Ward 6 School Work Orders Older than 30 Days

Ahead of the Sept 28 hearing on school repairs at the Council, I requested every open work order the DC Department of General Services has for Ward 6 DCPS schools that is more than 30 days old.

I'm sharing the full list (472!) of items so Ward 6 neighbors can see what's happening at their school and others as I prepare to question DGS leadership later.

Building Name Work Order No Problem Type Room/ Location - Affected Area Assignment Description
AMIDON ELEMENTARY SCHOOL 660154 Interior Painting & Wall Issue 106 Interior Painting & Wall Issue:
? Patching & Painting
? Caulking

Assignment Description:
Need someone  to come out to repair the backsplash for the kids sink
AMIDON ELEMENTARY SCHOOL 676706 Interior Painting & Wall Issue 106 Need walls painted in classroom have paint on site
AMIDON ELEMENTARY SCHOOL 673949 Cooling 107 Need thermostat replaced or repaired in the room.
AMIDON ELEMENTARY SCHOOL 673952 Cooling 126 Need two univents serviced in the room unable to turn them on or off from the thermostat.
AMIDON ELEMENTARY SCHOOL 676704 Interior Painting & Wall Issue 126 Need walls painted in classroom have paint on site
AMIDON ELEMENTARY SCHOOL 676703 Interior Painting & Wall Issue 128 Need walls painted in classroom have paint on site
AMIDON ELEMENTARY SCHOOL 681897 Pipe 133 Need rail heater removed and capped off in the room.
AMIDON ELEMENTARY SCHOOL 676691 Interior Painting & Wall Issue 202 Need walls painted in classroom have paint on site
AMIDON ELEMENTARY SCHOOL 676693 Interior Painting & Wall Issue 205 Need walls painted in room have paint on site
AMIDON ELEMENTARY SCHOOL 676694 Interior Painting & Wall Issue 212 Need walls painted in classroom have paint on site
AMIDON ELEMENTARY SCHOOL 676696 Interior Painting & Wall Issue 223 Need walls painted in classroom have paint on site
AMIDON ELEMENTARY SCHOOL 676698 Interior Painting & Wall Issue 225 Need walls painted in classroom have paint on site
AMIDON ELEMENTARY SCHOOL 676701 Interior Painting & Wall Issue 227 Need purple wall painted in classroom have paint on site
AMIDON ELEMENTARY SCHOOL 676697 Interior Painting & Wall Issue 230 Need walls painted in classroom have paint on site
AMIDON ELEMENTARY SCHOOL 682579 Interior Painting & Wall Issue 231 Patch and paint walls in classroom 231
AMIDON ELEMENTARY SCHOOL 682580 Interior Painting & Wall Issue 232 Patch and painting  needed in room 232
AMIDON ELEMENTARY SCHOOL 676702 Interior Painting & Wall Issue 236 Need walls painted in classroom have paint on site
AMIDON ELEMENTARY SCHOOL 682584 Faucet 267 in library Need faucet repaired in room 267
AMIDON ELEMENTARY SCHOOL 669686 Heating B129 boiler room Need heat to be turned on in boiler room for the kids in the classrooms the heat has been completely shutdown for three days.
AMIDON ELEMENTARY SCHOOL 674720 Cooling Boiler Repair/replace worn rubber coupling on chill water circulating pump #3. Also the return FNW temp gauge is broken, unable get adequate temp. BPO Wright 202-345-7587
AMIDON ELEMENTARY SCHOOL 682031 Cooling Boiler room Pump 3 - chiller water
Coupler needs to be replaced
AMIDON ELEMENTARY SCHOOL 682032 Cooling Boiler room Chill water relief valve  leaking
AMIDON ELEMENTARY SCHOOL 677587 Interior Painting & Wall Issue Gym Need ceiling repaired from roof leak that is still going on
AMIDON ELEMENTARY SCHOOL 682191 Roof GYM Roof Issue:
? Roof Damage

Assignment Description:
Roof leak in the middle of the gym floor
AMIDON ELEMENTARY SCHOOL 659388 Fire Extinguisher Library & Elevator Room Fire Extinguisher Issue:
? Fire Code (IFC)

Assignment Description:
Amidon ES (VAMP Routine Priority III/Routine Repair)
IFC 901.6 Inspection, Testing & Maintenance - Fire Extinguishers
Library - replace missing service tag.
Elevator/Equipment Room -Replace blank service tag or Punch service date on existing service tags.
Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust systems, and smoke and heat vents shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.   FEMS Lvl-2
AMIDON ELEMENTARY SCHOOL 682660 Cooling Library rooftop Filters needs to be replaced
AMIDON ELEMENTARY SCHOOL 662453 Electronic Security Issue Main office Electronic Security Issue:
? Not Working

Assignment Description:
Problem with the alarm
AMIDON ELEMENTARY SCHOOL 672795 Cooling Multipurpose Room and Gym Cooling Issue:
? AC Unit
? Too Hot

Assignment Description:
Repairs rooftop unit that serves Multipurpose Room and Gym
AMIDON ELEMENTARY SCHOOL 682540 FIRE ALARM Multi purpose room pull station Slc loop is damaged between two pullstations in cafeteria area between exit 21 and exit 22, the physical conductor between those two pullstations is compromised, thus needing replaced to get the main FA panel out of ground fault trouble.
AMIDON ELEMENTARY SCHOOL 657400 Playground Playground Playground Issue:
? Equipment
? Repair/Remove/Replace Equipment

Assignment Description:
Need painter's to come out to treat and paint the bleachers for the basketball courts
AMIDON ELEMENTARY SCHOOL 676079 Building Structural Rooftop gym unit Need engineer to come out to repair unit on the roof for the gym water is leaking  from the unit and coming thru the ceiling of the gym flooding the gym floor.
AMIDON ELEMENTARY SCHOOL 682568 Cooling (HVAC Services) Rooftop unit duct installation specialist is needed as the duct on the roof is being filled with water when it rains. - RSC has been dispatch per Gassama
AMIDON ELEMENTARY SCHOOL 677535 Cooling Rooftop unit Need rooftop unit for multi purpose room serviced no a/c
AMIDON ELEMENTARY SCHOOL 678338 Lighting See Description for details Light Pollution - Parking Lot:
There are a few high intensity LED lights that are too bright as they come into my home on the third floor across 4th street. Please let me know if they be adjusted to point down or a guard / filter added at the top of the fixtures so they do not shine directly into my home. Thanks
BRENT ELEMENTARY SCHOOL 652091 Building Structural 203, 303, 311 Structural Issue:
? Ceiling

Assignment Description:
These three rooms leak whenever there's rain, but each room has a leak in different areas.  Room 203 leaks from under the univent but we know that the univent is not causing the leak.  Room 303 leaks from the cracks in the concrete portion of the ceiling.  Room 311 leaks from the ceiling over the window by the mirror on the wall.  POC Jason Lawrence 301-706-3387
BRENT ELEMENTARY SCHOOL 634810 Interior Painting & Wall Issue 208 Interior Painting & Wall Issue:
? Patching
? Caulking

Assignment Description:
There is a large hole in the wall under the sink in room 208.  Pest Control has reported that this is an entry point and exit for the mice that are frequenting this room and the 2nd floor.  We need the hole to be filled to help alleviate the continuing issue with mice.
BRENT ELEMENTARY SCHOOL 614921 Lock and Door 311 The doorknob is not functioning properly in room 311.  There have been several instance where teachers and student have not been able to get out of the room because the knob would not function.
BRENT ELEMENTARY SCHOOL 662155 Leak Chiller Leak Issue:
? Pipe / Line / Drain

Assignment Description:
Chiller is leaking a large amount of water. The chiller is not draining either.
BRENT ELEMENTARY SCHOOL 682083 FIRE ALARM Fire Alarm Fire Alarm Issue:
? Repair

Assignment Description:
The fire alarm continued to go off for several hours on Sunday. Security came and could not resolve the issue. The fire alarm was disconnected from power.
BRENT ELEMENTARY SCHOOL 682408 Power Kitchen Power Issue:
? Partial Outage
? The emergency lights are working

Assignment Description:
Our equipment repair vendor TKC were on site to recently and inspected the kitchen exhaust hood system.
They found that the exhaust hood is not getting any power. Diagnosed as ? 1 of 3 legs of electrical is missing to the unit on the roof.
BRENT ELEMENTARY SCHOOL 668279 Fire Extinguisher Kitchen Fire Extinguisher Issue:
? Fire Code (IFC)

Assignment Description:
Brent  ES  (West EC population) VAMP Emergency Priority I/Emergency Repair)
IFC 904.11.6/IFC 901.6   Operation and Maintenance (Inspection/Testing) ? Kitchen Suppression system
Kitchen - Service, update and re-tag expired (July 2020) Ansul kitchen fire suppression system.  Implement service PM plan to update every 6-mos as required bit IFC/ Fems Inspector.  ( Note: FLS PM is scheduled for Aug 2022)Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust systems, and smoke and heat vents shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
 -  FEMS LVL-2
BRENT ELEMENTARY SCHOOL 665122 Lock and Door Lobby/Front Door Lock and Door Issue:
? Door
? Handicap Entrance/Door
? Repair/Replace/Install Door/Door Frame
? null

Assignment Description:
The front door that is connected to the electrical remote opening system is not functioning properly.  The door does not open when the button is pressed and sometimes gets stuck open when it is opened manually.  We have turn the switch off which has helped with the door getting stuck open, but we can no longer remotely open the door.  A staff member or security guard has to manually open the door whenever someone needs access to the school which only increase face to face contact and does not allow social distancing during the Covid-19 pandemic.  A technician is needed to fix this issue.  POC Jason Lawrence 301-706-3387
BRENT ELEMENTARY SCHOOL 652081 Roof Main Lobby Roof Issue:
? Water Leak
? Rooftop
Also included:  RM 302 - There is a significant amount of water falling from the concrete portion of the ceiling in room 302. The section of the ceiling leaking is closest to the teacher's corner; the area by the kidney table, cabinet etc. is where the water is leaking. Work Orders 652081 and 660258 also pertain to roof leaks in other parts of the school. This room is a classroom that will be physically occupied by students and staff members. Roofers are needed to assess and resolves the issues. POC Jason Lawrence 301-706-3387
library - 1st floor library ceiling window glass is cracked in the corner and water is leaking in through the window into the library. Assistance needed. There is a crack in the first skylight on the roof of the library. Water pours into the library whenever we have inclement weather. The skylight is located over top of several computers, which have to be moved when there's inclement weather.

Assignment Description:
There is a significant leak coming from the roof as soon as you enter the Main Lobby at Brent ES.  Whenever we have rain the ceiling tiles get saturated with  water and are in danger of falling on students parents and staff.  A roofing solution is needed to stop this issue from occurring. POC Jason Lawrence 301-706-3387
BRENT ELEMENTARY SCHOOL 682085 Building Structural Room 203 Structural Issue:
? Wall

Assignment Description:
A significant amount of water leaks into the classroom from under the HVAC unit after every rain. The building engineer noted that it was a building structural issue.  This classroom is an 1st grade classroom.
BRENT ELEMENTARY SCHOOL 672485 Playground Yellow Top Playground Playground Issue:
? Equipment
? Repair/Remove/Replace Equipment

Assignment Description:
The tan colored sliding board on the yellow top playground has been damaged.  There is a significantly large hole in the sliding board now that is a cutting hazard.  The students are not able to use the sliding board as the jagged edges will injure anyone who attempts to use it.  Work Order 662799 was put in on 1/6/2021 but the work order has been closed without the work being completed.  When the original work order was put in there were two holes in the sliding board.  Since the original work order was put in Salesforce, the holes have now become one larger hole.  POC Jason Lawrence 301-706-3387
EASTERN HIGH SCHOOL 675267 Grounds 1st floor roof top. Grounds Issue:
? Grass

Assignment Description:
Requesting Ms. Utility .
EASTERN HIGH SCHOOL 656550 Roof 1st floor W-137 court yard . Roof Issue:
? Water Leak
? Gutters

Assignment Description:
The down spout leading from the roof need to be repair .
EASTERN HIGH SCHOOL 665981 Lighting 2nd floor East atrium Lighting Issue:
? Interior Lights
? Above 8 feet
? Hallway
? null

Assignment Description:
the 1st light fixture globe need to be replace .
EASTERN HIGH SCHOOL 676690 Window 3rd floor hallway  west wing Window Issue:
? Below 8 feet /1 story
? Window Glass
? Broken
? null

Assignment Description:
Hallway glass is broken
EASTERN HIGH SCHOOL 631296 Lighting Auditorium Lighting Issue:
? Interior Lights
? Above 8 feet
? Room(s)/Auditorium/Gymnasium
? null

Assignment Description:
Adjust the stage lights
EASTERN HIGH SCHOOL 681362 Cooling Auditorium Cooling Issue:
? AC Unit
? No AC

Assignment Description:
The A/C unit is not cooling in the auditorium
EASTERN HIGH SCHOOL 674098 Drinking Water Filter (Plumbing Services) Basketball court Water Fountain Issue:
? Permanent Water Fountain
? Not Working

Assignment Description:
Water fountain is missing near the exterior  basketball court //please send to contract service for replacement.
EASTERN HIGH SCHOOL 658045 Railing and Step basketball court / tennis court Railing and Step Issue:
? Rail

Assignment Description:
The steps leading to the basket ball court and tennis courts  need a railing install for safety .
EASTERN HIGH SCHOOL 671982 Leak (Plumbing Services) Boiler Room Cooling Issue:
? AC Unit
? Central Air

