/Replace/Install Door/Door Frame ? null Assignment Description: ADA door does not shut all the way |
MAURY ES | 659579 | Building Structural | 211 Ms Battle Room | Structural Issue: ? Ceiling Assignment Description: Water leak ceiling. |
MAURY ES | 651605 | Building Structural | 216 | Structural Issue: ? Ceiling Assignment Description: WAP and wire hanging from ceiling |
MAURY ES | 662411 | Window | 302, 303 | Window Issue: ? Below 8 feet /1 story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Blinds were not installed with modernization like the other classrooms. The picture shows one window with and one without. |
MAURY ES | 659580 | Building Structural | 327 | Structural Issue: ? Wall Assignment Description: Water leak from modernization in corner office. |
MAURY ES | 676140 | Lighting | 3rd floor hall historic | Lighting Issue: ? Interior Lights ? Above 8 feet ? Hallway ? null Assignment Description: New light out. Dont know if its bulb, ballast? Foreman doesnt know how to change. |
MAURY ES | 662577 | Heating | 3rd floor multiple rooms | Heating Issue: ? Thermostat ? Too Cold Assignment Description: Thermostats are blinking. Temp in the 60s. |
MAURY ES | 636304 | Outlet | Art Room | Outlet Issue: ? Repair Outlet ? The conduit is not exposed Assignment Description: Modernization: Kiln never worked. Outlet needs to be tested. All three wires have to carry proper current. They are at 114 volts. They need to each be 208 per SKUTT which is manufacturer of the kiln. |
MAURY ES | 670586 | Playground | Basketball court | Playground Issue: ? Equipment ? Repair/Remove/Replace Equipment Assignment Description: Basketball Stand/hoop broken |
MAURY ES | 630677 | Window | Cafeteria | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Modernization: Electronic blinds dont close. |
MAURY ES | 681562 | Building Structural | Cafeteria | Structural Issue: ? Partition Assignment Description: Partition Wall installed with modernization has broken several times. It will not move. |
MAURY ES | 676136 | Ceiling | cafeteria by art room | Ceiling Issue: ? Damaged Tiles Assignment Description: Roof Leak |
MAURY ES | 670506 | Building Structural | Cafeteria ceiling above PE office | Structural Issue: ? Ceiling Assignment Description: Leak in ceiling and its caused damage to bricks below it. I cant tell if bricks are dangerously loose. |
MAURY ES | 670587 | MASONRY | Exterior Building Wall | Masonry Issue: ? Wall ? Tile Assignment Description: Panels of modernization exterior wall have been damaged. |
MAURY ES | 673502 | Building Structural (Interior Services) | Exterior Perimeter | Window Issue: ? Below 8 feet /1 story ? Window Glass ? Broken ? null Assignment Description: The two windows are located on the 12th Place side of the building, right at the corner of 12th Place and Constitution Ave NE. Both windows remain intact, however, they are visibly damaged and can possibly be broken inwards if not fixed in a timely manner. The windows are located on the ground floor. I completed my perimeter check with negative results, the building is secure. need contract service to repair with a glass contractor. |
MAURY ES | 662548 | Building Structural (Interior Services) | First floor hall by room 127 | Flooring Issue: ? Tile ? Repair/Replace Assignment Description: Tile coming up building is still under warranty |
MAURY ES | 634994 | Building Structural | Library | Structural Issue: ? Ceiling Assignment Description: Modernization: Did not install an intercom. Communication does not happen between library and main office. Unsafe for student tracking, lockdown scenarios, and teacher information. |
MAURY ES | 675845 | Cooling | Library | Repair/Replace inoperable t-stats in the library, 3rd floor historic hallway and room 316, areas are without extremely hot. |
MAURY ES | 651610 | Building Structural | Main Entrance | Structural Issue: ? Ceiling Assignment Description: Vent hole needs a cover |
MAURY ES | 663854 | Heating | Main Entrance Lobby | Heating Issue: ? Heating Unit ? Too Cold Assignment Description: The individual heater is not working. This is where the Nurses take temperatures of students coming in the building. Its cold in that section and the heater wont turn on. |
MAURY ES | 674073 | Lock and Door | Maury ES | ? New Key(s) Replace Key(s) Assignment Description: Council has a requested hose bibb and water keys for Maury ES so that the school community can water the trees and plants there. |
MAURY ES | 675300 | Cooling | Rooftop Units and classrooms | BMS to make adjustments to the cooling setpoints, setpoints kept changing back from 72 degrees to 81 degrees. I also found several compressors on the Roof Top Units that were in alarm as well (see picture).....please provide Contractor support to address the cooling issues at Maury. Classrooms 327, 326, 324, 323, 322, 320, 319, 315, Hallway 328, Stairway 1. |
MAURY ES | 666785 | Window | room 302 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Window leaking. You can see water stains on white top surface. Starting in the Southwest corner of the room, its the third window. |
MAURY ES | 666786 | Building Structural | room 302 | Structural Issue: ? Wall Assignment Description: Window blinds were not installed with new building in this room. All other rooms have shades. |
MAURY ES | 669821 | Building Structural | School flag pole broken: The wire that hangs/holds the flag broke inside the pole. | Structural Issue: ? Floor/Ground Assignment Description: School flag pole broken: The wire that hangs/holds the flag broke inside the pole. |
MAURY ES | 670764 | Heating | Several Rooms | Heating Issue: ? Thermostat ? Too Hot Assignment Description: Something happened over the weekend. Many thermostats are not cooling. Its 80 degrees in some rooms |
MAURY ES | 634995 | Sidewalks | Sidewalk on 13th Street NE | Sidewalk Issue: ? Concrete Pavement ? Broken Damaged Assignment Description: Modernization: Storm grate that was installed is not safe for kids and animals. Community is upset and complaining kids and animals have to walk into the street |
MAURY ES | 659578 | Building Structural | Stair 1 | Structural Issue: ? Wall Assignment Description: Stairwell leak since modernization. |
MAURY ES | 670504 | Building Structural | Whole school | Structural Issue: ? Wall Assignment Description: Clocks need to be recalibrated. They are not showing correct time. |
MAURY ES | 670584 | Hot Water | Whole school | Hot Water Issue: ? Temperature Assignment Description: Faucets do not get hot. They also dont run long enough to wash hands. |
MAURY ES | 670505 | Building Structural | Whole school: BELLS | Structural Issue: ? Wall Assignment Description: The bell schedule needs to be changed to 8:30am, 8:45am, 3:15am |
MINER ELEMENTARY SCHOOL | 672550 | Window | Cafeteria exterior door | Window Issue: ? Below 8 feet /1 story ? Window Glass ? Broken ? null Assignment Description: Bottom glass on cafeteria door looked like it was kicked and is now broken. |
MINER ELEMENTARY SCHOOL | 677838 | Leak | Cafeteria Kitchen | Leak Issue: ? Sink Assignment Description: Sink leaking from filter |
MINER ELEMENTARY SCHOOL | 680069 | Cooling | Entire building | Cooling Issue: ? AC Unit ? No AC Assignment Description: The AC unit has not been working consistently for the past 3 days. |
MINER ELEMENTARY SCHOOL | 655459 | Fence and Gate | K-5 Playground | Fence and Gate Issue: ? Gate ? Repair Gate Assignment Description: There are two current issues. 1) students are able to stand on the hand railing and jump up and over the fence which has caused a problem with vandalism on the playground regularly. 2) the gate now has two cut-outs above the push bar that need to be repaired on both gates - 15th st and 16th street. To remedy this we need the mesh on the gate fixed and we are asking that the fence surrounding the door be raised another several feet to make it impossible to climb over. |
MINER ELEMENTARY SCHOOL | 572107 | OTHER MASONRY | Outside Structur | The expansion joints at the base of the school near the front entrance and the concrete sidewalk have deteriorated allowing water and ice to get underneath. This corroded caulking is present around the entire building structure. The many openings are large crevices pose a safety hazard for children foot traffic and hands possibly being injured. The openings also provide rodents locations to nest and mate within a very close proximity of the school and students. |
MINER ELEMENTARY SCHOOL | 672549 | Playground | Playground on the left side of the building | Playground Issue: ? Equipment ? Repair/Remove/Replace Equipment Assignment Description: One of the anchors of the swing came off. |
MINER ELEMENTARY SCHOOL | 674062 | Grounds | Playgrounds | Remove small rock beds from ECE & 3-5 Playgrounds please. 5 small rock beds |
MINER ELEMENTARY SCHOOL | 666232 | Roof | Roof/drain by loading dock. Room 167 | Roof Issue: ? Water Leak ? Rooftop Assignment Description: Custodian office is leaking. Foreman checked roof, noticed a thick sheet of ice over drain. Water is sitting |
MINER ELEMENTARY SCHOOL | 679584 | Cooling | Rooftop | The Chiller goes into alarm saying Evaporator Flow Switch Alarm |
MINER ELEMENTARY SCHOOL | 682278 | Cooling | Rooftop area | It was reported by the Protech Contractor that #2 Compressor on the Chiller is bad and it needs replacing |
MINER ELEMENTARY SCHOOL | 679168 | Leak | Room 140; Workroom in the library | Leak Issue: ? Ceiling Assignment Description: The ceiling has been leaking. The drain is above this room |
MINER ELEMENTARY SCHOOL | 673900 | Fire Sprinkler | Sprinkler Room | Miner ES (VAMP Emergency Priority I/Emergency Repair) IFC 907.8.5 - Inspection, testing and maintenance IFC 903.5 - Testing and maintenance: Sprinkler systems shall be tested and maintained in accordance with Section 901. Throughout Building ing (The sprinkler pressure is low, and shall be address immediately. The building owner shall be responsible to maintain the fire and life safety systems in an operable condition at all times. Service personnel shall meet the qualification requirements of NFPA 72 for inspection, testing and maintenance of such systems. Records of inspection, testing and maintenance shall be maintained. |
MINER ELEMENTARY SCHOOL | 660614 | FIRE ALARM | Throughout | Fire Alarm Issue: ? Fire Code (IFC) Assignment Description: Minor ES (VAMP Emergency Priority I/Emergency Repair) IFC. 907.8.5 - Inspection, testing and maintenance: Fire Alarm in trouble mode Fault command indicates Second floor zone 1 duct & smoke detector Mechanical room air handler unit -4. Abatement repairs are required immediately by the FEMS Inspector. Service, repair and test fire alarm system and provide copies of service maintenance documentation and records for review as required by the FEMS Inspector. The building owner shall be responsible to maintain the fire and life safety systems in an operable condition at all times. Service personnel shall meet the qualification requirements of NFPA 72 for inspection, testing and maintenance of such systems. FEMS Lvl-2 |
MINER ELEMENTARY SCHOOL | 682101 | Cooling | Whole building | Cooling Issue: ? AC Unit ? Central Air Assignment Description: AC unit (chiller) went out. The building is humid. Floors, doors, countertops are sweating due to no air /humidity. |
MINER ELEMENTARY SCHOOL | 672630 | Building Structural (Interior Services) | Window is stairwell between the Orange and Blue hallway | Window Issue: ? Above 8 feet/1 Story ? Window Glass ? Broken ? null Assignment Description: Both windows are cracked. windows need to be replace by a glass contractor |
PAYNE ELEMENTARY SCHOOL | 676183 | Building Structural (Interior Services) | 3rd floor staircase-1 | Payne ES. VAMP High Priority II/Priority Repair) IFC 1010.1.9.1 ? Damaged Hardware IFC 703.2.3 - Door operation 3rd floor stair #1 ? Fire exit door not latching/closing properly. Repair internal vertical rod and latch on right door. Right exit door closer arm detached; reattach arm to closer track; adjust hinges realign both doors. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. FEMS Lvl-2 From Craft Person Assignment: Forward this work order to contract services to repair double doors with panic exit devices with Internal vertical rods @Andre Thompson @Randolph Tobin @Antonio Simms |
PAYNE ELEMENTARY SCHOOL | 677451 | Building Structural (Interior Services) | 3rd floor staircase-2 | Payne ES. VAMP High Priority II/Priority Repair) IFC 1010.1.9.1 ? Damaged Hardware IFC 703.2.3 - Door operation 3rd floor staircase-2 ? Door not latching/closing properly. Repair internal vertical rod and latch on right door. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. FEMS Lvl-2 need Contract service to replace or repair the interior rods of the door. |
PAYNE ELEMENTARY SCHOOL | 670808 | Building Structural | All Stairwells | Structural Issue: ? Wall Assignment Description: Repair crumbling plaster walls - all stairwells |
PAYNE ELEMENTARY SCHOOL | 678762 | Interior Painting & Wall Issue | BES Room, Payne ES | Interior Painting & Wall Issue: ? Patching & Painting ? Painting Maintenance Assignment Description: There are 4 walls where drywall was hung. The drywall needs to be taped, mudded, sanded, and then painted to be finished. |
PAYNE ELEMENTARY SCHOOL | 616923 | FLOORING | Cafeteria Floor | please repair floor tiles |
PAYNE ELEMENTARY SCHOOL | 676386 | Pipe | Exterior, 14th Street, Outside Media Center | Pipe Issue: ? Valve ? Installation Assignment Description: The bib is not functioning. We need it to be functional for watering, cleaning, and operation of school science program. |
PAYNE ELEMENTARY SCHOOL | 680913 | MASONRY | Exterior, 14th street side | Masonry Issue: ? Walkway ? Tile Assignment Description: The sidewalk is broken and a hazard. It needs to be removed to make room for a community garden. |
PAYNE ELEMENTARY SCHOOL | 676390 | Sidewalks | Exterior, Sidewalk, 14th Street Side of building | Sidewalk Issue: ? Concrete Pavement ? Broken Damaged Assignment Description: The sidewalk is destroyed. |
PAYNE ELEMENTARY SCHOOL | 654718 | FIRE ALARM | First floor | Fire Alarm Issue: ? Repair Assignment Description: Troubleshoot and repair fire alarm. POC: 439-8271 |
PAYNE ELEMENTARY SCHOOL | 679596 | Roof | Front Entrance Overhang | Roof Issue: ? Roof Damage Assignment Description: There is clear and obvious water damage indicating a leak in the roof. |
PAYNE ELEMENTARY SCHOOL | 625049 | Lock and Door | Front Lobby Door | The front lobby middle door inside is not locking properly with the door handle. The small bar is not locking the door. |
PAYNE ELEMENTARY SCHOOL | 676109 | Cooling | Ms. Baggett's Room, 136 | Cooling Issue: ? AC Unit ? Central Air Assignment Description: The air conditioning unit stopped working. |
PAYNE ELEMENTARY SCHOOL | 675105 | Cooling | RM#136 | Classroom not cooling thermostat blinking code CH05 |
PAYNE ELEMENTARY SCHOOL | 676048 | Fire Extinguisher | Room 134 Kindergarten | Payne ES (VAMP Priority III/Routine Repair) IFC 901.6 Inspection, Testing & Maintenance Room 134 Kindergarten ? Service, inspect expired (July 2019) portable ABC fire extinguisher. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer?s installation instructions. FEMS Lvl-2 |
PAYNE ELEMENTARY SCHOOL | 654950 | Roof (Exterior Services) | Throughout | NOTE:Roof leaking when it rains, customer requesting that the roof repaired be for we install ceiling tiles, this is the 3rd time tiles have been replaced. Ceiling Tiles missing throughout the school, ceiling tiles need to be repaired/replaced |
PEABODY ELEMENTARY SCHOOL | 653886 | Interior Painting & Wall Issue | 1,2,3,basement floor lobby | Interior Painting & Wall Issue: ? Patching & Painting ? Repaint Assignment Description: The walls need to be repainted. |
PEABODY ELEMENTARY SCHOOL | 655667 | Window(Interior Services) | 2nd floor | Ceiling Issue: ? Damaged Tiles Assignment Description: The classroom ceiling is leaking water//Water is coming thru around window frame when it rain |
PEABODY ELEMENTARY SCHOOL | 618135 | Lock and Door | 5 street side exit door. | The handicap access door push button is not working |
PEABODY ELEMENTARY SCHOOL | 655834 | Building Structural | All Levels | Structural Issue: ? Wall Assignment Description: Water clean up |