Assignment Description:
Repair/Replace rupture 2? filter canister pvc line.
EASTERN HIGH SCHOOL 669428 Fire Sprinkler Boiler room Fire Sprinkler Issue:
? Fire Code (IFC)

Assignment Description:
Fire sprinkler system in trouble
EASTERN HIGH SCHOOL 682418 Cooling Chiller  / outside of building Chiller down , possible both circuits down on refrigerant
EASTERN HIGH SCHOOL 682260 Lighting E-100 B Lighting Issue:
? Interior Lights
? Below 8 feet
? Hallway
? null

Assignment Description:
Replace two balances
EASTERN HIGH SCHOOL 666536 Lighting E-122 Lighting Issue:
? Interior Lights
? Below 8 feet
? Room(s)/Auditorium/Gymnasium
? null

Assignment Description:
Requesting to have the light balance change .
EASTERN HIGH SCHOOL 681771 Lock and Door E-209 door handle need to be replace .
EASTERN HIGH SCHOOL 652521 Ceiling e-307 Ceiling Issue:
? Missing ceiling tile

Assignment Description:
Missing ceiling tile needs to be replaced.
EASTERN HIGH SCHOOL 680212 Lighting E-320 Lighting Issue:
? Interior Lights
? Above 8 feet
? Room(s)/Auditorium/Gymnasium
? null

Assignment Description:
Replace balance in the light fixture .
EASTERN HIGH SCHOOL 677163 Cooling E320 ,E114 , E116 , E313 , E412 , W137 , W113 E320 - Possible bad fan motor, E114 blown fuses, E116 not cooling & low on Freon, E313 need to reassembled, E412 want start , W137  Motor blown , W113 out on low pressure
EASTERN HIGH SCHOOL 682453 Cooling ERV/ Roof Top Cooling Issue:
? AC Unit
? Central Air

Assignment Description:
Control problems and barring are bad
EASTERN HIGH SCHOOL 676013 Building Structural (Interior Services) Exterior door zone 3 Lock and Door Issue:
? Lock/Latch & Door
? Standard Door
? Repair/Replace/Install Door Knob/Door Handle
? null

Assignment Description:
The 15 second egress panic bar is not working .

panic bar is electrical need contract service
EASTERN HIGH SCHOOL 682766 Lock and Door exterior zone  doors 7, 9-A, 9-b , zone 10 Lock and Door Issue:
? Lock/Latch & Door
? Standard Door
? Repair/Replace/Install Door Lock
? null

Assignment Description:
The exteriors doors are not closing properly
EASTERN HIGH SCHOOL 681773 FIRE ALARM Fire alarm panel Fire Alarm Issue:
? Fire Code (IFC)

Assignment Description:
The fire alarm panel reads RTU in trouble
EASTERN HIGH SCHOOL 681343 Fence and Gate Football field Fence and Gate Issue:
? Fence & Pole
? Repair Fence & Pole

Assignment Description:
fence need to be repair.
EASTERN HIGH SCHOOL 682034 Landscaping Football field Landscaping Issue:
? Trees/Leaves
? Cut/Trim Trees
? Entrance/Egress is obstructed
? null

Assignment Description:
Damage tree .
EASTERN HIGH SCHOOL 675806 Exterior Painting football field Exterior Painting Issue:
? Building/Doors

Assignment Description:
The score board need to be painting
EASTERN HIGH SCHOOL 675807 Exterior Painting football field Exterior Painting Issue:
? Building/Doors

Assignment Description:
Score board need painting
EASTERN HIGH SCHOOL 678402 Lighting football field Lighting Issue:
? Exterior Lights
? Above one (1) story
? Athletic Field(s)
? null

Assignment Description:
The football field stadium has 18 lights out , need to be replace .
EASTERN HIGH SCHOOL 679545 Lighting football field Lighting Issue:
? Exterior Lights
? Below one (1) story
? Athletic Field(s)
? null

Assignment Description:
The two score boards on the football field needs lights on the lower level .
EASTERN HIGH SCHOOL 679740 Pipe football field Pipe Issue:
? Water
? Rupture / Burst

Assignment Description:
Burst pipe
EASTERN HIGH SCHOOL 649774 Lighting Front Entrance Lighting Issue:
? Exterior Lights
? Above one (1) story
? Outside/Building/Street/Parking Lot
? null

Assignment Description:
Requesting  the  lights to be change,  exterior front  entrance
EASTERN HIGH SCHOOL 667364 MASONRY Front entrance Masonry Issue:
? Ground/Pavement
? Brick

Assignment Description:
The brick walk way is uneven  front the tree root . It's a safety issue .
EASTERN HIGH SCHOOL 682577 Fire Sprinkler G-07 Fire Sprinkler Issue:
? Fire Code (IFC)

Assignment Description:
The fire sprinkler is leaking
EASTERN HIGH SCHOOL 682597 Roof G-07 Roof Issue:
? Water Leak
? Rooftop

Assignment Description:
Roof top drain need to clean , check for leaks .
EASTERN HIGH SCHOOL 667811 Power greenhouse Power Issue:
? Partial Outage
? The emergency lights are working

Assignment Description:
Converting the gas heating to electric , the gas heater pilot keep going out .
EASTERN HIGH SCHOOL 671641 Switch greenhouse bulb is out
EASTERN HIGH SCHOOL 610690 Building Structural Gymnasium The main north basketball hoop need a bolt in the rim to hold it in place .
EASTERN HIGH SCHOOL 662969 Building Structural Gymnasium  area Structural Issue:
? Ceiling

Assignment Description:
The ceiling is  dropping
EASTERN HIGH SCHOOL 669911 Lock and Door Gymnasium exterior doors Lock and Door Issue:
? Lock/Latch
? Standard Door
? Locksmith
? null

Assignment Description:
The 15 seconds Egress doors need 9 volt batteries  zone 5,6,4.
EASTERN HIGH SCHOOL 613649 Building Structural (Interior Services) kitchen THE FLOOR IS A SHEET VLY AND NEED A CONTRACTOR TO PURCHASE THE MATERIALS AND INSTALL  the floor is made of a hold sheet of qronlla
EASTERN HIGH SCHOOL 680249 Outlet Main Office Outlet Issue:
? Repair Outlet
? The conduit is not exposed

Assignment Description:
Requesting a designated phone line for main  PA- System .
EASTERN HIGH SCHOOL 682417 Cooling MAU # 1 / Boiler Room MAU # 1 is down , multiple error code to include safety lockouts and low pressure on  compressors
EASTERN HIGH SCHOOL 682419 Cooling MAU # 3 / Roof Cooling Issue:
? AC Unit
? No AC

Assignment Description:
Possibly bad disconnect and also need new motor pulley
EASTERN HIGH SCHOOL 629735 Parking Lot Parking Lot Large pot hole in the back parking lot by the trash can.
EASTERN HIGH SCHOOL 658041 Exterior Painting Parking lot Exterior Painting Issue:
? Line(s)/Stripe(s)

Assignment Description:
The parking lot need to be strip and paint .
EASTERN HIGH SCHOOL 680885 Odor parking lot Odor Issue:
? Sewage Odor

Assignment Description:
Requesting trash compactor
EASTERN HIGH SCHOOL 675477 Cooling Press box/ football field Cooling Issue:
? AC Unit
? Too Hot

Assignment Description:
Unit not cooling, bad condenser fan
EASTERN HIGH SCHOOL 671123 Roof Press box in the football field Roof Issue:
? Water Leak
? Rooftop

Assignment Description:
Roof is leaking and ceiling towels needs to be changed
EASTERN HIGH SCHOOL 682416 Cooling RTU #2 Possibly bad compressor and bad contractor?.possible bad burner ignition board?also broken condensate line
EASTERN HIGH SCHOOL 682415 Cooling RTU # 5,6,7,&8 They have all lost communication with the EMS . They also need multiple repairs such as a bad gas valves, flame sensors , burned contractors ,pulley , and shives ? need new condensate drain lines
EASTERN HIGH SCHOOL 668778 Roof Second-floor east side atrium Roof Issue:
? Water Leak
? Rooftop

Assignment Description:
Second-floor east side atrium Roof is leaking
EASTERN HIGH SCHOOL 670233 Lighting See Description for details Tennis court lights:
Hi ? one of the light poles at the tennis courts doesn?t light when the rest do.
EASTERN HIGH SCHOOL 658817 Power The marquee  font entrance  east lawn Power Issue:
? Complete Outage
? The emergency lights are working

Assignment Description:
Requesting to have the marquee electrical wiring repair .
EASTERN HIGH SCHOOL 664184 Building Structural (Interior Services) W- 108 Window Issue:
? Below 8 feet /1 story
? Window Glass
? Repair/Replace/Install
? null

Assignment Description:
The main office first window don't stay up .
need CS to have a window contractor to replace the pulleys per size and etc.
EASTERN HIGH SCHOOL 669135 Window(Interior Services) W-119 The exterior window in W-119 is broken . It's a double pane window .
EASTERN HIGH SCHOOL 682440 Cooling W141B and EMT Cooling Issue:
? AC Unit
? No AC

Assignment Description:
Unit inoperable, possible low pressure
EASTERN HIGH SCHOOL 670528 Window W143 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
When it rains water be dripping down it may be the gutters causing this issue.
EASTERN HIGH SCHOOL 680505 Cooling W415,W412,W410,W409,W408,W307,W312,W314 W415-unit is frozen, possible low on refrigerant,W412 not cooling,410 - low pressure, W409 - Bad fan motor,W408 W314 & W307-not proper charge, W312 - low pressure
EASTERN HIGH SCHOOL 682386 Building Structural (Interior Services) Weight Room Structural Issue:
? Wall

Assignment Description:
The mirrors on the walls of the weight room are broken and need to be repaired. The broken mirrors represent a hazard to our students as they can possibly cut our students.

need contract services to replace broken glass with a contractor
EASTERN HIGH SCHOOL 678053 Building Structural Weight room Structural Issue:
? Wall

Assignment Description:
Remove broken mirrors , and install new mirrors .
EASTERN HIGH SCHOOL 680765 Building Structural Weight Room Structural Issue:
? Wall

Assignment Description:
The mirrors on the walls of the weight room are broken and need to be repaired. The broken mirrors represent a hazard to our students as they can possibly cut our students.
EASTERN HIGH SCHOOL 664145 Roof west atrium Roof Issue:
? Water Leak
? Rooftop

Assignment Description:
west atrium roof is leaking .
EASTERN HIGH SCHOOL 666282 Ceiling west wing zone 9 Ceiling Issue:
? Falling (loose) tiles

Assignment Description:
The ceiling need  new brackets install.
EASTERN HIGH SCHOOL 666284 Ceiling zone 5 & 6 gymnasium area Ceiling Issue:
? Falling (loose) tiles

Assignment Description:
The ceiling  new bracket need to be install .
EASTERN HIGH SCHOOL 681473 Lighting Zone 7 Lighting Issue:
? Exterior Lights
? Below one (1) story
? Outside/Building/Street/Parking Lot
? null

Assignment Description:
The exterior light is not working in zone 7
EASTERN HIGH SCHOOL 651508 Interior Painting & Wall Issue zone 9 ramp Interior Painting & Wall Issue:
? Painitng
? Paint Peeling

Assignment Description:
Requesting to have zone 9 ramp floor  paint .
ELIOT-HINE MIDDLE SCHOOL 680946 Grounds 162 B Grounds Issue:
? Bulk Trash

Assignment Description:
BULK TRASH FOR STUDIO CAMERA LIGHTS , AND STUDIO POLE GRIDS /525 order #60240
ELIOT-HINE MIDDLE SCHOOL 678122 Interior Painting & Wall Issue 236 Interior Painting & Wall Issue:
? Patching & Painting
? Painting Maintenance

Assignment Description:
PATCH AND PAINTING NEEDED TO WALLS
ELIOT-HINE MIDDLE SCHOOL 676588 Cooling 372 , 327 261, Kitchen, Lobby Cooling Issue:
? Temperature
? Too Cold

Assignment Description:
ALL ROOMS LISTED NEED A ADJUSTMENT WITH THE TEMPERATURE
ELIOT-HINE MIDDLE SCHOOL 681260 Heating Boiler Room Heating Issue:
? Heating Unit
? No Heat

Assignment Description:
Boilers 1 and 2 have large amounts of scale and need Boiler Maintenance.
ELIOT-HINE MIDDLE SCHOOL 682061 Drain CAFETERIA Odor Issue:
? Sewage Odor

Assignment Description:
FOUL SMELL COMING FROM CLEANOUT FROM FLOOR
ELIOT-HINE MIDDLE SCHOOL 682067 PEST CONTROL CAFETERIA Pest Control Issue:
? School
? Flying Insects

Assignment Description:
PEST CONTROL NEEDED FOR MOSQUITOS IN CAFETERIA.
ELIOT-HINE MIDDLE SCHOOL 681554 Lock and Door G 10 Lock and Door Issue:
? Lock/Latch
? Metal Door
? Repair/Replace/Install Door Lock
? null

Assignment Description:
G10 CLASSROOM EXTERIOR DOOR THAT LEADS OUTSIDE KEYS DONT FIT.
ELIOT-HINE MIDDLE SCHOOL 675282 Window G67 CUSTODIAN OFFICE Window Issue:
? Above 8 feet/1 Story
? Window Glass
? Broken
? null

Assignment Description:
OUTSIDE  WINDOW PANE BROKE.
ELIOT-HINE MIDDLE SCHOOL 674276 Power KITCHEN Power Issue:
? Complete Outage
? The emergency lights are working