PEABODY ELEMENTARY SCHOOL | 658208 | Building Structural (Interior Services) | Back door landing by play ground | Flooring Issue: ? Tile ? Broken/Cracked/Damaged The floor is not a tile floor but its painted, ticket has been forward to the paint shop. Assignment Description: Floor needs repair |
PEABODY ELEMENTARY SCHOOL | 665154 | Power | Building | Power Issue: ? Complete Outage ? The emergency lights are working Assignment Description: Cut,Cap, Make safe basement electrical. |
PEABODY ELEMENTARY SCHOOL | 654829 | Fire Sprinkler | Fire Sprinkler | Fire Sprinkler Issue: ? Maintenance Assignment Description: Repair water gauge & relocate sprinkler head |
PEABODY ELEMENTARY SCHOOL | 611685 | Window | Library | There are 10 electrical window shades that will not got up . |
PEABODY ELEMENTARY SCHOOL | 652232 | Lighting | Outside | Lighting Issue: ? Exterior Lights ? Above one (1) story ? Outside/Building/Street/Parking Lot ? null Assignment Description: the large light in the alley that's attached to the building, that covers the perimeter of the alley is not working, this work order is not a duplicate of work order # 617950 this is a different outside light. |
PEABODY ELEMENTARY SCHOOL | 629680 | Railing and Step | Outside alley | The railing located by the boiler room steps are in danger of failing. |
PEABODY ELEMENTARY SCHOOL | 647942 | Railing and Step | OUT SIDE ALLEY 5 STREET SIDE | Railing and Step Issue: ? Rail Assignment Description: The railing next to the boiling room step is in danger of falling down the steps. |
PEABODY ELEMENTARY SCHOOL | 655832 | Building Structural | Third Floor | Structural Issue: ? Wall Assignment Description: Structural assessment of fire |
SCHOOL WITHIN SCHOOL @ GODING | 642781 | Electronic Security Issue | 407 | Electronic Security Issue: ? Not Working Assignment Description: the telephone will not come on getting no power |
SCHOOL WITHIN SCHOOL @ GODING | 614216 | Fire Extinguisher | all building | kitchen suppression system inspection |
SCHOOL WITHIN SCHOOL @ GODING | 651354 | Pipe | Boiler room ground floor | Pipe Issue: ? Water ? Leak Assignment Description: main water line continue to leak a new situation from the one in the past critical |
SCHOOL WITHIN SCHOOL @ GODING | 622915 | Fire Sprinkler | building | Repair fire sprinkler system |
SCHOOL WITHIN SCHOOL @ GODING | 611802 | Switch | Cafeteria | Switch in panel box is trip for the handicap lift to operate |
SCHOOL WITHIN SCHOOL @ GODING | 659707 | FIRE ALARM | CARE Room 101 | Fire Alarm Issue: ? Repair Assignment Description: Verification of Fire Alarm Phone Line |
SCHOOL WITHIN SCHOOL @ GODING | 635296 | Environmental | Custodial storage room ground | Environmental Issue: ? Fire ? Fire Code Assignment Description: On the ground Florida pull station for the alarm and foddrill the battery is dead critical |
SCHOOL WITHIN SCHOOL @ GODING | 673375 | FIRE ALARM | fire alarm repair phone dialers | Fire Alarm Issue: ? Repair Assignment Description: fire alarm repair phone dialers |
SCHOOL WITHIN SCHOOL @ GODING | 651759 | Building Structural | Room oo5 | Structural Issue: ? Wall Assignment Description: ground floor everytime it rain water comes through the wall causing structural damage |
SCHOOL WITHIN SCHOOL @ GODING | 671976 | Grounds | Trailer number 4 | Front door will not open can not unlock the door |
SEATON ELEMENTARY SCHOOL | 682528 | Lighting | 107 | Lighting Issue: ? Interior Lights ? Above 8 feet ? Room(s)/Auditorium/Gymnasium ? null Assignment Description: I changed all the lights and two of them keep going back out. Ballast |
SEATON ELEMENTARY SCHOOL | 675576 | Cooling (HVAC Services) | 108 | Leak Issue: ? Pipe / Line / Drain Assignment Description: Leaking from pipe in the ceiling // This is the HVAC condensate problem refer to HVAC |
SEATON ELEMENTARY SCHOOL | 659608 | Heating | 1st fl cafeteria/ multi purpose rm | Heating Issue: ? Heating Unit ? Too Cold Assignment Description: Leak on supply heating line for AHU |
SEATON ELEMENTARY SCHOOL | 664360 | Interior Painting & Wall Issue | 2025829279 | Interior Painting & Wall Issue: ? Painitng ? Repaint Assignment Description: Radiator cover rusty may harm kids need to be replaced |
SEATON ELEMENTARY SCHOOL | 682544 | Cooling | 205 2nd floor | Cooling Issue: ? Thermostat ? Too Hot Assignment Description: A/C unit blowing out warm air |
SEATON ELEMENTARY SCHOOL | 674093 | Interior Painting & Wall Issue | 2nd floor boys restroom | Interior Painting & Wall Issue: ? Painitng ? Painting Maintenance Assignment Description: Very rusty need to be painted |
SEATON ELEMENTARY SCHOOL | 675561 | Cooling (HVAC Services) | 2nd floor girls restroom | Leak Issue: ? Source Unknown Assignment Description: Leaking from ceiling // This is an HVAC condensate problem refer to HVAC department |
SEATON ELEMENTARY SCHOOL | 671675 | Ceiling | 2nd floor Storage Room | Seaton ES (VAMP High Priority II/Priority Repair) IFC 703.3 Ceilings-Maintenance/Opening Protectives Second floor Storage room ? Patch, resurface and paint several breach holes around pipe penetrations on plaster ceiling surface. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be visually inspected by the owner annually and properly repaired, restored or replaced when damaged, altered, breached or penetrated. FEMS Lvl-2 |
SEATON ELEMENTARY SCHOOL | 676669 | Cooling | 309 | Cooling Issue: ? AC Unit ? Too Hot Assignment Description: Both a/c unit blowing out warm air |
SEATON ELEMENTARY SCHOOL | 675563 | Cooling (HVAC Services) | Boiler room | Leak Issue: ? Pipe / Line / Drain Assignment Description: Leaking from pipe causing water to settle on the floor //This is the HVAC condensate problem refer to HVAC |
SEATON ELEMENTARY SCHOOL | 678435 | Pipe | Boiler room | Pipe Issue: ? Water ? Installation Assignment Description: Replace water treatment system |
SEATON ELEMENTARY SCHOOL | 624904 | Ceiling | cafeteria | everytime it rain it leaks |
SEATON ELEMENTARY SCHOOL | 665496 | Heating | Cafeteria | Heating Issue: ? Heating Unit ? Too Cold Assignment Description: AHU has control issue |
SEATON ELEMENTARY SCHOOL | 678414 | Cooling | Cafeteria | Cooling Issue: ? AC Unit ? HVAC Leak Assignment Description: Leaking from ceiling causing puddles of water |
SEATON ELEMENTARY SCHOOL | 663725 | Heating | Conference room | Heating Issue: ? Heating Unit ? Too Cold Assignment Description: Univent blowing out cold air |
SEATON ELEMENTARY SCHOOL | 678505 | Heating | First Floor Boy's Bathroom | Heating Issue: ? Heating Unit ? No Heat Assignment Description: Uninstalled unit sitting in front of old, broken unit |
SEATON ELEMENTARY SCHOOL | 668874 | Fence and Gate | Front of building | Fence and Gate Issue: ? Gate ? Repair Gate Assignment Description: Someone ran into gate causing it to break |
SEATON ELEMENTARY SCHOOL | 676033 | Cooling | IT room 3rd floor | Cooling Issue: ? AC Unit ? Too Hot Assignment Description: Too hot unit not working |
SEATON ELEMENTARY SCHOOL | 644539 | Roof (Exterior Services) | Kitchen | Leak Issue: ? Roof Assignment Description: The Plumbers abated this concern and determined that they Investigated complaint of water leaking from ceiling after close check found leak not coming from any water feed, this appears to be coming from the roof. |
SEATON ELEMENTARY SCHOOL | 671678 | Fire Extinguisher | Kitchen | Seaton ES. VAMP Emergency Priority I/Emergency Repair) IFC 904.12.6.2 Operation and Maintenance (Inspection/Testing) ? Kitchen Ansul Suppression system Kitchen - Service, update and re-tag expired (July 2020 ) Ansul kitchen fire suppression system. Implement service PM plan to update every 6-mos as required bit IFC/ FEMS Inspector. Extinguishing system service: Automatic fire-extinguishing systems shall be serviced at least every six months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. FEMS LVL-2 |
SEATON ELEMENTARY SCHOOL | 672370 | Cooling | Kitchen | Cooling Issue: ? AC Unit ? Too Hot Assignment Description: No a/c in kitchen can we get a window unit or portable unit |
SEATON ELEMENTARY SCHOOL | 680252 | Cooling (HVAC Services) | Left side of stage | Leak Issue: ? Source Unknown Assignment Description: Leaking from ceiling source unknown//This is a leak on the air handler unit in the ceiling refer to HVAC |