Assignment Description:
ELECTRICAL ISSUE WITH CIRCUIT CAUSING BREAKER TO TRIP
ELIOT-HINE MIDDLE SCHOOL 678076 Interior Painting & Wall Issue ROOM 245 Interior Painting & Wall Issue:
? Patching & Painting
? Painting Maintenance

Assignment Description:
PATCH JOB NEEDED FOR FRONT WALL
ELIOT-HINE MIDDLE SCHOOL 681956 Cooling THROUGHOUT Cooling Issue:
? Temperature
? Too Hot

Assignment Description:
AIR IS NOT WORKING IN CERTAIN LOCATIONS THROUGHOUT
J.O. WILSON ELEMENTARY SCHOOL 658568 Window 108 Window Issue:
? Below 8 feet /1 story
? Window Glass
? Broken
? null

Assignment Description:
shattered window pane
J.O. WILSON ELEMENTARY SCHOOL 679689 Cooling 110,211c 1st floor&2nd a technician is needed to investigate and make repair at following location J.O.Wiso
660 k street N.E
Repair or replace defective blower motor bearings, shaft,drive,coupling,pulley, motorize  control valve, and microprocessors board on univent in classroom 110,211c room in alarm readings F1,F8, and de temperature sensor failure rooms are without cooling. Assistance is needed.
J.O. WILSON ELEMENTARY SCHOOL 682558 Window 124 and 123 Window Issue:
? Below 8 feet /1 story
? Window Glass
? Repair/Replace/Install
? null

Assignment Description:
Would like to add shades or window treatment to the ECE rooms.
J.O. WILSON ELEMENTARY SCHOOL 671797 Interior Painting & Wall Issue 1ST, 2ND, & 3RD FLOOR The walls of J.O. Wilson have not been painted in a number of years. When they were last painted, they were painted a very dull, dingy, institutional gray color that is not kid-friendly.  Currently, the walls have a drab look which sends a negative message to both our students and families. As we prepare for a return to school, we are putting a major emphasis on the SEL needs of our students and something as simple as a fresh coat of paint on the walls would send a message of care and love. Having a  fresh coat of paint would help us to debunk the broken window theory and send a message to our students that their learning environment is a priority.
J.O. WILSON ELEMENTARY SCHOOL 652526 Interior Painting & Wall Issue 1ST, 2ND, AND 3RD FLOOR HALLWAYS Interior Painting & Wall Issue:
? Painitng
? Painting Maintenance

Assignment Description:
HALLWAY WALLS ARE IN NEED OF A PAINT JOB.
J.O. WILSON ELEMENTARY SCHOOL 627172 Lock and Door 208 Window Pane Shattered
J.O. WILSON ELEMENTARY SCHOOL 682561 Leak 221 Leak Issue:
? Sink

Assignment Description:
Sink leaks to second floor when turned on.  Student will return to a bathroom with no running water.
J.O. WILSON ELEMENTARY SCHOOL 676695 Interior Painting & Wall Issue 221 Interior Painting & Wall Issue:
? Painitng
? Paint Peeling

Assignment Description:
Paint Walls
J.O. WILSON ELEMENTARY SCHOOL 680875 Window 308 Replace door glass
Lower panel Shattered glass - Computer Lab 308
J.O. WILSON ELEMENTARY SCHOOL 568027 GENERAL SRV 323, 306 Leak in room 306 in the ceiling coming from the roof.
J.O. WILSON ELEMENTARY SCHOOL 682802 Outlet 328B Outlet Issue:
? Repair Outlet
? The conduit is exposed

Assignment Description:
Exposed electrical box/wires
J.O. WILSON ELEMENTARY SCHOOL 682803 Lighting 328B Lighting Issue:
? Interior Lights
? Below 8 feet
? Room(s)/Auditorium/Gymnasium
? null

Assignment Description:
Lights will not come on bulbs have been changed and switch turned on from electrical panel.
J.O. WILSON ELEMENTARY SCHOOL 676470 Interior Painting & Wall Issue blue section on 2nd and 3rd floor Interior Painting & Wall Issue:
? Painitng
? Repaint

Assignment Description:
Walls Painted 2nd and 3rd floor.
J.O. WILSON ELEMENTARY SCHOOL 652527 Building Structural commons area 1st floor Structural Issue:
? Partition

Assignment Description:
replace wall partitions with the permanent walls. This is a safety issue students are climbing walls and hiding from staff.
J.O. WILSON ELEMENTARY SCHOOL 599772 FLOORING c stairwells steps rubber coming off cause students and staff to trip.
J.O. WILSON ELEMENTARY SCHOOL 578727 Flooring (Interior Services) ECE 109 The leak that?s causing damage to the floor is still active. Once the leak is fixed the school want the vinyl sheet removed and replaced with new vinyl sheet. Work needs to be completed by C/S.
J.O. WILSON ELEMENTARY SCHOOL 671759 Fire Extinguisher Kitchen JO Wilson ES.  ***(ABATED AND CORRECTED by DGS Contract Services ; CLOSE OUT WORK ORDER)*** 

VAMP Emergency Priority I/Emergency Repair)
IFC 904.12.6.2   Operation and Maintenance (Inspection/Testing) ? Kitchen Ansul Suppression system
Kitchen - Service, update and re-tag expired (July 2020 ) Ansul kitchen fire suppression system.  Implement service PM plan to update every 6-mos as required bit IFC/ FEMS Inspector.
J.O. WILSON ELEMENTARY SCHOOL 674713 Grounds K Street West Ext door Ground Grounds Issue:
? Grass

Assignment Description:
Sink Hole - Please fill
J.O. WILSON ELEMENTARY SCHOOL 669564 Heating Outside/storage room Technical is needed to investigate and make repair at following location urgent
Repair/replace ruptured pipe hot water supply line leaking .
You Assistant is needed
J.O. WILSON ELEMENTARY SCHOOL 593787 Playground (Exterior Services) PLAYGROUND EQUIPMENT SEVERAL PIECES OF EQUIPMENT NEED TO BE SERVICED
ECE Playground: There is a large crack in the slide that is hazardous and there is a missing step on the monkey bars. Has been cited by OSSE inspection.

POC Tony Rich @ 2024121713
J.O. WILSON ELEMENTARY SCHOOL 673818 Window West Entrance Window Issue:
? Below 8 feet /1 story
? Window Glass
? Broken
? null

Assignment Description:
Replace shattered lower panel window
J.O. WILSON ELEMENTARY SCHOOL 614486 Fire Sprinkler whole bldg sprinkler inspections
JEFFERSON MIDDLE SCHOOL 625821 Lock and Door 134, 301, 219, 234, 210, 205 208, 207, The door glass is cracked in each of these classrooms 134, 301, 219, 234, 210, 205 208, 207,
JEFFERSON MIDDLE SCHOOL 631800 Lock and Door 143 Lock and Door Issue:
? Door
? Metal Door
? Repair/Replace/Install Door/Door Frame
? null

Assignment Description:
The glass in the door is cracked. This is room 143
JEFFERSON MIDDLE SCHOOL 631801 Lock and Door 147 Lock and Door Issue:
? Door
? Metal Door
? Repair/Replace/Install Door/Door Frame
? null

Assignment Description:
The door glass in from 147 is cracked
JEFFERSON MIDDLE SCHOOL 678489 Outlet 222 and 320 Outlet Issue:
? Repair Outlet
? The conduit is not exposed

Assignment Description:
Need special outlet for Sharp copiers in both rooms. there is a  "regular" outlet. we need it switched. They should be near the existing data port to allow for network connectivity.
JEFFERSON MIDDLE SCHOOL 621304 Building Structural (Interior Services) 225 This school is still under warranty by the contractor, please forward to capital construction.
Glass was broken due to contractor, glass is being order under them.
JEFFERSON MIDDLE SCHOOL 626231 Lock and Door 228 the door glass is cracking
JEFFERSON MIDDLE SCHOOL 678502 Lighting 2nd floor hallway Lighting Issue:
? Interior Lights
? Above 8 feet
? Hallway
? null

Assignment Description:
The lcd light is not working.
JEFFERSON MIDDLE SCHOOL 657162 Building Structural (Interior Services) 302 Leak Issue:
? Ceiling

Assignment Description:
Water Leak//water coming in thru window seal
JEFFERSON MIDDLE SCHOOL 638426 Building Structural (Interior Services) 305 crack in door glass of classroom 305

building under warranty need to go to capital construction
JEFFERSON MIDDLE SCHOOL 681501 Leak Boiler room Leak Issue:
? Pipe / Line / Drain

Assignment Description:
Leak on the domestic water line.
JEFFERSON MIDDLE SCHOOL 678512 Cooling building Cooling Issue:
? Temperature
? Too Cold

Assignment Description:
it is very cold in the building. staff and students are complaining even with sweaters on. Can the set point be changed to make the building warmer. We were told it is only something that can be done by DGS remotely
JEFFERSON MIDDLE SCHOOL 682070 Interior Painting & Wall Issue Cafeteria These Tiles NEed to be changed Fingers cut
JEFFERSON MIDDLE SCHOOL 680641 Environmental cafeteria Environmental Issue:
? Air Quality
? Air Filters

Assignment Description:
We have 6 air purifiers that are not working properly.
JEFFERSON MIDDLE SCHOOL 666902 Heating Cafeteria and Kitchen Heating Issue:
? Temperature
? Too Cold

Assignment Description:
The space are not heating up to temperature. They are cold, making it hard for staff to work, make food for students.
JEFFERSON MIDDLE SCHOOL 634664 Lock and Door classroom 138 Lock and Door Issue:
? Door
? Metal Door
? Repair/Replace/Install Door/Door Frame
? null

Assignment Description:
The door glass of room 138 is cracked
JEFFERSON MIDDLE SCHOOL 626840 Building Structural (Interior Services) classroom 203 glass door is crack and need a glass contractor to replace the glass. Door glass is broken
JEFFERSON MIDDLE SCHOOL 680952 Fire Extinguisher Fire Marshall says all the steamers need t0 be tagged Fire Marshall says all the steamers need t0 be tagged
JEFFERSON MIDDLE SCHOOL 662103 Interior Painting & Wall Issue first floor student restrooms Interior Painting & Wall Issue:
? Patching & Painting
? Caulking

Assignment Description:
The soap dispensers are broken and we need new ones installed (total of 2)
JEFFERSON MIDDLE SCHOOL 643950 FLOORING Gym Flooring Issue:
? Wood
? Repair/Replace
-Broken/Cracked/Damaged

Assignment Description:
The Gym is rented out to local groups within the community and the last group that rented out the gym caused damaged to the floor by  removing the volleyball post and caused the wooden floors to lift.  Now there is a hazardous hole in the middle that was caused by a user  with a building use agreement with Reality (DC Fray) This is a hazard to our students, staff and users from the community. timeline 02/27/2020
JEFFERSON MIDDLE SCHOOL 676513 Fire Extinguisher Kitchen Jefferson MS (VAMP Emergency Priority I/Emergency Repair)
IFC 904.12.6.2   Operation and Maintenance (Inspection/Testing) ? Kitchen Ansul Suppression system
Kitchen ?  Service update and re-tag expired (Aug 2020) Ansul kitchen fire suppression system.  Implement service PM plan to update every 6-mos as required bit IFC/ FEMS Inspector.

Extinguishing system service: Automatic fire-extinguishing systems shall be serviced at least every six months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.  FEMS LVL-2
JEFFERSON MIDDLE SCHOOL 666998 Fire Extinguisher L05 Office Jefferson MS   (VAMP Routine Priority III/Routine Repair)
IFC 901.6 Inspection, Testing & Maintenance - Fire Extinguishers
Room L05 Office - Service, update and re-tag all expired (April 2019) ABC portable fire extinguisher.
FEMS Lvl-2
JEFFERSON MIDDLE SCHOOL 627730 Building Structural (Interior Services) l24 The tile on the wall to the left is broken only due to the installation was not install correct.
we found that the tile pcs are hollow behind them. this need to go back to CCT
JEFFERSON MIDDLE SCHOOL 673199 Window Need to be fix Window Issue:
? Below 8 feet /1 story
? Window Glass
? Broken
? null

Assignment Description:
JEFFERSON MIDDLE SCHOOL 664792 Lock and Door Outside Lock and Door Issue:
? Lock/Latch
? Automatic Door
? Locksmith
? null

Assignment Description:
Key card don't work  need a locksmith
JEFFERSON MIDDLE SCHOOL 628957 Fence and Gate parking area The bollards in front of the staff parking are not secured correctly
JEFFERSON MIDDLE SCHOOL 677208 Parking Lot Parking Lot The parking lot gate has a malfunction
JEFFERSON MIDDLE SCHOOL 664559 Heating Roof Heating Issue:
? Heating Unit
? Too Cold

Assignment Description:
Repair/replace inoperable fan on RTU #1. Serves lower level of facility. Level without heat. BPO Wright 202-345-7587
JEFFERSON MIDDLE SCHOOL 642588 Athletic Field Tennis Courts Athletic Facility Issue:
? Tennis Court
? Field Repair

Assignment Description:
Court crack repair needed.  Cracks on the playing surface are starting to get larger in size and will compromise the integrity of the asphalt if not repaired.
JEFFERSON MIDDLE SCHOOL 679936 Athletic Field Tennis Courts Athletic Facility Issue:
? Tennis Court
? Grass/Weed Removal

Assignment Description:
There are giant weeds and shrubs growing across the entry gate to the tennis courts, on the sides of the perimeter fencing, and on the smaller tennis court towards the building there are branches that stick out making it impossible to use the court.  See attached pictures.  Removal requested please.  Thank you
JEFFERSON MIDDLE SCHOOL 676514 Fire Extinguisher Various Jefferson MS   (VAMP Priority III/Routine Repair)
IFC 901.6 Inspection, Testing & Maintenance
Maintenance service required - inspect and test portable ABC fire extinguishers in the following locations; .
; .
? Corridor next to room 307 ? Inspect, service and re-tag untagged portable ABC fire extinguishers.
? Corridor near room L42 ? Inspect, service and re-tag untagged portable ABC fire extinguisher.
? Corridor near cafeteria next to room L05 office - Service, inspect and test expired (Aug 2019) portable ABC fire extinguisher.

Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer?s installation instructions.  FEMS Lvl-2
LUDLOW-TAYLOR ELEMENTARY SCHOOL 674620 Window 103 Room 103 on the 1st floor outside window has is cracked.
LUDLOW-TAYLOR ELEMENTARY SCHOOL 661177 Leak 132,hall,kitchen Leak Issue:
? Ceiling

Assignment Description:
Ceiling leaks when it rain across room 132(after care storage),hall,kitchen,to the back door. Think it?s a roof problem.
LUDLOW-TAYLOR ELEMENTARY SCHOOL 668011 Building Structural 3rd Floor Structural Issue:
? Wall

Assignment Description:
Toilet paper dispenser and tile was set on fire
LUDLOW-TAYLOR ELEMENTARY SCHOOL 665382 Building Structural (Interior Services) Baseball field Fence and Gate Issue:
? Fence Only
? Repair Fence

Assignment Description:
Hole in the fence on Morrison Pl. baseball field.
LUDLOW-TAYLOR ELEMENTARY SCHOOL 657972 Playground Basketball court Playground Issue:
? Grounds/Fence/Turf
? Turf

Assignment Description:
The basketball court on the playground has cracks in the ground.
LUDLOW-TAYLOR ELEMENTARY SCHOOL 664542 Pipe Boiler Pipe Issue:
? Water
? Leak

Assignment Description:
Boiler room room pipe is leaking from the ceiling
LUDLOW-TAYLOR ELEMENTARY SCHOOL 673626 Fire Extinguisher Boiler Room and Kitchen Ludlow-TaylorES  (VAMP Priority III/Routine Repair)
IFC 901.6 Inspection, Testing & Maintenance
Expired fire extinguishers
? Boiler Room below stairs inside fire extinguisher cabinet ? Service and update expired (June 2019) portable fire extinguisher.  Remove the entire fire extinguisher cabinet and re-locate and anchor mount on masonry wall near exterior exit door.

IFC 906.7 Hangers and brackets.
Mount fire extinguishers in the following locations;
? Kitchen -  Provide and mount K-class fire extinguisher on masonry wall as required by the FEMS Inspector.

Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer?s installation instructions. FEMS Lvl-2
LUDLOW-TAYLOR ELEMENTARY SCHOOL 673625 Fire Extinguisher Kitchen Ludlow-Taylor ES (VAMP Emergency Priority I/Emergency Repair)
IFC 904.12.6.2   Operation and Maintenance (Inspection/Testing) ? Kitchen Ansul Suppression system
Kitchen ?  Service update and re-tag expired (Sept 2020).  (Note: Service Tags were scribed ?Lincoln? oppose to Langley.) Ansul kitchen fire suppression system.  Implement service PM plan to update every 6-mos as required bit IFC/ FEMS Inspector.

 Extinguishing system service: Automatic fire-extinguishing systems shall be serviced at least every six months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.  FEMS LVL-2
LUDLOW-TAYLOR ELEMENTARY SCHOOL 664911 Window Library 310 Window Issue:
? Above 8 feet/1 Story
? Window Glass
? Repair/Replace/Install
? null

Assignment Description:
Library window cracked.Room 310 3rd floor
LUDLOW-TAYLOR ELEMENTARY SCHOOL 660749 FIRE ALARM Lobby Fire Alarm Issue:
? Panel

Assignment Description:
Fire alarm panel has trouble signal flashing..
LUDLOW-TAYLOR ELEMENTARY SCHOOL 682650 Cooling Room 208 Cooling Issue:
? AC Unit
? Too Hot

Assignment Description:
AC is not working.
LUDLOW-TAYLOR ELEMENTARY SCHOOL 664899 Lighting Several Lighting Issue:
? Interior Lights
? Below 8 feet
? Room(s)/Auditorium/Gymnasium
? null

Assignment Description:
Need light covers in classrooms,closets,hallway,and bathrooms.
Pictures attached with room numbers and covers.
MAURY ES 651697 Building Structural (Interior Services) 103B Window Issue:
? Below 8 feet /1 story
? Window Glass
? Repair/Replace/Install
? null

Assignment Description:
Broken window
need contract services to provide a glass company to install new glass.
MAURY ES 662421 Window 108 Principals Office Window Issue:
? Below 8 feet /1 story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Window wont open because handle is broken.  Principal is working on site and would like ventilation for covid protection.
MAURY ES 673898 Fire Alarm (Life Safety Services) 126 ? Wall

Assignment Description:
Fire alarm strobe lights cover missing
MAURY ES 659577 Building Structural 137 Art Room Structural Issue:
? Ceiling

Assignment Description:
Same leak from modernization.
MAURY ES 631517 Lock and Door 138C Lock and Door Issue:
? Door
? Standard Door
? Repair/Replace/Install Door/Door Frame
? null

Assignment Description:
Modernization:  Kitchen Dry Storage Room never had glass put in the door.
MAURY ES 651622 Lock and Door 13th Street Entrance Lock and Door Issue:
? Lock/Latch
? Handicap Entrance/Door
? Repair/Replace/Install Door/Door Frame
? null

Assignment Description:
ADA door does not shut all the way
MAURY ES 659579 Building Structural 211 Ms Battle Room Structural Issue:
? Ceiling

Assignment Description:
Water leak ceiling.
MAURY ES 651605 Building Structural 216 Structural Issue:
? Ceiling

Assignment Description:
WAP and wire hanging from ceiling
MAURY ES 662411 Window 302, 303 Window Issue:
? Below 8 feet /1 story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Blinds were not installed with modernization like the other classrooms.  The picture shows one window with and one without.
MAURY ES 659580 Building Structural 327 Structural Issue:
? Wall

Assignment Description:
Water leak from modernization in corner office.
MAURY ES 676140 Lighting 3rd floor hall historic Lighting Issue:
? Interior Lights
? Above 8 feet
? Hallway
? null

Assignment Description:
New light out.  Dont know if its bulb, ballast?  Foreman doesnt know how to change.
MAURY ES 662577 Heating 3rd floor multiple rooms Heating Issue:
? Thermostat
? Too Cold

Assignment Description:
Thermostats are blinking.  Temp in the 60s.
MAURY ES 636304 Outlet Art Room Outlet Issue:
? Repair Outlet
? The conduit is not exposed

Assignment Description:
Modernization:  Kiln never worked.  Outlet needs to be tested.  All three wires have to carry proper current.  They are at 114 volts.  They need to each be 208 per SKUTT which is manufacturer of the kiln.
MAURY ES 670586 Playground Basketball court Playground Issue:
? Equipment
? Repair/Remove/Replace Equipment

Assignment Description:
Basketball Stand/hoop broken
MAURY ES 630677 Window Cafeteria Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Modernization:  Electronic blinds dont close.
MAURY ES 681562 Building Structural Cafeteria Structural Issue:
? Partition

Assignment Description:
Partition Wall installed with modernization has broken several times.  It will not move.
MAURY ES 676136 Ceiling cafeteria by art room Ceiling Issue:
? Damaged Tiles

Assignment Description:
Roof Leak
MAURY ES 670506 Building Structural Cafeteria ceiling above PE office Structural Issue:
? Ceiling

Assignment Description:
Leak in ceiling and its caused damage to bricks below it.  I cant tell if bricks are dangerously loose.
MAURY ES 670587 MASONRY Exterior Building Wall Masonry Issue:
? Wall
? Tile

Assignment Description:
Panels of modernization exterior wall have been damaged.
MAURY ES 673502 Building Structural (Interior Services) Exterior Perimeter Window Issue:
? Below 8 feet /1 story
? Window Glass
? Broken
? null

Assignment Description:
The two windows are located on the 12th Place side of the building, right at the corner of 12th Place and Constitution Ave NE. Both windows remain intact, however, they are visibly damaged and can possibly be broken inwards if not fixed in a timely manner. The windows are located on the ground floor. I completed my perimeter check with negative results, the building is secure.

need contract service to repair with a glass contractor.
MAURY ES 662548 Building Structural (Interior Services) First floor hall by room 127 Flooring Issue:
? Tile
? Repair/Replace

Assignment Description:
Tile coming up
building is still under warranty
MAURY ES 634994 Building Structural Library Structural Issue:
? Ceiling

Assignment Description:
Modernization:  Did not install an intercom.  Communication does not happen between library and main office.  Unsafe for student tracking, lockdown scenarios, and teacher information.
MAURY ES 675845 Cooling Library Repair/Replace inoperable t-stats in the library, 3rd floor historic hallway and room 316, areas are without extremely hot.
MAURY ES 651610 Building Structural Main Entrance Structural Issue:
? Ceiling

Assignment Description:
Vent hole needs a cover
MAURY ES 663854 Heating Main Entrance Lobby Heating Issue:
? Heating Unit
? Too Cold

Assignment Description:
The individual heater is not working.  This is where the Nurses take temperatures of students coming in the building.  Its cold in that section and the heater wont turn on.
MAURY ES 674073 Lock and Door Maury ES ? New Key(s) Replace Key(s)

Assignment Description:
Council has a requested hose bibb  and water keys for Maury ES so that the school community can water the trees and plants there.
MAURY ES 675300 Cooling Rooftop Units and classrooms BMS to make adjustments to the cooling setpoints, setpoints kept changing back from 72 degrees to 81 degrees.  I also found  several compressors on the Roof Top Units that were in alarm as well (see picture).....please provide Contractor support to address the cooling issues at Maury.  Classrooms 327, 326, 324, 323, 322, 320, 319, 315, Hallway 328, Stairway 1.
MAURY ES 666785 Window room 302 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Window leaking.  You can see water stains on white top surface.  Starting in the Southwest corner of the room, its the third window.
MAURY ES 666786 Building Structural room 302 Structural Issue:
? Wall

Assignment Description:
Window blinds were not installed with new building in this room.  All other rooms have shades.
MAURY ES 669821 Building Structural School flag pole broken:  The wire that hangs/holds the flag broke inside the pole. Structural Issue:
? Floor/Ground

Assignment Description:
School flag pole broken:  The wire that hangs/holds the flag broke inside the pole.
MAURY ES 670764 Heating Several Rooms Heating Issue:
? Thermostat
? Too Hot

Assignment Description:
Something happened over the weekend.  Many thermostats are not cooling.  Its 80 degrees in some rooms
MAURY ES 634995 Sidewalks Sidewalk on 13th Street NE Sidewalk Issue:
? Concrete Pavement
? Broken Damaged

Assignment Description:
Modernization:  Storm grate that was installed is not safe for kids and animals.  Community is upset and complaining kids and animals have to walk into the street
MAURY ES 659578 Building Structural Stair 1 Structural Issue:
? Wall

Assignment Description:
Stairwell leak since modernization.
MAURY ES 670504 Building Structural Whole school Structural Issue:
? Wall

Assignment Description:
Clocks need to be recalibrated.  They are not showing correct time.
MAURY ES 670584 Hot Water Whole school Hot Water Issue:
? Temperature

Assignment Description:
Faucets do not get hot.  They also dont run long enough to wash hands.
MAURY ES 670505 Building Structural Whole school:  BELLS Structural Issue:
? Wall

Assignment Description:
The bell schedule needs to be changed to 8:30am, 8:45am, 3:15am
MINER ELEMENTARY SCHOOL 672550 Window Cafeteria exterior door Window Issue:
? Below 8 feet /1 story
? Window Glass
? Broken
? null

Assignment Description:
Bottom glass on cafeteria door looked like it was kicked and is now broken.
MINER ELEMENTARY SCHOOL 677838 Leak Cafeteria Kitchen Leak Issue:
? Sink

Assignment Description:
Sink leaking from filter
MINER ELEMENTARY SCHOOL 680069 Cooling Entire building Cooling Issue:
? AC Unit
? No AC

Assignment Description:
The AC unit has not been working consistently for the past 3 days.
MINER ELEMENTARY SCHOOL 655459 Fence and Gate K-5 Playground Fence and Gate Issue:
? Gate
? Repair Gate

Assignment Description:
There are two current issues. 
1) students are able to stand on the hand railing and jump up and over the fence which has caused a problem with vandalism on the playground regularly. 
2) the gate now has two cut-outs above the push bar that need to be repaired on both gates - 15th st and 16th street.   

To remedy this we need the mesh on the gate fixed and we are asking that the fence surrounding the door be raised another several feet to make it impossible to climb over.
MINER ELEMENTARY SCHOOL 572107 OTHER MASONRY Outside Structur The expansion joints at the base of the school near the front entrance and the concrete sidewalk have deteriorated allowing water and ice to get underneath. This corroded caulking is present around the entire building structure.