SEATON ELEMENTARY SCHOOL | 664841 | Heating | Library | Heating Issue: ? Thermostat ? Too Cold Assignment Description: Heat won't come on |
SEATON ELEMENTARY SCHOOL | 675305 | Cooling | Library | Cooling Issue: ? Thermostat ? Too Hot Assignment Description: A/C not working to hot |
SEATON ELEMENTARY SCHOOL | 674792 | Cooling | Main lobby | Water is leaking from under the hallway units |
SEATON ELEMENTARY SCHOOL | 680729 | Outlet | Multipurpose room | Seaton ES (VAMP High Priority II/Priority Repair) IFC 605.6 Unapproved conditions Exposed Wires Multipurpose room left of stage ? Install blank cover plate on ceiling mounted to junction box. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. FEMS Lvl-2 |
SEATON ELEMENTARY SCHOOL | 681251 | Grounds | outside by dumpster | Grounds Issue: ? Bulk Trash Assignment Description: a lot of broken funiture and other item |
SEATON ELEMENTARY SCHOOL | 663307 | Heating | Outside elevator room | Heating Issue: ? Temperature ? Too Cold Assignment Description: No ventilation may cause oil to freeze and stop operation |
SEATON ELEMENTARY SCHOOL | 622684 | Lock and Door | Outside of RM 124 | Unable to enter classroom from the playground using Fob |
SEATON ELEMENTARY SCHOOL | 680929 | Cooling | Room 100C | Cooling Issue: ? Temperature ? Too Hot Assignment Description: AC is not working. |
SEATON ELEMENTARY SCHOOL | 661245 | Cooling | Room 214 | Perform maintenance on the HVAC unit in Room 214, ensuring the source of the leak causing staining has been corrected. |
SEATON ELEMENTARY SCHOOL | 674207 | Cooling | Spanish | Leaking from ceiling when a/c is turned on |
SEATON ELEMENTARY SCHOOL | 662845 | Lock and Door | Stairway #2 | Lock and Door Issue: ? Lock/Latch ? Metal Door ? Repair/Replace/Install Door/Door Frame ? null Assignment Description: When I use my fob key to enter the building the latch is on a 25 min delay causing the door to be unsecured |
SEATON ELEMENTARY SCHOOL | 680250 | Cooling (HVAC Services) | Stairway #2 | Leak Issue: ? Source Unknown Assignment Description: Leaking down wall//This is a Univent leak on the wall refer to HVAC |
SEATON ELEMENTARY SCHOOL | 680728 | Cooling | Various | Seaton ES. (VAMP High Priority II/Priority Repair) IFC 703.3 Ceilings-Maintenance/Opening Protectives Missing ceiling tiles in the library multipurpose room left and right of stage ? HVAC/AHU system and associated pipelines are leaking causing water damage to ceiling tiles. Trash cans and buckets used to collect water is continuous during cooling season The pipe insulation was observed to be saturated with water in several areas. Electrical outlets, light fixtures and conduit lines are also affected.All leaks must be repaired before replacing water damaged & missing acoustical ceiling tiles to satisfy this cited fire code violation. Leaks also continue in the main office and other areas Wasina systems were altered to provide air and ventilation above the ceiling system to no avail. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be visually inspected by the owner annually and properly repaired, restored or replaced when damaged, altered, breached or penetrated. FEMS Lvl-2 |
STUART-HOBSON MIDDLE SCHOOL | 672259 | Cooling | 105D, 105E, Main Office General, Ground Level Hallway, Auditorium,Gym, 109, 111,114, 202, 222, 219, 218, 211, 207 , Nurse Suite, First Floor and Second Floor Hallway | Cooling Issue: ? Temperature ? Too Hot Assignment Description: School is experiencing elevated heat temperatures in classrooms and working spaces: Some spaces are reaching between 85 to 90 degrees. See below 105D, 105E, Main Office General, Ground Level Hallway, Auditorium,Gym, 109, 111,114, 202, 222, 219, 218, 211, 207, Nurse Suite, First Floor and Second Floor Hallway |
STUART-HOBSON MIDDLE SCHOOL | 643859 | Interior Painting & Wall Issue | 1st Floor | Interior Painting & Wall Issue: ? Painitng ? Painting Maintenance Assignment Description: Requesting to have the 1st floor painted a white semi gloss. |
STUART-HOBSON MIDDLE SCHOOL | 664103 | Faucet | 1st floor girls restroom | Faucet Issue: ? Sink ? Repair / Replace Assignment Description: Requesting to have sink caulked and sealed to be back against the wall. |
STUART-HOBSON MIDDLE SCHOOL | 638647 | Building Structural (Interior Services) | 1st Floor Hallway | carpentry has completed this task. for new glass installation need to be completed by contract services. |
STUART-HOBSON MIDDLE SCHOOL | 614321 | Window | 215 | Blinds in Room 215 are off the track and needs to be remounted. |
STUART-HOBSON MIDDLE SCHOOL | 643862 | Interior Painting & Wall Issue | 2nd Floor | Interior Painting & Wall Issue: ? Painitng ? Painting Maintenance Assignment Description: Requesting to have the 2nd floor hallway painted a semi gloss white paint. |
STUART-HOBSON MIDDLE SCHOOL | 682632 | Interior Painting & Wall Issue | 304 | Requesting to have damage baseboard replaced in room 304. |
STUART-HOBSON MIDDLE SCHOOL | 681637 | Cooling | 3rd floor hallway | Requesting to have leak coming from the HVAC unit resolved ASAP before the ceiling collapse. |
STUART-HOBSON MIDDLE SCHOOL | 668407 | Grounds | 4th and E/Outside of School | Grounds Issue: ? Bulk Trash Assignment Description: Requesting Facilities lower Flag sor provide the school a temporary flag crank starting on March 18 until March 22, 2021 in compliance with the Mayor's order. Also, in the event that a flag crank is not able to be loaned, we will need the flag raised back on March 23rd, 2021. Also note, there is no appropriate coding for the issue. Principals and Operations POC?s, At the request of the Mayor, we are asking that you please lower the United States and District of Columbia flags to half-staff until sunset, March 22, 2021 in remembrance of the victims of the shooting in Atlanta. Our hearts and prayers are extended to the families of those who have lost a loved one in this tragedy. If you have any questions or need support, please reach out to your cluster Operations Specialist. Thanks, Patrick Patrick Davis Chief Operating Officer Office of the Chief Operating Officer District of Columbia Public Schools 1200 First Street, NE Washington, DC 20002 C: 202-365-4746 |
STUART-HOBSON MIDDLE SCHOOL | 580164 | Roof (Exterior Services) | Atrium | the roof area over top of the atrium is leaking in mutliplw spots. |
STUART-HOBSON MIDDLE SCHOOL | 674416 | Interior Painting & Wall Issue | Atrium | Requesting to have wood trim put back on to the wall inside of the atrium in the cafeteria. |
STUART-HOBSON MIDDLE SCHOOL | 679289 | Interior Painting & Wall Issue | Atrium | Requesting to have the wood trim around the entrance trim around the access area between the atrium and the kitchen secured back to the wall. |
STUART-HOBSON MIDDLE SCHOOL | 677173 | Interior Painting & Wall Issue | Atrium of Cafeteria | Wall needs painting(white eggshell) due to discoloration from leak |
STUART-HOBSON MIDDLE SCHOOL | 665507 | Heating | Boiler room | Heating Issue: ? Heating Unit ? Too Cold Assignment Description: Requesting to have unit repaired. |
STUART-HOBSON MIDDLE SCHOOL | 675665 | Heating | Boiler Room | Repair ignition wire on boiler#3. |
STUART-HOBSON MIDDLE SCHOOL | 671790 | Interior Painting & Wall Issue | Boys locker room | Requesting to have the wall inside of the boys locker room inside of the gymnasium painted a semi gloss. |
STUART-HOBSON MIDDLE SCHOOL | 631560 | PA and Clock System | G02 | PA and Clock System Issue: ? Intercom/PA System ? Sound Too Low Assignment Description: Room G02 inter comm system is not loud or clear. We had a lockdown situation a few days ago and the announcement could not reach the room. |
STUART-HOBSON MIDDLE SCHOOL | 664110 | Faucet | Girls restroom ground floor | Faucet Issue: ? Sink ? Repair / Replace Assignment Description: Requesting to have sinks cualked and secure back to the wall. |
STUART-HOBSON MIDDLE SCHOOL | 678286 | Ceiling | Ground floor hallway | Requesting to have water damage ceiling tiles replaced. |
STUART-HOBSON MIDDLE SCHOOL | 658836 | Interior Painting & Wall Issue | Ground Level/Gym Floor | Interior Painting & Wall Issue: ? Painitng ? Repaint Assignment Description: Requesting semi gloss paint for the wall in the girl's restroom. |
STUART-HOBSON MIDDLE SCHOOL | 631561 | PA and Clock System | Gym | PA and Clock System Issue: ? Intercom/PA System ? Sound Too Low Assignment Description: Gym area inter comm system is not loud or clear. We had a lockdown situation a few days ago and the announcement could not reach the room. Impossible to hear announcements when activities are taking place. |
STUART-HOBSON MIDDLE SCHOOL | 652687 | Roof | Gymnasium | Roof Issue: ? Water Leak ? Rooftop Assignment Description: Requesting to have the roof repaired over top of the gymnasium which leaks when it rains. |
STUART-HOBSON MIDDLE SCHOOL | 631563 | PA and Clock System | Library | PA and Clock System Issue: ? Intercom/PA System ? Reset/Synchronize Assignment Description: Library inter comm system is not loud or clear. We had a lockdown situation a few days ago and the announcement could not reach the room. |
STUART-HOBSON MIDDLE SCHOOL | 665888 | Building Structural | Main Lobby | Requesting to have automatic door repaired the door doesn?t close properly. |
STUART-HOBSON MIDDLE SCHOOL | 669474 | Lock and Door | Main lobby | Need a electrician for automatic main lobby door contractors replaced something on the door and said all we need was a electrician for the power. |
STUART-HOBSON MIDDLE SCHOOL | 679147 | Lighting | Main office | Requesting to have blown hanging lights inside of the main office waiting area replaced on the 1st floor. |
STUART-HOBSON MIDDLE SCHOOL | 680410 | Electronic Security Issue | Main Office Entrance | Electronic Security Issue: ? Not Working Assignment Description: Requesting to have security alarm panel trouble transmit code cleared from constant alerts that keep going off every 5-10 minutes |
STUART-HOBSON MIDDLE SCHOOL | 671710 | Roof | Outside of the main entrance lobby | Requesting to have standing water and debris removed and drain pipe repaired or replace on outside concrete roof over top of the main lobby door. |
STUART-HOBSON MIDDLE SCHOOL | 671657 | Roof | Outside of the main lobby | Requesting to have outside concrete balcony repaired from deterioration and leaking. (Safety hazard) It will eventually collapse. |
STUART-HOBSON MIDDLE SCHOOL | 667308 | Building Structural | Principals office | Structural Issue: ? Ceiling Assignment Description: Requesting to have vertical blimd repaired or replaced because the lowering cable does not work. |
STUART-HOBSON MIDDLE SCHOOL | 643571 | Roof | Rooftop | Roof Issue: ? Roof Damage Assignment Description: Need catwalk installed Filters need to be replaced throughout building |
STUART-HOBSON MIDDLE SCHOOL | 681966 | Lighting | Room 121 | Requesting to have light motion detection module replaced because the it?s not working this not letting the lights come on in room 121 on the 1st floor. |
STUART-HOBSON MIDDLE SCHOOL | 679269 | Lighting | Room 209 | Requesting to have light fixture in room 209 on the 2nd floor repaired from hanging improperly. |
STUART-HOBSON MIDDLE SCHOOL | 682667 | Interior Painting & Wall Issue | Room 303 | Requesting to have wall patched and painted in room 303. |
STUART-HOBSON MIDDLE SCHOOL | 682670 | Interior Painting & Wall Issue | Room 303 | Requesting have baseboard replaced in room 303 |
STUART-HOBSON MIDDLE SCHOOL | 672314 | Roof | Room 314 | Roof Issue: ? Water Leak ? Rooftop Assignment Description: Ceiling leaking. Plaster is peeling |
STUART-HOBSON MIDDLE SCHOOL | 643905 | Interior Painting & Wall Issue | Stairwell #2 | Interior Painting & Wall Issue: ? Painitng ? Painting Maintenance Assignment Description: Requesting to have stairwell #2 painted a semi gloss white paint. |
STUART-HOBSON MIDDLE SCHOOL | 643854 | Interior Painting & Wall Issue | Stairwell #3 | Interior Painting & Wall Issue: ? Painitng ? Painting Maintenance Assignment Description: Requesting to have stairwell #3 painted a semi gloss white. |
STUART-HOBSON MIDDLE SCHOOL | 643865 | Interior Painting & Wall Issue | Stairwell 1 | Interior Painting & Wall Issue: ? Painitng ? Painting Maintenance Assignment Description: Requesting to have stairwell #1, #2, #3 painted a semi gloss white paint. |
STUART-HOBSON MIDDLE SCHOOL | 668978 | Building Structural | Sub basement hallway | Requesting to have sub floor repaired throughout the sub basement area. |
STUART-HOBSON MIDDLE SCHOOL | 676721 | Interior Painting & Wall Issue | Third floor hallway above lockers | Walls need painting because of roof leak and bubbling plaster |
TYLER ELEMENTARY SCHOOL | 663208 | Cooling | 109 | Pipes leaking resulting in ceiling tiles collapsing. Room is located across the hall form another pipe leak in the main office. |
TYLER ELEMENTARY SCHOOL | 682365 | Cooling | 115 | Univent stop working |
TYLER ELEMENTARY SCHOOL | 676930 | FLOORING | 115 | Flooring Issue: ? Carpet ? Repair/Replace Assignment Description: Classroom carpet worn and displays liquid damage areas. |
TYLER ELEMENTARY SCHOOL | 682356 | Cooling | 115 Univent AC unit | Cooling Issue: ? AC Unit ? Too Hot Assignment Description: Room's univent AC unit is not pushing out any cool air at all!! |
TYLER ELEMENTARY SCHOOL | 676932 | Interior Painting & Wall Issue | 116 | Interior Painting & Wall Issue: ? Patching & Painting ? Repaint Assignment Description: Drywall has holes in it and needs to be repaired in the Teacher's lounge. |
TYLER ELEMENTARY SCHOOL | 682294 | Cooling | 135 | Univent is leaking on the floor |
TYLER ELEMENTARY SCHOOL | 679127 | Cooling | 135 | AC unit leaking water on floor |
TYLER ELEMENTARY SCHOOL | 673415 | Window | 201 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Classroom needs (2) window screens installed. |
TYLER ELEMENTARY SCHOOL | 673414 | Window | 202 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Windows need (2) window screens installed. |
TYLER ELEMENTARY SCHOOL | 673410 | Window | 206 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Classroom needs (2) window screens installed. |
TYLER ELEMENTARY SCHOOL | 669860 | Window | 207 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Windows will not remain open without a book or some form of stopper. |
TYLER ELEMENTARY SCHOOL | 673409 | Window | 207 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Classroom needs (3) window screens installed. |
TYLER ELEMENTARY SCHOOL | 673407 | Window | 208 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Classroom needs (1) window screen installed. |
TYLER ELEMENTARY SCHOOL | 680138 | Lock and Door | 208 | Assistant principals key will not open lock |
TYLER ELEMENTARY SCHOOL | 674455 | Cooling | 209 | Replace blown univent motor and capacitor. The fuses are good. Unit does not energize when switched on. |
TYLER ELEMENTARY SCHOOL | 672640 | Cooling | 210 | Repair univent motor. Motor will not engage. Motor is 1/8hp, 115v, and 1ph. |
TYLER ELEMENTARY SCHOOL | 682782 | Cooling | 216 | Cooling Issue: ? AC Unit ? No AC Assignment Description: Univent isn't pushing out any cool air. |
TYLER ELEMENTARY SCHOOL | 676378 | Interior Painting & Wall Issue | 216 | Please remount cabinets that fell off the wall |
TYLER ELEMENTARY SCHOOL | 673417 | Window | 217 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Classroom needs (1) window screen installed. |
TYLER ELEMENTARY SCHOOL | 677846 | Interior Painting & Wall Issue | 2nd floor wall | Interior Painting & Wall Issue: ? Patching & Painting ? Repaint Assignment Description: Second floor gray, base level painting is chipped and cracked. |
TYLER ELEMENTARY SCHOOL | 669871 | Window | 301/302 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Window cannot stay open without a book or something to hold them. |
TYLER ELEMENTARY SCHOOL | 673396 | Window | 304 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Classroom needs (6) window screens installed. |
TYLER ELEMENTARY SCHOOL | 658685 | Overhead Door | 305 | Overhead Door / Mechanical Fence Issue: ? Overhead Door ? Repair/Replace Assignment Description: Top window has dropped to the bottom top of frame as bent needs to be permanently sealed and put back into place |