The many openings are large crevices pose a safety hazard for children foot traffic and hands possibly being injured. The openings also provide rodents locations to nest and mate within a very close proximity of the school and students.
MINER ELEMENTARY SCHOOL 672549 Playground Playground on the left side of the building Playground Issue:
? Equipment
? Repair/Remove/Replace Equipment

Assignment Description:
One of the anchors of the swing came off.
MINER ELEMENTARY SCHOOL 674062 Grounds Playgrounds Remove small rock beds from
ECE & 3-5 Playgrounds please. 
5 small rock beds
MINER ELEMENTARY SCHOOL 666232 Roof Roof/drain by loading dock. Room 167 Roof Issue:
? Water Leak
? Rooftop

Assignment Description:
Custodian office is leaking. Foreman checked roof, noticed a thick sheet of ice over drain. Water is sitting
MINER ELEMENTARY SCHOOL 679584 Cooling Rooftop The Chiller goes into alarm saying Evaporator Flow Switch Alarm
MINER ELEMENTARY SCHOOL 682278 Cooling Rooftop area It was reported by the Protech Contractor that #2 Compressor on the Chiller is bad and it needs replacing
MINER ELEMENTARY SCHOOL 679168 Leak Room 140; Workroom in the library Leak Issue:
? Ceiling

Assignment Description:
The ceiling has been leaking. The drain is above this room
MINER ELEMENTARY SCHOOL 673900 Fire Sprinkler Sprinkler Room Miner ES (VAMP Emergency Priority I/Emergency Repair)
IFC 907.8.5 - Inspection, testing and maintenance
IFC 903.5 - Testing and maintenance: Sprinkler systems shall be tested and maintained in accordance with Section 901.
Throughout Building ing  (The sprinkler pressure is low, and shall be address immediately.

The building owner shall be responsible to maintain the fire and life safety systems in an operable condition at all times. Service personnel shall meet the qualification requirements of NFPA 72 for inspection, testing and maintenance of such systems. Records of inspection, testing and maintenance shall be maintained.
MINER ELEMENTARY SCHOOL 660614 FIRE ALARM Throughout Fire Alarm Issue:
? Fire Code (IFC)

Assignment Description:
Minor ES (VAMP Emergency Priority I/Emergency Repair)
IFC. 907.8.5 - Inspection, testing and maintenance:
Fire Alarm in trouble mode Fault command indicates Second floor zone 1 duct & smoke detector Mechanical room air handler unit -4.  Abatement repairs are required immediately by the FEMS Inspector.  Service, repair  and test fire alarm system and provide copies of service maintenance documentation and records for review as required by the FEMS Inspector. The building owner shall be responsible to maintain the fire and life safety systems in an operable condition at all times. Service personnel shall meet the qualification requirements of NFPA 72 for inspection, testing and maintenance of such systems. FEMS Lvl-2
MINER ELEMENTARY SCHOOL 682101 Cooling Whole building Cooling Issue:
? AC Unit
? Central Air

Assignment Description:
AC unit (chiller) went out. The building is humid. Floors, doors, countertops are sweating due to no air /humidity.
MINER ELEMENTARY SCHOOL 672630 Building Structural (Interior Services) Window is stairwell between the Orange and Blue hallway Window Issue:
? Above 8 feet/1 Story
? Window Glass
? Broken
? null

Assignment Description:
Both windows are cracked.
windows need to be replace by a glass contractor
PAYNE ELEMENTARY SCHOOL 676183 Building Structural (Interior Services) 3rd floor staircase-1 Payne ES. VAMP High Priority II/Priority Repair)
IFC 1010.1.9.1 ? Damaged Hardware
IFC 703.2.3 - Door operation
3rd floor stair #1 ? Fire exit door not latching/closing properly.  Repair internal vertical rod and latch on right door.  Right exit door closer arm detached; reattach arm to closer track; adjust hinges realign both doors.
Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. FEMS Lvl-2

From Craft Person Assignment: Forward this work order to contract services to repair double doors with panic exit devices with Internal vertical rods @Andre Thompson @Randolph Tobin @Antonio Simms
PAYNE ELEMENTARY SCHOOL 677451 Building Structural (Interior Services) 3rd floor staircase-2 Payne ES. VAMP High Priority II/Priority Repair)
IFC 1010.1.9.1 ? Damaged Hardware
IFC 703.2.3 - Door operation
3rd floor staircase-2 ? Door not latching/closing properly.  Repair internal vertical rod and latch on right door.

Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. FEMS Lvl-2

need Contract service to replace or repair the interior rods of the door.
PAYNE ELEMENTARY SCHOOL 670808 Building Structural All Stairwells Structural Issue:
? Wall

Assignment Description:
Repair crumbling plaster walls - all stairwells
PAYNE ELEMENTARY SCHOOL 678762 Interior Painting & Wall Issue BES Room, Payne ES Interior Painting & Wall Issue:
? Patching & Painting
? Painting Maintenance

Assignment Description:
There are 4 walls where drywall was hung.  The drywall needs to be taped, mudded, sanded, and then painted to be finished.
PAYNE ELEMENTARY SCHOOL 616923 FLOORING Cafeteria Floor please repair floor tiles
PAYNE ELEMENTARY SCHOOL 676386 Pipe Exterior, 14th Street, Outside Media Center Pipe Issue:
? Valve
? Installation

Assignment Description:
The bib is not functioning.  We need it to be functional for watering, cleaning, and operation of school science program.
PAYNE ELEMENTARY SCHOOL 680913 MASONRY Exterior, 14th street side Masonry Issue:
? Walkway
? Tile

Assignment Description:
The sidewalk is broken and a hazard. It needs to be removed to make room for a community garden.
PAYNE ELEMENTARY SCHOOL 676390 Sidewalks Exterior, Sidewalk, 14th Street Side of building Sidewalk Issue:
? Concrete Pavement
? Broken Damaged

Assignment Description:
The sidewalk is destroyed.
PAYNE ELEMENTARY SCHOOL 654718 FIRE ALARM First floor Fire Alarm Issue:
? Repair

Assignment Description:
Troubleshoot and repair fire alarm.  POC:  439-8271
PAYNE ELEMENTARY SCHOOL 679596 Roof Front Entrance Overhang Roof Issue:
? Roof Damage

Assignment Description:
There is clear and obvious water damage indicating a leak in the roof.
PAYNE ELEMENTARY SCHOOL 625049 Lock and Door Front Lobby Door The front lobby middle door inside is not locking properly with the door handle.  The small bar is not locking the door.
PAYNE ELEMENTARY SCHOOL 676109 Cooling Ms. Baggett's Room, 136 Cooling Issue:
? AC Unit
? Central Air

Assignment Description:
The air conditioning unit stopped working.
PAYNE ELEMENTARY SCHOOL 675105 Cooling RM#136 Classroom not cooling thermostat blinking code CH05
PAYNE ELEMENTARY SCHOOL 676048 Fire Extinguisher Room 134 Kindergarten Payne ES  (VAMP Priority III/Routine Repair)
IFC 901.6 Inspection, Testing & Maintenance
Room 134 Kindergarten ? Service, inspect expired (July 2019) portable ABC fire extinguisher.

Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer?s installation instructions.  FEMS Lvl-2
PAYNE ELEMENTARY SCHOOL 654950 Roof (Exterior Services) Throughout NOTE:Roof leaking when it rains, customer requesting that the roof repaired be for we install ceiling tiles, this is the 3rd time tiles have been replaced.
Ceiling Tiles missing throughout the school, ceiling tiles need to be repaired/replaced
PEABODY ELEMENTARY SCHOOL 653886 Interior Painting & Wall Issue 1,2,3,basement floor lobby Interior Painting & Wall Issue:
? Patching & Painting
? Repaint

Assignment Description:
The walls need to be repainted.
PEABODY ELEMENTARY SCHOOL 655667 Window(Interior Services) 2nd floor Ceiling Issue:
? Damaged Tiles

Assignment Description:
The classroom ceiling is leaking water//Water is coming thru around window frame when it rain
PEABODY ELEMENTARY SCHOOL 618135 Lock and Door 5 street side exit door. The handicap access door push button is not working
PEABODY ELEMENTARY SCHOOL 655834 Building Structural All Levels Structural Issue:
? Wall

Assignment Description:
Water clean up
PEABODY ELEMENTARY SCHOOL 658208 Building Structural (Interior Services) Back door landing  by play ground Flooring Issue:
? Tile
? Broken/Cracked/Damaged

The floor is not a tile floor but its painted, ticket has been forward to the paint shop.

Assignment Description:
Floor needs repair
PEABODY ELEMENTARY SCHOOL 665154 Power Building Power Issue:
? Complete Outage
? The emergency lights are working

Assignment Description:
Cut,Cap, Make safe basement electrical.
PEABODY ELEMENTARY SCHOOL 654829 Fire Sprinkler Fire Sprinkler Fire Sprinkler Issue:
? Maintenance

Assignment Description:
Repair water gauge & relocate sprinkler head
PEABODY ELEMENTARY SCHOOL 611685 Window Library There are 10 electrical window shades that will  not got up .
PEABODY ELEMENTARY SCHOOL 652232 Lighting Outside Lighting Issue:
? Exterior Lights
? Above one (1) story
? Outside/Building/Street/Parking Lot
? null

Assignment Description:
the large light in the alley that's attached to the building, that covers the perimeter of the alley is not working, this work order is not a duplicate of work order  # 617950 this is a different outside light.
PEABODY ELEMENTARY SCHOOL 629680 Railing and Step Outside alley The railing located by the boiler room steps are in danger of failing.
PEABODY ELEMENTARY SCHOOL 647942 Railing and Step OUT SIDE ALLEY 5 STREET SIDE Railing and Step Issue:
? Rail

Assignment Description:
The railing next to the boiling room step is in danger of falling down the steps.
PEABODY ELEMENTARY SCHOOL 655832 Building Structural Third Floor Structural Issue:
? Wall

Assignment Description:
Structural assessment of fire
SCHOOL WITHIN SCHOOL @ GODING 642781 Electronic Security Issue 407 Electronic Security Issue:
? Not Working

Assignment Description:
the telephone will not come on getting no power
SCHOOL WITHIN SCHOOL @ GODING 614216 Fire Extinguisher all building kitchen suppression system inspection
SCHOOL WITHIN SCHOOL @ GODING 651354 Pipe Boiler room ground floor Pipe Issue:
? Water
? Leak

Assignment Description:
main water line continue to leak a new situation from the one in the past critical
SCHOOL WITHIN SCHOOL @ GODING 622915 Fire Sprinkler building Repair fire sprinkler system
SCHOOL WITHIN SCHOOL @ GODING 611802 Switch Cafeteria Switch in panel box is trip for the handicap lift to operate
SCHOOL WITHIN SCHOOL @ GODING 659707 FIRE ALARM CARE Room 101 Fire Alarm Issue:
? Repair

Assignment Description:
Verification of Fire Alarm Phone Line
SCHOOL WITHIN SCHOOL @ GODING 635296 Environmental Custodial storage room ground Environmental Issue:
? Fire
? Fire Code

Assignment Description:
On the ground Florida pull station for the alarm and foddrill the battery is dead critical
SCHOOL WITHIN SCHOOL @ GODING 673375 FIRE ALARM fire alarm repair phone dialers Fire Alarm Issue:
? Repair

Assignment Description:
fire alarm repair phone dialers
SCHOOL WITHIN SCHOOL @ GODING 651759 Building Structural Room oo5 Structural Issue:
? Wall

Assignment Description:
ground floor everytime it rain water comes through the wall causing structural damage
SCHOOL WITHIN SCHOOL @ GODING 671976 Grounds Trailer number 4 Front door will not open can not unlock the door
SEATON ELEMENTARY SCHOOL 682528 Lighting 107 Lighting Issue:
? Interior Lights
? Above 8 feet
? Room(s)/Auditorium/Gymnasium
? null

Assignment Description:
I changed  all the lights and two of them keep going back  out. Ballast
SEATON ELEMENTARY SCHOOL 675576 Cooling (HVAC Services) 108 Leak Issue:
? Pipe / Line / Drain

Assignment Description:
Leaking from pipe in the ceiling // This is the HVAC condensate problem refer to HVAC
SEATON ELEMENTARY SCHOOL 659608 Heating 1st fl cafeteria/ multi purpose rm Heating Issue:
? Heating Unit
? Too Cold

Assignment Description:
Leak on supply heating line for AHU
SEATON ELEMENTARY SCHOOL 664360 Interior Painting & Wall Issue 2025829279 Interior Painting & Wall Issue:
? Painitng
? Repaint

Assignment Description:
Radiator cover rusty may harm kids need to be replaced
SEATON ELEMENTARY SCHOOL 682544 Cooling 205 2nd floor Cooling Issue:
? Thermostat
? Too Hot

Assignment Description:
A/C unit blowing out  warm  air
SEATON ELEMENTARY SCHOOL 674093 Interior Painting & Wall Issue 2nd floor  boys restroom Interior Painting & Wall Issue:
? Painitng
? Painting Maintenance

Assignment Description:
Very rusty need to be painted
SEATON ELEMENTARY SCHOOL 675561 Cooling (HVAC Services) 2nd floor  girls  restroom Leak Issue:
? Source Unknown

Assignment Description:
Leaking from ceiling // This is an HVAC condensate problem refer to HVAC department
SEATON ELEMENTARY SCHOOL 671675 Ceiling 2nd floor Storage Room Seaton ES (VAMP High Priority II/Priority Repair)
IFC 703.3  Ceilings-Maintenance/Opening Protectives
Second floor Storage room ? Patch, resurface and paint several breach holes around pipe penetrations on plaster ceiling surface.