TYLER ELEMENTARY SCHOOL | 673397 | Window | 305 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Classroom needs (1) window screen installed. |
TYLER ELEMENTARY SCHOOL | 668613 | Heating | 306 | Heating Issue: ? Temperature ? Too Hot Assignment Description: Extremely hot inside of In Person classroom 97. Some students asked to step outside of the classroom due to the heat thus interrupting the lesson plans. |
TYLER ELEMENTARY SCHOOL | 673399 | Window | 306 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Classroom needs (2) window screens installed. |
TYLER ELEMENTARY SCHOOL | 673401 | Window | 307 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Classroom needs (1) window screen installed. |
TYLER ELEMENTARY SCHOOL | 673402 | Window | 308 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Classroom needs (5) window screens installed. |
TYLER ELEMENTARY SCHOOL | 673406 | Window | 309 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Classroom needs (2) window screens installed. |
TYLER ELEMENTARY SCHOOL | 673400 | Window | 311 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Classroom needs (1) window screen installed. |
TYLER ELEMENTARY SCHOOL | 673394 | Window | 316 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Broken ? null Assignment Description: Window is cracked and needs replacement. Classroom needs (6) window screens. |
TYLER ELEMENTARY SCHOOL | 673392 | Window | 317 | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Classroom needs (7) window screens installed. |
TYLER ELEMENTARY SCHOOL | 665454 | Electronic Security Issue | Basement it room | Electronic Security Issue: ? Maintenance Assignment Description: Battery leaking |
TYLER ELEMENTARY SCHOOL | 667636 | Heating | Boiler room | Heating Issue: ? Heating Unit ? Too Cold Assignment Description: Repair boiler1. Boiler will not shut off at the modulator control. Fan continues to run. Only shuts down at the breaker. |
TYLER ELEMENTARY SCHOOL | 671401 | Cooling | chiller | Cooling Issue: ? AC Unit ? Central Air Assignment Description: Complete Tube Chiller PM |
TYLER ELEMENTARY SCHOOL | 676417 | FLOORING | First floor Art room | Flooring Issue: ? Tile ? Broken/Cracked/Damaged Assignment Description: HVAC renovation cracked the floor tiles in the art room. |
TYLER ELEMENTARY SCHOOL | 676922 | Interior Painting & Wall Issue | First floor boys bathroom | Interior Painting & Wall Issue: ? Patching & Painting ? Caulking Assignment Description: Boys bathroom wall tiles are missing and damaged. |
TYLER ELEMENTARY SCHOOL | 676923 | Interior Painting & Wall Issue | First floor boys bathroom | Interior Painting & Wall Issue: ? Patching & Painting ? Paint Peeling Assignment Description: Boys bathroom wall needs some replacement painting. |
TYLER ELEMENTARY SCHOOL | 676928 | Interior Painting & Wall Issue | First floor hallway | Interior Painting & Wall Issue: ? Patching ? Repaint Assignment Description: Patch paint first floor hallway. |
TYLER ELEMENTARY SCHOOL | 673412 | Window | Library | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Room need (3) window screens installed. |
TYLER ELEMENTARY SCHOOL | 674779 | Window | Main office | Window needs to be reinforced window from the top will fall at any time |
TYLER ELEMENTARY SCHOOL | 677845 | FLOORING | Main Office | Flooring Issue: ? Carpet ? Repair/Replace Assignment Description: Main office carpet has unremovable stains and damage from an extended ceiling leak which require replacement. |
TYLER ELEMENTARY SCHOOL | 677107 | PA and Clock System | Network room 2nd floor | PA and Clock System Issue: ? Clock System ? Reset/Synchronize Assignment Description: We need a synchronized clock server to connect and sync with the clocks around the building. |
TYLER ELEMENTARY SCHOOL | 656597 | Playground | Playground | Playground Issue: ? Equipment ? Repair/Remove/Replace Equipment Assignment Description: The basketball hoop extender pipe has been severed/broken. |
TYLER ELEMENTARY SCHOOL | 663468 | Heating | Rm201 | Heating Issue: ? Heating Unit ? Too Hot Assignment Description: Closed loop 3/4? supply line, after the isolation valve, 10ft high, in the ceiling, has a leak from a nipple. |
TYLER ELEMENTARY SCHOOL | 668546 | Heating | Room 305 | Heating Issue: ? Heating Unit ? Too Hot Assignment Description: Social worker room is extremely hot, reading 97.5. |
TYLER ELEMENTARY SCHOOL | 676933 | Interior Painting & Wall Issue | Staircase foyer | Interior Painting & Wall Issue: ? Painitng ? Repaint Assignment Description: Staircase walls need repainting. |
TYLER ELEMENTARY SCHOOL | 657168 | Roof (Exterior Services) | Third floor custodian closet | Leak Issue: ? Source Unknown Assignment Description: Slop sink is leaking at base//roof leak |
TYLER ELEMENTARY SCHOOL | 677984 | Cooling | Throughout building | Check and recalibrate the Univents some univent are not cooling through out building |
TYLER ELEMENTARY SCHOOL | 672523 | Interior Painting & Wall Issue | Throughout building boys and girls restrooms | Please replace all soap dispensers that aren't working throughout building boys and girls restrooms |
VAN NESS ELEMENTARY | 678791 | Toilet | 3rd floor girls bathroom | Toilet Issue: ? Toilet ? Leak Assignment Description: The toilets in the first and last stalls in the 3rd floor girls bathrooms are leaking at the connection to the wall. |
VAN NESS ELEMENTARY | 654487 | Roof | 3rd floor hallway | Roof Issue: ? Water Leak ? Rooftop Assignment Description: Leak from roof it's still leaking |
VAN NESS ELEMENTARY | 668988 | Heating | all rooms | Heating Issue: ? Heating Unit ? Too Hot Assignment Description: secure thermostats |
VAN NESS ELEMENTARY | 675970 | Cooling | Building second floor lower roof | Cooling Issue: ? AC Unit ? Too Hot Assignment Description: RRU #2 sensors/controls are not reading correctly, they?re causing the RTU to cool and heat simultaneously. |
VAN NESS ELEMENTARY | 669969 | Sidewalks | Outside | Flagpole have knots in the line it needs to be rethreaded canraise or lower sometimes |
VAN NESS ELEMENTARY | 665016 | Playground | Outside playground | Playground Issue: ? Equipment ? Repair/Remove/Replace Equipment Assignment Description: Equipment needs repair is a safety hazard |
VAN NESS ELEMENTARY | 673482 | Playground | Playground | Utility pipe needs cover kid had his foot in it safely issue |
VAN NESS ELEMENTARY | 679856 | Outlet | Room 218 | Outlet Issue: ? Repair Outlet ? The conduit is not exposed Assignment Description: There are two outlets in the room: duplex and quadplex. Neither plug is working on the duplex and only one is working on the quadplex. |
VAN NESS ELEMENTARY | 668410 | Switch | Room 312 | Switch Issue: ? Light Sensor Problem ? The conduit is not exposed Assignment Description: The dimmer in the classroom keeps turning lights on and then down repeatedly. Can't keep contact level of illumination. |
WALKER-JONES EDUCATION CAMPUS | 678399 | Lock and Door | 1st floor staircase 1 near room 102 | Walker-Jones EC VAMP High Priority II/Priority Repair) IFC 703.2.3 - Door operation First floor staircase 1 near room 102 ? Adjust door closer latch speed on left door ; Adjust hinges and realign doors to properly latch shut.. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. FEMS Lvl-2 |
WALKER-JONES EDUCATION CAMPUS | 678395 | Lock and Door | 1st floor staircase 2 | Walker-Jones ED (VAMP High Priority II/Priority Repair) IFC 703.2.2 Door Holding Devices First floor staircase-2 Replace damaged or missing magnet(s) on exit doors; reenergized electromagnetic armature(s) where needed. Increase sweep and latch speed on left door; repair or replace vertical rod on right door, door will not disengage. Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. FEMS Lvl-2 |
WALKER-JONES EDUCATION CAMPUS | 678396 | Lock and Door | 2nd floor staircase 2 | Walker-Jones ED (VAMP High Priority II/Priority Repair) IFC 703.2.2 Door Holding Devices Second floor staircase-2 Replace damaged or missing magnet(s) on exit doors; reenergized electromagnetic armature(s) where needed. Repair or replace damaged latch head and vertical rod assembly on left door. Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. FEMS Lvl-2 |
WALKER-JONES EDUCATION CAMPUS | 635359 | Lock and Door | 314/ Early Stages Main Office Door | Lock and Door Issue: ? Lock/Latch & Door ? Standard Door ? Repair/Replace/Install Door Lock ? null Assignment Description: Maintenance came in and installed new locks on all doors that did not have the ability to lock and unlock from the inside. On the Early Stages Main Office Door they installed the wrong part, causing the door to Jam and never close all the way, needs to be fixed or repaired. May need to check to see if any other tickets have been placed already to repair this door. |
WALKER-JONES EDUCATION CAMPUS | 653496 | Window | 314 Early Stages | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Repair/Replace/Install ? null Assignment Description: Blinds need to be replaced in several rooms throughout early stages, which is room# 300-318, except room 317. |
WALKER-JONES EDUCATION CAMPUS | 635376 | FLOORING | 318/314/310/308/305/ Early Stages | Flooring Issue: ? Carpet ? Repair/Replace Assignment Description: Carpet needs to be replaced, it hasn't been replaced over 10 years. It has been infested with rodents and their droppings, regular wear and tear. This is testing area for 2.5 yr old to 5 year old, clean environment is needed. Allergy issues are flared from both workers and children been tested. Need carpet removed and replaced. |
WALKER-JONES EDUCATION CAMPUS | 673607 | Cooling | 4th floor rooftop | Request to repair or replace rooftop unit number 4 compressors will not engage for cooling possible refrigerant leak |
WALKER-JONES EDUCATION CAMPUS | 677732 | Cooling | 4th floor rooftop | Request to repair or replace bad condenser fan motor on rooftop unit number 4 need for cooling |
WALKER-JONES EDUCATION CAMPUS | 677711 | Heating | Back loading dock area | Request to have generator service it will not run in auto |
WALKER-JONES EDUCATION CAMPUS | 665495 | Fire Sprinkler | Basement Pump room | Pump Issue: ? Pressure ? Leak / Discharge Assignment Description: Sprinkler system to be service |
WALKER-JONES EDUCATION CAMPUS | 656484 | Heating | Boiler room | Heating Issue: ? Heating Unit ? Too Hot Assignment Description: Request to have boiler number 2 burner calibrated |
WALKER-JONES EDUCATION CAMPUS | 677903 | Fire Extinguisher | Building exterior | Walker-Jones EC (VAMP Routine Priority III/Routine Repair) IFC 912.2.2 Existing buildings Fire Connection (FDC) Signs Pierce St side near corner ofNew Jersey Ave side of building on exterior walls - Fire Department Connection (FDC) placard. Provide and install visible ?FDC? Signage on masonry wall surface above FDC connection inlets as required by the fire inspector. On existing buildings, wherever the fire department connection is not visible to approaching fire apparatus, the fire department connection shall be indicated by an approved sign mounted on the street front or on the side of the building. Such sign shall have the letters ?FDC? at least 6 inches (152 mm) high and words in letters at least 2 inches (51 mm) high or an arrow to indicate the location. All such signs shall be subject to the approval of the fire code official. FEMS Lvl -2 |
WALKER-JONES EDUCATION CAMPUS | 596315 | Power | Cafeteria | Resubmitting this work order. Automatic curtains in the cafeteria are not functioning properly. The curtains are low voltage, and this work needs to go to contract services. |
WALKER-JONES EDUCATION CAMPUS | 678397 | Lock and Door | Exterior doors near security office | Walker-Jones EC (VAMP High Priority II/Priority Repair) IFC 703.2.2 Door Holding Devices Corridor near security office & room 102- Exterior exit doors near security office will not open; adjust pivot hinges and realign doors to open, close and latch. Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. FEMS Lvl-2 |
WALKER-JONES EDUCATION CAMPUS | 677901 | Fire Sprinkler | Fire Pump room | Walker-Jones EC (VAMP Routine Priority III/Routine Repair) IFC 913.5 - Testing and maintenance - Fire Pump Room - Annual service, maintenance requiredFire pumps shall be inspected, tested and maintained in accordance with the requirements of this section and NFPA 25. Records of inspection, testing and maintenance shall be maintained. Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust systems, and smoke and heat vents shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. FEMS Lvl-2 |
WALKER-JONES EDUCATION CAMPUS | 680133 | Lock and Door | Front entrance door | Metal detierating from around the door frame |
WALKER-JONES EDUCATION CAMPUS | 640206 | Lock and Door | Front School Door | Lock and Door Issue: ? Door ? Automatic Door ? Repair/Replace/Install Door Lock ? null Assignment Description: The door connected to the doorbell is not currently opening. not sure if a ticket has been placed for this yet. |
WALKER-JONES EDUCATION CAMPUS | 673538 | Cooling | in several rooms 114,114a,114b,114c,114d,114e,114f,214,214a,214b,216,218,314, 314a,314b,314c,314d,312,318,316 | cooling issue>temperature>too hot Assignment Description: Cooling issue rooms are to hot we are in the need for 20 fans. This area of the building is always a on going issue. |
WALKER-JONES EDUCATION CAMPUS | 654352 | Roof | roof top oner gym | roof issue>water leak>rooftop Assignment Description: roof leaking badly in gym |
WALKER-JONES EDUCATION CAMPUS | 679118 | Interior Painting & Wall Issue | Room 112 | Principal office needs painting |
WALKER-JONES EDUCATION CAMPUS | 679339 | Lock and Door | Room 112 | Repair door handle so that the Principal can secure his door |
WALKER-JONES EDUCATION CAMPUS | 678126 | Lock and Door | Room 220 | Can not open the door also wrong door handle install |
WALKER-JONES EDUCATION CAMPUS | 679115 | Outlet | Room 320A | Install outlet for copier machine |
WALKER-JONES EDUCATION CAMPUS | 682683 | Environmental | Rooms 321,325,326 | Hepa filters machine needed |
WALKER-JONES EDUCATION CAMPUS | 678398 | Lock and Door | Staircase near room 031 | Walker-Jones EC VAMP High Priority II/Priority Repair) IFC 703.2.3 - Door operation Exit door to staircase near Room 031 Storage - Adjust hinges and realign doors to properly latch shut. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. FEMS Lvl-2 |
WATKINS ELEMENTARY SCHOOL | 631673 | Lock and Door | 161 cafeteria | Lock and Door Issue: ? Door ? Metal Door ? Repair/Replace/Install Door Lock ? null Assignment Description: Rollup door is not staying up in place. |
WATKINS ELEMENTARY SCHOOL | 627888 | Lock and Door | 190 Back door | The handicap wave to open sensor housing is broken |
WATKINS ELEMENTARY SCHOOL | 681495 | Ceiling | 1st Floor Hallway by 12th and Dst entrance | Ceiling tile needs to be replaced has a water stain in it. |
WATKINS ELEMENTARY SCHOOL | 674070 | Lock and Door | 1st floor Hallway Door lead to classrooms | Lock and Door Issue: ? Lock/Latch & Door ? Standard Door ? Repair/Replace/Install Door Lock ? null Assignment Description: Hallway door does not lock at all in case of lock down emergency the door will not keep first floor classroom out of harms way ticket needs to be escalated ASAP URGENT!!!!! Safety Issue!!!!!! |
WATKINS ELEMENTARY SCHOOL | 659480 | Window | 1st floor Main Entrance Door | Window Issue: ? Above 8 feet/1 Story ? Window Frame ? Broken ? null Assignment Description: Broken window ledge on the top right hand main entrance door. |
WATKINS ELEMENTARY SCHOOL | 674365 | Pipe | 1st Floor Outside of Room 143 | Pipe Issue: ? Water ? Leak Assignment Description: There's a pipe leaking in the ceiling needs immediate attention URGENT Safety Issue!!!! |
WATKINS ELEMENTARY SCHOOL | 678645 | Interior Painting & Wall Issue | 1st Floor Room 115 | Wall has patches in the paint on wall that needs immediate attention |
WATKINS ELEMENTARY SCHOOL | 652123 | Interior Painting & Wall Issue | 1st floor Room 135 | Interior Painting & Wall Issue: ? Patching & Painting ? Painting Maintenance Assignment Description: Hole in wall |
WATKINS ELEMENTARY SCHOOL | 659481 | Toilet | 1st floor Room 144 | Toilet Issue: ? Urinal ? Clog / Unclog Assignment Description: Urinal on the right hand side of the door is not flooding when flushed. |