  The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be visually inspected by the owner annually and properly repaired, restored or replaced when damaged, altered, breached or penetrated. FEMS Lvl-2
SEATON ELEMENTARY SCHOOL 676669 Cooling 309 Cooling Issue:
? AC Unit
? Too Hot

Assignment Description:
Both a/c unit blowing out warm air
SEATON ELEMENTARY SCHOOL 675563 Cooling (HVAC Services) Boiler room Leak Issue:
? Pipe / Line / Drain

Assignment Description:
Leaking from pipe causing water to settle  on the floor //This is the HVAC condensate problem refer to HVAC
SEATON ELEMENTARY SCHOOL 678435 Pipe Boiler room Pipe Issue:
? Water
? Installation

Assignment Description:
Replace water treatment system
SEATON ELEMENTARY SCHOOL 624904 Ceiling cafeteria everytime it rain it leaks
SEATON ELEMENTARY SCHOOL 665496 Heating Cafeteria Heating Issue:
? Heating Unit
? Too Cold

Assignment Description:
AHU has control issue
SEATON ELEMENTARY SCHOOL 678414 Cooling Cafeteria Cooling Issue:
? AC Unit
? HVAC Leak

Assignment Description:
Leaking from ceiling causing puddles of water
SEATON ELEMENTARY SCHOOL 663725 Heating Conference room Heating Issue:
? Heating Unit
? Too Cold

Assignment Description:
Univent blowing out cold air
SEATON ELEMENTARY SCHOOL 678505 Heating First Floor Boy's Bathroom Heating Issue:
? Heating Unit
? No Heat

Assignment Description:
Uninstalled unit sitting in front of old, broken unit
SEATON ELEMENTARY SCHOOL 668874 Fence and Gate Front of building Fence and Gate Issue:
? Gate
? Repair Gate

Assignment Description:
Someone  ran into gate causing  it to break
SEATON ELEMENTARY SCHOOL 676033 Cooling IT room 3rd floor Cooling Issue:
? AC Unit
? Too Hot

Assignment Description:
Too hot unit not working
SEATON ELEMENTARY SCHOOL 644539 Roof (Exterior Services) Kitchen Leak Issue:
? Roof

Assignment Description:
The Plumbers abated this concern and determined that they  Investigated complaint of water leaking from ceiling after close check found leak not coming from any water feed, this appears to be coming from the roof.
SEATON ELEMENTARY SCHOOL 671678 Fire Extinguisher Kitchen Seaton ES.  VAMP Emergency Priority I/Emergency Repair)
IFC 904.12.6.2   Operation and Maintenance (Inspection/Testing) ? Kitchen Ansul Suppression system
Kitchen - Service, update and re-tag expired (July 2020 ) Ansul kitchen fire suppression system.  Implement service PM plan to update every 6-mos as required bit IFC/ FEMS Inspector.

 Extinguishing system service: Automatic fire-extinguishing systems shall be serviced at least every six months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.  FEMS LVL-2
SEATON ELEMENTARY SCHOOL 672370 Cooling Kitchen Cooling Issue:
? AC Unit
? Too Hot

Assignment Description:
No a/c in kitchen can we get a window unit or portable unit
SEATON ELEMENTARY SCHOOL 680252 Cooling (HVAC Services) Left side of stage Leak Issue:
? Source Unknown

Assignment Description:
Leaking from ceiling source unknown//This is a leak on the air handler unit in the ceiling refer to HVAC
SEATON ELEMENTARY SCHOOL 664841 Heating Library Heating Issue:
? Thermostat
? Too Cold

Assignment Description:
Heat won't come on
SEATON ELEMENTARY SCHOOL 675305 Cooling Library Cooling Issue:
? Thermostat
? Too Hot

Assignment Description:
A/C not working  to hot
SEATON ELEMENTARY SCHOOL 674792 Cooling Main lobby Water is leaking from under the hallway  units
SEATON ELEMENTARY SCHOOL 680729 Outlet Multipurpose room Seaton  ES   (VAMP High Priority II/Priority Repair)
IFC 605.6 Unapproved conditions Exposed Wires
Multipurpose room left of stage ?  Install blank cover plate on ceiling mounted to junction box.

Open junction boxes and open-wiring splices shall be prohibited.  Approved covers shall be provided for all switch and electrical outlet boxes.   FEMS Lvl-2
SEATON ELEMENTARY SCHOOL 681251 Grounds outside by dumpster Grounds Issue:
? Bulk Trash

Assignment Description:
a lot of broken funiture and other item
SEATON ELEMENTARY SCHOOL 663307 Heating Outside elevator room Heating Issue:
? Temperature
? Too Cold

Assignment Description:
No ventilation may cause  oil to freeze and stop operation
SEATON ELEMENTARY SCHOOL 622684 Lock and Door Outside of RM 124 Unable to enter classroom from the playground  using Fob
SEATON ELEMENTARY SCHOOL 680929 Cooling Room 100C Cooling Issue:
? Temperature
? Too Hot

Assignment Description:
AC is not working.
SEATON ELEMENTARY SCHOOL 661245 Cooling Room 214 Perform maintenance on the HVAC unit in Room 214, ensuring the source of the leak causing staining has been corrected.
SEATON ELEMENTARY SCHOOL 674207 Cooling Spanish Leaking from ceiling when a/c is turned on
SEATON ELEMENTARY SCHOOL 662845 Lock and Door Stairway #2 Lock and Door Issue:
? Lock/Latch
? Metal Door
? Repair/Replace/Install Door/Door Frame
? null

Assignment Description:
When I use my fob key to enter the building the latch is on a 25 min delay causing the door to be unsecured
SEATON ELEMENTARY SCHOOL 680250 Cooling (HVAC Services) Stairway #2 Leak Issue:
? Source Unknown

Assignment Description:
Leaking down wall//This is a Univent leak on the wall refer to HVAC
SEATON ELEMENTARY SCHOOL 680728 Cooling Various Seaton ES. (VAMP High Priority II/Priority Repair)  IFC 703.3 Ceilings-Maintenance/Opening Protectives Missing ceiling tiles in the library multipurpose room left and right of stage ? HVAC/AHU system and associated pipelines are leaking causing water damage to ceiling tiles. Trash cans and buckets used to collect water is continuous during cooling season The pipe insulation was observed to be saturated with water in several areas.  Electrical outlets, light fixtures and conduit lines are also affected.All leaks must be repaired before replacing water damaged & missing acoustical ceiling tiles to satisfy this cited fire code violation. Leaks also continue in the main office and other areas Wasina systems were altered to provide air and ventilation above the ceiling system to no avail.  The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be visually inspected by the owner annually and properly repaired, restored or replaced when damaged, altered, breached or penetrated. FEMS Lvl-2
STUART-HOBSON MIDDLE SCHOOL 672259 Cooling 105D, 105E, Main Office General, Ground Level Hallway, Auditorium,Gym, 109, 111,114, 202, 222, 219, 218, 211, 207 , Nurse Suite, First Floor and Second Floor Hallway Cooling Issue:
? Temperature
? Too Hot

Assignment Description:
School is experiencing elevated heat temperatures in classrooms and working spaces:  Some spaces are reaching between 85 to 90 degrees. See below

105D, 105E, Main Office General, Ground Level Hallway, Auditorium,Gym, 109, 111,114, 202, 222, 219, 218, 211, 207,  Nurse Suite, First Floor and Second Floor Hallway
STUART-HOBSON MIDDLE SCHOOL 643859 Interior Painting & Wall Issue 1st Floor Interior Painting & Wall Issue:
? Painitng
? Painting Maintenance

Assignment Description:
Requesting to have the 1st floor painted a white semi gloss.
STUART-HOBSON MIDDLE SCHOOL 664103 Faucet 1st floor girls restroom Faucet Issue:
? Sink
? Repair / Replace

Assignment Description:
Requesting to have sink caulked and sealed to be back against the wall.
STUART-HOBSON MIDDLE SCHOOL 638647 Building Structural (Interior Services) 1st Floor Hallway carpentry has completed this task.
for new glass installation need to be completed by contract services.
STUART-HOBSON MIDDLE SCHOOL 614321 Window 215 Blinds in Room 215 are off the track and needs to be remounted.
STUART-HOBSON MIDDLE SCHOOL 643862 Interior Painting & Wall Issue 2nd Floor Interior Painting & Wall Issue:
? Painitng
? Painting Maintenance

Assignment Description:
Requesting to have the 2nd floor hallway painted a semi gloss white paint.
STUART-HOBSON MIDDLE SCHOOL 682632 Interior Painting & Wall Issue 304 Requesting to have damage baseboard replaced in room 304.
STUART-HOBSON MIDDLE SCHOOL 681637 Cooling 3rd floor hallway Requesting to have leak coming from the HVAC unit resolved ASAP before the ceiling collapse.
STUART-HOBSON MIDDLE SCHOOL 668407 Grounds 4th and E/Outside of School Grounds Issue:
? Bulk Trash

Assignment Description:
Requesting Facilities lower Flag sor provide the school a temporary flag crank starting on March 18 until March 22, 2021 in compliance with the Mayor's order. Also,  in the event that a flag crank is not able to be loaned, we will need the flag raised back on March 23rd, 2021.

Also note, there is no appropriate coding for the issue.


Principals and Operations POC?s,

At the request of the Mayor, we are asking that you please lower the United States and District of Columbia flags to half-staff until sunset, March 22, 2021 in remembrance of the victims of the shooting in Atlanta. Our hearts and prayers are extended to the families of those who have lost a loved one in this tragedy.

If you have any questions or need support, please reach out to your cluster Operations Specialist.

Thanks,
Patrick

Patrick Davis
Chief Operating Officer
 
Office of the Chief Operating Officer
District of Columbia Public Schools
1200 First Street, NE
Washington, DC  20002
C: 202-365-4746
STUART-HOBSON MIDDLE SCHOOL 580164 Roof (Exterior Services) Atrium the roof area over top of the atrium is leaking in mutliplw spots.
STUART-HOBSON MIDDLE SCHOOL 674416 Interior Painting & Wall Issue Atrium Requesting to have wood trim put back on to the wall inside of the atrium in the cafeteria.
STUART-HOBSON MIDDLE SCHOOL 679289 Interior Painting & Wall Issue Atrium Requesting to have the wood trim around the entrance trim around the access area between the atrium and the kitchen secured back to the wall.
STUART-HOBSON MIDDLE SCHOOL 677173 Interior Painting & Wall Issue Atrium of Cafeteria Wall needs painting(white eggshell) due to discoloration from leak
STUART-HOBSON MIDDLE SCHOOL 665507 Heating Boiler room Heating Issue:
? Heating Unit
? Too Cold

Assignment Description:
Requesting to have unit repaired.
STUART-HOBSON MIDDLE SCHOOL 675665 Heating Boiler Room Repair ignition wire on boiler#3.
STUART-HOBSON MIDDLE SCHOOL 671790 Interior Painting & Wall Issue Boys locker room Requesting to have the wall inside of the boys locker room inside of the gymnasium painted a semi gloss.
STUART-HOBSON MIDDLE SCHOOL 631560 PA and Clock System G02 PA and Clock System Issue:
? Intercom/PA System
? Sound Too Low

Assignment Description:
Room G02 inter comm system is not loud or clear. We had a lockdown situation a few days ago and the announcement could not reach the room.
STUART-HOBSON MIDDLE SCHOOL 664110 Faucet Girls restroom ground floor Faucet Issue:
? Sink
? Repair / Replace

Assignment Description:
Requesting to have sinks cualked and secure back to the wall.
STUART-HOBSON MIDDLE SCHOOL 678286 Ceiling Ground floor hallway Requesting to have water damage ceiling tiles replaced.
STUART-HOBSON MIDDLE SCHOOL 658836 Interior Painting & Wall Issue Ground Level/Gym Floor Interior Painting & Wall Issue:
? Painitng
? Repaint

Assignment Description:
Requesting semi gloss paint for the wall in the girl's restroom.
STUART-HOBSON MIDDLE SCHOOL 631561 PA and Clock System Gym PA and Clock System Issue:
? Intercom/PA System
? Sound Too Low

Assignment Description:
Gym area inter comm system is not loud or clear. We had a lockdown situation a few days ago and the announcement could not reach the room.  Impossible to hear announcements when activities are taking place.
STUART-HOBSON MIDDLE SCHOOL 652687 Roof Gymnasium Roof Issue:
? Water Leak
? Rooftop

Assignment Description:
Requesting to have the roof repaired over top of the gymnasium which leaks when it rains.
STUART-HOBSON MIDDLE SCHOOL 631563 PA and Clock System Library PA and Clock System Issue:
? Intercom/PA System
? Reset/Synchronize

Assignment Description:
Library inter comm system is not loud or clear. We had a lockdown situation a few days ago and the announcement could not reach the room.
STUART-HOBSON MIDDLE SCHOOL 665888 Building Structural Main Lobby Requesting to have automatic door repaired the door doesn?t close properly.
STUART-HOBSON MIDDLE SCHOOL 669474 Lock and Door Main lobby Need a electrician for automatic main lobby door contractors replaced something on the door and said all we need was a electrician for the power.
STUART-HOBSON MIDDLE SCHOOL 679147 Lighting Main office Requesting to have blown hanging lights inside of the main office waiting area replaced on the 1st floor.
STUART-HOBSON MIDDLE SCHOOL 680410 Electronic Security Issue Main Office Entrance Electronic Security Issue:
? Not Working

Assignment Description:
Requesting to have security alarm panel trouble transmit code cleared from constant alerts that keep going off every 5-10 minutes
STUART-HOBSON MIDDLE SCHOOL 671710 Roof Outside of the main entrance lobby Requesting to have standing water and debris removed and drain pipe repaired or replace on outside concrete roof over top of the main lobby door.
STUART-HOBSON MIDDLE SCHOOL 671657 Roof Outside of the main lobby Requesting to have outside concrete balcony repaired from deterioration and leaking. (Safety hazard) It will eventually collapse.
STUART-HOBSON MIDDLE SCHOOL 667308 Building Structural Principals office Structural Issue:
? Ceiling