WATKINS ELEMENTARY SCHOOL | 682427 | Cooling | 1st floor Room 190 | Cooling Issue: ? AC Unit ? No AC Assignment Description: Right side of the Gymnasium is not producing any cool air on days of 88degrees and above the right side of the gym feels like a steam room leaving windows foggy and gym floor moist needs immediate attention URGENT!!!!! Safety Hazarad. |
WATKINS ELEMENTARY SCHOOL | 660331 | Leak | 1st floor Room 190 | Leak Issue: ? Ceiling Assignment Description: Ceiling is leaking tremendously and needs immediate attention URGENT!!!! |
WATKINS ELEMENTARY SCHOOL | 675905 | Pipe | 1st floor Room 190 | Pipe Issue: ? Water ? Leak Assignment Description: We have a leaking water pipe in the ceiling outside of gymnasium causing the ceiling tile to collapse in hallway where kids water fountain are located ticket needs immediate attention URGENT!!!!! Safety hazarad!!!!! |
WATKINS ELEMENTARY SCHOOL | 600433 | Leak | 240 | the green roof is leaking (again) into Rm. 240. There is one tile that has to be replaced consistently due to leak. |
WATKINS ELEMENTARY SCHOOL | 678595 | Interior Painting & Wall Issue | 2nd floor Room 215 | Classroom is in need of paint for entrance walls also needs touch up's thru out the rooms |
WATKINS ELEMENTARY SCHOOL | 678852 | Window | 2nd floor Room 220 | Classroom window is shattered in multiple pieces safety harzard children inside of classroom needs immediate attention URGENT!!!!!! |
WATKINS ELEMENTARY SCHOOL | 653543 | Roof (Exterior Services) | 2nd floor Room 240 | Ceiling Issue: ? Damaged Tiles Assignment Description: Heavy Leaking from ceiling by the window//roof leak, sent to contract service |
WATKINS ELEMENTARY SCHOOL | 662354 | Roof (Exterior Services) | 2nd floor Room 240 | Leak Issue: ? Ceiling Assignment Description: Ceiling needs immediate attention URGENT!!!!! Ceiling is collapsing//roof leak |
WATKINS ELEMENTARY SCHOOL | 652141 | Interior Painting & Wall Issue | 3rd Floor Hallway | Interior Painting & Wall Issue: ? Patching ? Painting Maintenance Assignment Description: Hallway window ledge broken off window across from the common area |
WATKINS ELEMENTARY SCHOOL | 680268 | Landscaping | 3rd floor Outside Garden | Garden above footprint room needs to to cut because grass is growing wildly cause water drain to be blocked flooding garden leaking the footprint classroom. |
WATKINS ELEMENTARY SCHOOL | 651944 | Interior Painting & Wall Issue | 4th Floor Hallway | Interior Painting & Wall Issue: ? Patching & Painting ? Painting Maintenance Assignment Description: Panel detached from wall |
WATKINS ELEMENTARY SCHOOL | 681579 | Electronic Security Issue | Alarm panels keypads on 1st floor | Electronic Security Issue: ? Maintenance Assignment Description: Alarm panels are stating that they need troubleshooting adjustments in order to set alarm on the building URGENT!!!!! |
WATKINS ELEMENTARY SCHOOL | 682507 | Cooling | ALL 2ND FLOOR | URGENT! URGENT!! URGENT!! Repair or replace the LG VRF 2A and VRF 2B and VRF 6 , displaying different faults code CH106 , CH 10,CH 03 , CH04, on thermostat , the VRF 2A & VRF 2B serves all the classrooms and VRF #6 serves the library. The VRF 2A& 2B are located on the main roof and the VRF #6 is located on lower roof access through 3rd floor mechanical room 350. Please additional support is needed ASAP. |
WATKINS ELEMENTARY SCHOOL | 665189 | Interior Painting & Wall Issue | All staircases 1st-4th floor | Interior Painting & Wall Issue: ? Patching ? Caulking Assignment Description: All placards need to be properly installed on walls needs immediate attention URGENT!!!! |
WATKINS ELEMENTARY SCHOOL | 652132 | Interior Painting & Wall Issue | Entire school | Interior Painting & Wall Issue: ? Painitng ? Repaint Assignment Description: School hallways needs to be painted with a darker color. |
WATKINS ELEMENTARY SCHOOL | 662931 | Power | Exterior roof top from Room 350 mechanical room | Power Issue: ? Partial Outage ? The emergency lights are working Assignment Description: Watkins ES (Watkins ES & Peabody ES population) (VAMP Emergency Priority I/Emergency Repair) IFC 907.8.5 - Inspection, testing and maintenance: Rooftop emergency generator accessible from third-floor mechanical room 350 - The Generator is out of service, and shall be abated immedately. Generator fault indicator light on fire alarm annunciator panel. Repair and service rooftop emergency generator and restore service back on line. The building owner shall be responsible to maintain the fire and life safety systems in an operable condition at all times. Service personnel shall meet the qualification requirements of NFPA 72 for inspection, testing and maintenance of such systems. Records of inspection, testing and maintenance shall be maintained. FEMS Lvl-2 |
WATKINS ELEMENTARY SCHOOL | 667866 | FIRE ALARM | First Floor Room 121 | Health suite fire alarm annouciator is not alarming nurse with neither sound or flashing not alerting nurse when fire drill nor fire is in place fire hazarad as well as safety issue ticket needs to be escalated. |
WATKINS ELEMENTARY SCHOOL | 581763 | Flooring (Interior Services) | front entrance | Recommend for DCPS Capital Structural Project. Earlier Note: Floor tiles are coming up as a result of a roof leak. There's about 20 tiles that need to be replaced. |
WATKINS ELEMENTARY SCHOOL | 675987 | Building Structural | Front of school building | Black slate tile is falling apart from wall out front of school building needs immediate attention safety hazarad. URGENT!!!!!! |
WATKINS ELEMENTARY SCHOOL | 660316 | Building Structural | Front of the school building | Structural Issue: ? Wall Assignment Description: Tile coming apart on front of building needs immediate attention |
WATKINS ELEMENTARY SCHOOL | 680263 | Building Structural | Gymnasium 1st floor Room 190 | Rubber lining on the track for the gymnasium wall partition in center of the floor is worn preventing the divider to close . |
WATKINS ELEMENTARY SCHOOL | 637006 | Lighting | Gymnasium Room 190 | Lighting Issue: ? Interior Lights ? Above 8 feet ? Room(s)/Auditorium/Gymnasium ? null Assignment Description: LEDs light blown |
WATKINS ELEMENTARY SCHOOL | 631445 | Roof | Library 250 | Roof Issue: ? Water Leak ? Rooftop Assignment Description: leak coming in the library ceiling. |
WATKINS ELEMENTARY SCHOOL | 669919 | Environmental | Loading dock rear of school on Cst side S.E | Environmental Issue: ? Hazmat ? Hazmat Cleanup Assignment Description: Trash compactor has no source of power technicians have been out numerous of times to fix compactor and still doesn't work. Situation is becoming a ongoing problem and request to have compactors removed and replaced with regular dumpsters before trash get unbearable causing a rodents issues ticket needs to be escalated ASAP. Urgent!!!!!!! |
WATKINS ELEMENTARY SCHOOL | 659938 | Power | Mechanical Room 350 outside left door | Power Issue: ? Partial Outage ? The emergency lights are working Assignment Description: Repair or replace Emergency generator motor rotor locked out, the generator is in alarm state, it?s located in the mechanical room 350 outside left door. |
WATKINS ELEMENTARY SCHOOL | 652126 | Ceiling | Nurse Office Rm121 | Ceiling Issue: ? Replace Tiles Assignment Description: Leaking from outside nursing office ceiling |
WATKINS ELEMENTARY SCHOOL | 670854 | Power | Outside trash compactor | Power Issue: ? Complete Outage ? The emergency lights are not working Assignment Description: Emergency assistance need for trash compactor no power is on to operate compactor as trash continues to pile up in school ticket needs to be escalated ASAP URGENT!!!!!! |
WATKINS ELEMENTARY SCHOOL | 587370 | Roof (Exterior Services) | Rm 140 | Roof leaking causing water from the roof to travel and enter classroom 140 through the window seal causing puddles to form. Leak needs to be fixed and roof needs to be repaired. POC: Robert Kinney (202) 698-6390 |
WATKINS ELEMENTARY SCHOOL | 670887 | WATER FOUNTAIN | See Description for details | Leaking water fountain: Water fountain near the splash park is damaged and is spraying water |
WATKINS ELEMENTARY SCHOOL | 681500 | PEST CONTROL | Thru out building | Mass trapping URGENT!!!!! |