Assignment Description:
Requesting to have vertical blimd repaired or replaced because the lowering cable does not work.
STUART-HOBSON MIDDLE SCHOOL 643571 Roof Rooftop Roof Issue:
? Roof Damage

Assignment Description:
Need catwalk installed
Filters need to be replaced throughout building
STUART-HOBSON MIDDLE SCHOOL 681966 Lighting Room 121 Requesting to have light motion detection module replaced because the it?s not working this not letting the lights come on in room 121 on the 1st floor.
STUART-HOBSON MIDDLE SCHOOL 679269 Lighting Room 209 Requesting to have light fixture in room 209 on the 2nd floor repaired from hanging improperly.
STUART-HOBSON MIDDLE SCHOOL 682667 Interior Painting & Wall Issue Room 303 Requesting to have wall patched and painted in room 303.
STUART-HOBSON MIDDLE SCHOOL 682670 Interior Painting & Wall Issue Room 303 Requesting have baseboard replaced in room 303
STUART-HOBSON MIDDLE SCHOOL 672314 Roof Room 314 Roof Issue:
? Water Leak
? Rooftop

Assignment Description:
Ceiling leaking. Plaster is peeling
STUART-HOBSON MIDDLE SCHOOL 643905 Interior Painting & Wall Issue Stairwell #2 Interior Painting & Wall Issue:
? Painitng
? Painting Maintenance

Assignment Description:
Requesting to have stairwell #2 painted a semi gloss white paint.
STUART-HOBSON MIDDLE SCHOOL 643854 Interior Painting & Wall Issue Stairwell #3 Interior Painting & Wall Issue:
? Painitng
? Painting Maintenance

Assignment Description:
Requesting to have stairwell #3 painted a semi gloss white.
STUART-HOBSON MIDDLE SCHOOL 643865 Interior Painting & Wall Issue Stairwell 1 Interior Painting & Wall Issue:
? Painitng
? Painting Maintenance

Assignment Description:
Requesting to have stairwell #1, #2, #3 painted a semi gloss white paint.
STUART-HOBSON MIDDLE SCHOOL 668978 Building Structural Sub basement hallway Requesting to have sub floor repaired throughout the sub basement area.
STUART-HOBSON MIDDLE SCHOOL 676721 Interior Painting & Wall Issue Third floor hallway above lockers Walls need painting because of roof leak and bubbling plaster
TYLER ELEMENTARY SCHOOL 663208 Cooling 109 Pipes leaking  resulting in ceiling tiles collapsing. Room is located across the hall form another pipe leak in the main office.
TYLER ELEMENTARY SCHOOL 682365 Cooling 115 Univent stop working
TYLER ELEMENTARY SCHOOL 676930 FLOORING 115 Flooring Issue:
? Carpet
? Repair/Replace

Assignment Description:
Classroom carpet worn and displays liquid damage areas.
TYLER ELEMENTARY SCHOOL 682356 Cooling 115 Univent AC unit Cooling Issue:
? AC Unit
? Too Hot

Assignment Description:
Room's univent AC unit is not pushing out any cool air at all!!
TYLER ELEMENTARY SCHOOL 676932 Interior Painting & Wall Issue 116 Interior Painting & Wall Issue:
? Patching & Painting
? Repaint

Assignment Description:
Drywall has holes in it and needs to be repaired in the Teacher's lounge.
TYLER ELEMENTARY SCHOOL 682294 Cooling 135 Univent is leaking on the floor
TYLER ELEMENTARY SCHOOL 679127 Cooling 135 AC unit leaking water on floor
TYLER ELEMENTARY SCHOOL 673415 Window 201 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Classroom needs (2) window screens installed.
TYLER ELEMENTARY SCHOOL 673414 Window 202 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Windows need (2) window screens installed.
TYLER ELEMENTARY SCHOOL 673410 Window 206 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Classroom needs (2) window screens installed.
TYLER ELEMENTARY SCHOOL 669860 Window 207 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Windows will not remain open without a book or some form of stopper.
TYLER ELEMENTARY SCHOOL 673409 Window 207 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Classroom needs (3) window screens installed.
TYLER ELEMENTARY SCHOOL 673407 Window 208 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Classroom needs (1) window screen installed.
TYLER ELEMENTARY SCHOOL 680138 Lock and Door 208 Assistant principals key will not open lock
TYLER ELEMENTARY SCHOOL 674455 Cooling 209 Replace blown univent motor and capacitor. The fuses are good. Unit does not energize when switched on.
TYLER ELEMENTARY SCHOOL 672640 Cooling 210 Repair univent motor. Motor will not engage. Motor is 1/8hp, 115v, and 1ph.
TYLER ELEMENTARY SCHOOL 682782 Cooling 216 Cooling Issue:
? AC Unit
? No AC

Assignment Description:
Univent isn't pushing out any cool air.
TYLER ELEMENTARY SCHOOL 676378 Interior Painting & Wall Issue 216 Please remount cabinets that fell off the wall
TYLER ELEMENTARY SCHOOL 673417 Window 217 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Classroom needs (1) window screen installed.
TYLER ELEMENTARY SCHOOL 677846 Interior Painting & Wall Issue 2nd floor wall Interior Painting & Wall Issue:
? Patching & Painting
? Repaint

Assignment Description:
Second floor gray, base level painting is chipped and cracked.
TYLER ELEMENTARY SCHOOL 669871 Window 301/302 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Window cannot stay open without a book or something to hold them.
TYLER ELEMENTARY SCHOOL 673396 Window 304 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Classroom needs (6) window screens installed.
TYLER ELEMENTARY SCHOOL 658685 Overhead Door 305 Overhead Door / Mechanical Fence Issue:
? Overhead Door
? Repair/Replace

Assignment Description:
Top window has dropped to the bottom top of frame as bent needs to be permanently sealed and put back into place
TYLER ELEMENTARY SCHOOL 673397 Window 305 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Classroom needs (1) window screen installed.
TYLER ELEMENTARY SCHOOL 668613 Heating 306 Heating Issue:
? Temperature
? Too Hot

Assignment Description:
Extremely hot inside of In Person classroom 97.  Some students asked to step outside of the classroom due to the heat thus interrupting the lesson plans.
TYLER ELEMENTARY SCHOOL 673399 Window 306 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Classroom needs (2) window screens installed.
TYLER ELEMENTARY SCHOOL 673401 Window 307 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Classroom needs (1) window screen installed.
TYLER ELEMENTARY SCHOOL 673402 Window 308 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Classroom needs (5) window screens installed.
TYLER ELEMENTARY SCHOOL 673406 Window 309 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Classroom needs (2) window screens installed.
TYLER ELEMENTARY SCHOOL 673400 Window 311 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Classroom needs (1) window screen installed.
TYLER ELEMENTARY SCHOOL 673394 Window 316 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Broken
? null

Assignment Description:
Window is cracked and needs replacement.  Classroom needs (6) window screens.
TYLER ELEMENTARY SCHOOL 673392 Window 317 Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Classroom needs (7) window screens installed.
TYLER ELEMENTARY SCHOOL 665454 Electronic Security Issue Basement it room Electronic Security Issue:
? Maintenance

Assignment Description:
Battery leaking
TYLER ELEMENTARY SCHOOL 667636 Heating Boiler room Heating Issue:
? Heating Unit
? Too Cold

Assignment Description:
Repair boiler1. Boiler will not shut off at the modulator control. Fan continues to run. Only shuts down at the breaker.
TYLER ELEMENTARY SCHOOL 671401 Cooling chiller Cooling Issue:
? AC Unit
? Central Air

Assignment Description:
Complete Tube Chiller PM
TYLER ELEMENTARY SCHOOL 676417 FLOORING First floor Art room Flooring Issue:
? Tile
? Broken/Cracked/Damaged

Assignment Description:
HVAC renovation cracked the floor tiles in the art room.
TYLER ELEMENTARY SCHOOL 676922 Interior Painting & Wall Issue First floor boys bathroom Interior Painting & Wall Issue:
? Patching & Painting
? Caulking

Assignment Description:
Boys bathroom wall tiles are missing and damaged.
TYLER ELEMENTARY SCHOOL 676923 Interior Painting & Wall Issue First floor boys bathroom Interior Painting & Wall Issue:
? Patching & Painting
? Paint Peeling

Assignment Description:
Boys bathroom wall needs some replacement painting.
TYLER ELEMENTARY SCHOOL 676928 Interior Painting & Wall Issue First floor hallway Interior Painting & Wall Issue:
? Patching
? Repaint

Assignment Description:
Patch paint first floor hallway.
TYLER ELEMENTARY SCHOOL 673412 Window Library Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Room need (3) window screens installed.
TYLER ELEMENTARY SCHOOL 674779 Window Main office Window needs to be reinforced window from the top will fall at any time
TYLER ELEMENTARY SCHOOL 677845 FLOORING Main Office Flooring Issue:
? Carpet
? Repair/Replace

Assignment Description:
Main office carpet has unremovable stains and damage from an extended ceiling leak which require replacement.
TYLER ELEMENTARY SCHOOL 677107 PA and Clock System Network room 2nd floor PA and Clock System Issue:
? Clock System
? Reset/Synchronize

Assignment Description:
We need a synchronized clock server to connect and sync with the clocks around the building.
TYLER ELEMENTARY SCHOOL 656597 Playground Playground Playground Issue:
? Equipment
? Repair/Remove/Replace Equipment

Assignment Description:
The basketball hoop extender pipe has been severed/broken.
TYLER ELEMENTARY SCHOOL 663468 Heating Rm201 Heating Issue:
? Heating Unit
? Too Hot

Assignment Description:
Closed loop 3/4? supply line, after the isolation valve, 10ft high, in the ceiling, has a leak from a nipple.
TYLER ELEMENTARY SCHOOL 668546 Heating Room 305 Heating Issue:
? Heating Unit
? Too Hot

Assignment Description:
Social worker room is extremely hot, reading 97.5.
TYLER ELEMENTARY SCHOOL 676933 Interior Painting & Wall Issue Staircase foyer Interior Painting & Wall Issue:
? Painitng
? Repaint

Assignment Description:
Staircase walls need repainting.
TYLER ELEMENTARY SCHOOL 657168 Roof (Exterior Services) Third floor custodian closet Leak Issue:
? Source Unknown

Assignment Description:
Slop sink is leaking at base//roof leak
TYLER ELEMENTARY SCHOOL 677984 Cooling Throughout building Check and recalibrate the Univents  some univent are not cooling through out building
TYLER ELEMENTARY SCHOOL 672523 Interior Painting & Wall Issue Throughout building boys and girls restrooms Please replace all soap dispensers that aren't working throughout building boys and girls restrooms
VAN NESS ELEMENTARY 678791 Toilet 3rd floor girls bathroom Toilet Issue:
? Toilet
? Leak

Assignment Description:
The toilets in the first and last stalls in the 3rd floor girls bathrooms are leaking at the connection to the wall.
VAN NESS ELEMENTARY 654487 Roof 3rd floor hallway Roof Issue:
? Water Leak
? Rooftop

Assignment Description:
Leak from roof it's still leaking
VAN NESS ELEMENTARY 668988 Heating all rooms Heating Issue:
? Heating Unit
? Too Hot

Assignment Description:
secure thermostats
VAN NESS ELEMENTARY 675970 Cooling Building second floor lower roof Cooling Issue:
? AC Unit
? Too Hot

Assignment Description:
RRU #2 sensors/controls are not reading correctly, they?re causing the RTU to cool and heat simultaneously.
VAN NESS ELEMENTARY 669969 Sidewalks Outside Flagpole have knots in the line it needs to be rethreaded canraise or lower sometimes
VAN NESS ELEMENTARY 665016 Playground Outside playground Playground Issue:
? Equipment
? Repair/Remove/Replace Equipment

Assignment Description:
Equipment needs repair is a safety hazard
VAN NESS ELEMENTARY 673482 Playground Playground Utility pipe needs cover kid had his foot in it  safely issue
VAN NESS ELEMENTARY 679856 Outlet Room 218 Outlet Issue:
? Repair Outlet
? The conduit is not exposed

Assignment Description:
There are two outlets in the room:  duplex and quadplex.  Neither plug is working on the duplex and only one is working on the quadplex.
VAN NESS ELEMENTARY 668410 Switch Room 312 Switch Issue:
? Light Sensor Problem
? The conduit is not exposed

Assignment Description:
The dimmer in the classroom keeps turning lights on and then down repeatedly.  Can't keep contact level of illumination.
WALKER-JONES EDUCATION CAMPUS 678399 Lock and Door 1st floor staircase 1 near room 102 Walker-Jones EC  VAMP High Priority II/Priority Repair)
IFC 703.2.3 - Door operation
First floor staircase 1 near room 102   ? Adjust door closer latch speed on left door ; Adjust hinges and realign doors to properly latch shut.. 

Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. FEMS Lvl-2
WALKER-JONES EDUCATION CAMPUS 678395 Lock and Door 1st floor staircase 2 Walker-Jones ED  (VAMP High Priority II/Priority Repair)
IFC 703.2.2  Door Holding Devices
First floor staircase-2  Replace damaged or missing magnet(s) on exit doors; reenergized electromagnetic armature(s) where needed.  Increase sweep and latch speed on left door; repair or replace vertical rod on right door, door will not disengage. 

Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position.  Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate.
FEMS Lvl-2
WALKER-JONES EDUCATION CAMPUS 678396 Lock and Door 2nd floor staircase 2 Walker-Jones ED  (VAMP High Priority II/Priority Repair)
IFC 703.2.2  Door Holding Devices
Second floor staircase-2  Replace damaged or missing magnet(s) on exit doors; reenergized electromagnetic armature(s) where needed.   Repair or replace damaged latch head and vertical rod assembly on left door.

Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position.  Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate.
FEMS Lvl-2
WALKER-JONES EDUCATION CAMPUS 635359 Lock and Door 314/ Early Stages Main Office Door Lock and Door Issue:
? Lock/Latch & Door
? Standard Door
? Repair/Replace/Install Door Lock
? null

Assignment Description:
Maintenance came in and installed new locks on all doors that did not have the ability to lock and unlock from the inside. On the Early Stages Main Office Door they installed the wrong part, causing the door to Jam and never close all the way, needs to be fixed or repaired. May need to check to see if any other tickets have been placed already to repair this door.
WALKER-JONES EDUCATION CAMPUS 653496 Window 314 Early Stages Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Repair/Replace/Install
? null

Assignment Description:
Blinds need to be replaced in several rooms throughout early stages, which is room# 300-318, except room 317.
WALKER-JONES EDUCATION CAMPUS 635376 FLOORING 318/314/310/308/305/ Early Stages Flooring Issue:
? Carpet
? Repair/Replace

Assignment Description:
Carpet needs to be replaced, it hasn't been replaced over 10 years. It has been infested with rodents and their droppings, regular wear and tear. This is testing area for 2.5 yr old to 5 year old, clean environment is needed.  Allergy issues are flared from both workers and children been tested. Need carpet removed and replaced.
WALKER-JONES EDUCATION CAMPUS 673607 Cooling 4th floor rooftop Request to repair or replace rooftop unit number 4 compressors will not engage for cooling possible refrigerant leak
WALKER-JONES EDUCATION CAMPUS 677732 Cooling 4th floor rooftop Request to repair or replace bad condenser fan motor on rooftop unit number 4 need for cooling
WALKER-JONES EDUCATION CAMPUS 677711 Heating Back loading dock area Request to have generator service it will not run in auto
WALKER-JONES EDUCATION CAMPUS 665495 Fire Sprinkler Basement Pump room Pump Issue:
? Pressure
? Leak / Discharge

Assignment Description:
Sprinkler system to be service
WALKER-JONES EDUCATION CAMPUS 656484 Heating Boiler room Heating Issue:
? Heating Unit
? Too Hot

Assignment Description:
Request to have boiler number 2 burner calibrated
WALKER-JONES EDUCATION CAMPUS 677903 Fire Extinguisher Building exterior Walker-Jones EC   (VAMP Routine Priority III/Routine Repair)
IFC 912.2.2 Existing buildings Fire Connection (FDC) Signs
Pierce St side near corner ofNew Jersey Ave side of building on exterior walls -  Fire Department Connection (FDC) placard. Provide and install visible ?FDC? Signage on masonry wall surface above FDC connection inlets  as required by the fire inspector.

On  existing buildings, wherever the fire department connection is not visible to approaching fire apparatus, the fire department connection shall be indicated by an approved sign mounted on the street front or on the side of the building. Such sign shall have the letters ?FDC? at least 6 inches (152 mm) high and words in letters at least 2 inches (51 mm) high or an arrow to indicate the location. All such signs shall be subject to the approval of the fire code official.
FEMS Lvl -2
WALKER-JONES EDUCATION CAMPUS 596315 Power Cafeteria Resubmitting this work order. Automatic curtains in the cafeteria are not functioning properly. The curtains are low voltage, and this work needs to go to contract services.
WALKER-JONES EDUCATION CAMPUS 678397 Lock and Door Exterior doors near security office Walker-Jones EC  (VAMP High Priority II/Priority Repair)
IFC 703.2.2  Door Holding Devices
Corridor near security office & room 102- Exterior exit doors near security office will not open; adjust pivot hinges and realign doors to open, close  and latch.

Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position.  Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate.
FEMS Lvl-2
WALKER-JONES EDUCATION CAMPUS 677901 Fire Sprinkler Fire Pump room Walker-Jones EC  (VAMP Routine Priority III/Routine Repair)
IFC 913.5 - Testing and maintenance -
Fire Pump Room -  Annual service, maintenance requiredFire pumps shall be inspected, tested and maintained in accordance with the requirements of this section and NFPA 25. Records of inspection, testing and maintenance shall be maintained. 

Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust systems, and smoke and heat vents shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.   FEMS Lvl-2
WALKER-JONES EDUCATION CAMPUS 680133 Lock and Door Front entrance door Metal detierating from around the door frame
WALKER-JONES EDUCATION CAMPUS 640206 Lock and Door Front School Door Lock and Door Issue:
? Door
? Automatic Door
? Repair/Replace/Install Door Lock
? null

Assignment Description:
The door connected to the doorbell is not currently opening. not sure if a ticket has been placed for this yet.
WALKER-JONES EDUCATION CAMPUS 673538 Cooling in several rooms 114,114a,114b,114c,114d,114e,114f,214,214a,214b,216,218,314, 314a,314b,314c,314d,312,318,316 cooling issue>temperature>too hot
Assignment Description:
Cooling issue rooms are to hot we are in the need for 20 fans.  This area of the building is always a on going issue.
WALKER-JONES EDUCATION CAMPUS 654352 Roof roof top oner gym roof issue>water leak>rooftop
Assignment Description:
roof leaking badly in gym
WALKER-JONES EDUCATION CAMPUS 679118 Interior Painting & Wall Issue Room 112 Principal office needs painting
WALKER-JONES EDUCATION CAMPUS 679339 Lock and Door Room 112 Repair door handle so that the Principal can secure his door
WALKER-JONES EDUCATION CAMPUS 678126 Lock and Door Room 220 Can not open the door also wrong door handle install
WALKER-JONES EDUCATION CAMPUS 679115 Outlet Room 320A Install outlet for copier machine
WALKER-JONES EDUCATION CAMPUS 682683 Environmental Rooms 321,325,326 Hepa filters machine needed
WALKER-JONES EDUCATION CAMPUS 678398 Lock and Door Staircase near room 031 Walker-Jones EC  VAMP High Priority II/Priority Repair)
IFC 703.2.3 - Door operation
Exit door to staircase near Room 031 Storage - Adjust hinges and realign doors to properly latch shut. 

Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. FEMS Lvl-2
WATKINS ELEMENTARY SCHOOL 631673 Lock and Door 161 cafeteria Lock and Door Issue:
? Door
? Metal Door
? Repair/Replace/Install Door Lock
? null

Assignment Description:
Rollup door is not staying up in place.
WATKINS ELEMENTARY SCHOOL 627888 Lock and Door 190 Back door The handicap wave to open sensor housing is broken
WATKINS ELEMENTARY SCHOOL 681495 Ceiling 1st Floor Hallway by 12th and Dst entrance Ceiling tile needs to be replaced has a water stain in it.
WATKINS ELEMENTARY SCHOOL 674070 Lock and Door 1st floor Hallway Door lead to classrooms Lock and Door Issue:
? Lock/Latch & Door
? Standard Door
? Repair/Replace/Install Door Lock
? null

Assignment Description:
Hallway door does not lock at all in case of lock down emergency the door will not keep first floor classroom out of harms way ticket needs to be escalated ASAP URGENT!!!!! Safety Issue!!!!!!
WATKINS ELEMENTARY SCHOOL 659480 Window 1st floor Main Entrance Door Window Issue:
? Above 8 feet/1 Story
? Window Frame
? Broken
? null

Assignment Description:
Broken window ledge on the top right hand main entrance door.
WATKINS ELEMENTARY SCHOOL 674365 Pipe 1st Floor Outside of Room 143 Pipe Issue:
? Water
? Leak

Assignment Description:
There's a pipe leaking in the ceiling needs immediate attention URGENT Safety Issue!!!!
WATKINS ELEMENTARY SCHOOL 678645 Interior Painting & Wall Issue 1st Floor Room 115 Wall has patches in the paint on wall that needs  immediate attention
WATKINS ELEMENTARY SCHOOL 652123 Interior Painting & Wall Issue 1st floor Room 135 Interior Painting & Wall Issue:
? Patching & Painting
? Painting Maintenance

Assignment Description:
Hole in wall
WATKINS ELEMENTARY SCHOOL 659481 Toilet 1st floor Room 144 Toilet Issue:
? Urinal
? Clog / Unclog

Assignment Description:
Urinal on the right hand side of the door is not flooding when flushed.
WATKINS ELEMENTARY SCHOOL 682427 Cooling 1st floor Room 190 Cooling Issue:
? AC Unit
? No AC

Assignment Description:
Right side of the Gymnasium is not producing any cool air on days of 88degrees and above the right side of the gym feels like a steam room leaving windows foggy and gym floor moist needs immediate attention URGENT!!!!! Safety Hazarad.
WATKINS ELEMENTARY SCHOOL 660331 Leak 1st floor Room 190 Leak Issue:
? Ceiling

Assignment Description:
Ceiling is leaking tremendously and needs immediate attention URGENT!!!!
WATKINS ELEMENTARY SCHOOL 675905 Pipe 1st floor Room 190 Pipe Issue:
? Water
? Leak

Assignment Description:
We have a leaking water pipe in the ceiling outside of gymnasium  causing the ceiling tile to collapse in hallway where kids water fountain are located ticket needs immediate attention URGENT!!!!! Safety hazarad!!!!!
WATKINS ELEMENTARY SCHOOL 600433 Leak 240 the green roof is leaking (again) into Rm. 240. There is one tile that has to be replaced consistently due to leak.
WATKINS ELEMENTARY SCHOOL 678595 Interior Painting & Wall Issue 2nd floor Room 215 Classroom is in need of paint for entrance walls also needs touch up's thru out the rooms
WATKINS ELEMENTARY SCHOOL 678852 Window 2nd floor Room 220 Classroom window is shattered in multiple pieces safety harzard children inside of classroom needs immediate attention URGENT!!!!!!
WATKINS ELEMENTARY SCHOOL 653543 Roof (Exterior Services) 2nd floor Room 240 Ceiling Issue:
? Damaged Tiles

Assignment Description:
Heavy Leaking from ceiling by the window//roof leak, sent to contract service
WATKINS ELEMENTARY SCHOOL 662354 Roof (Exterior Services) 2nd floor Room 240 Leak Issue:
? Ceiling

Assignment Description:
Ceiling needs immediate attention URGENT!!!!! Ceiling is collapsing//roof leak
WATKINS ELEMENTARY SCHOOL 652141 Interior Painting & Wall Issue 3rd Floor Hallway Interior Painting & Wall Issue:
? Patching
? Painting Maintenance

Assignment Description:
Hallway window ledge broken off window across from the common area
WATKINS ELEMENTARY SCHOOL 680268 Landscaping 3rd floor Outside Garden Garden above footprint room needs to to cut because grass is growing wildly cause water drain to be blocked flooding garden leaking the footprint classroom.
WATKINS ELEMENTARY SCHOOL 651944 Interior Painting & Wall Issue 4th Floor Hallway Interior Painting & Wall Issue:
? Patching & Painting
? Painting Maintenance

Assignment Description:
Panel detached from wall
WATKINS ELEMENTARY SCHOOL 681579 Electronic Security Issue Alarm panels keypads on 1st floor Electronic Security Issue:
? Maintenance

Assignment Description:
Alarm panels are stating that they need troubleshooting adjustments in order to set alarm on the building  URGENT!!!!!
WATKINS ELEMENTARY SCHOOL 682507 Cooling ALL 2ND FLOOR URGENT! URGENT!! URGENT!!
Repair or replace the LG VRF 2A and VRF 2B and VRF 6 , displaying different faults code CH106  , CH 10,CH 03 , CH04, on thermostat , the VRF 2A & VRF 2B serves all the classrooms and VRF #6 serves the library. The VRF 2A& 2B are located on the main roof and the VRF #6 is located on lower roof access through 3rd floor mechanical room 350.
Please additional support is needed ASAP.
WATKINS ELEMENTARY SCHOOL 665189 Interior Painting & Wall Issue All staircases 1st-4th floor Interior Painting & Wall Issue:
? Patching
? Caulking

Assignment Description:
All placards need to be properly installed on walls needs immediate attention URGENT!!!!
WATKINS ELEMENTARY SCHOOL 652132 Interior Painting & Wall Issue Entire school Interior Painting & Wall Issue:
? Painitng
? Repaint

Assignment Description:
School hallways needs to  be painted  with a darker color.
WATKINS ELEMENTARY SCHOOL 662931 Power Exterior roof top from Room 350 mechanical room Power Issue:
? Partial Outage
? The emergency lights are working

Assignment Description:
Watkins ES (Watkins ES & Peabody ES population)  (VAMP Emergency Priority I/Emergency  Repair)
IFC 907.8.5 - Inspection, testing and maintenance:
Rooftop emergency generator accessible from third-floor mechanical room 350 - The Generator is out of service, and shall be abated immedately.  Generator fault indicator light on fire alarm annunciator panel.  Repair and service rooftop emergency generator and restore service back on line.  The building owner shall be responsible to maintain the fire and life safety systems in an operable condition at all times. Service personnel shall meet the qualification requirements of NFPA 72 for inspection, testing and maintenance of such systems. Records of inspection, testing and maintenance shall be maintained.    FEMS Lvl-2
WATKINS ELEMENTARY SCHOOL 667866 FIRE ALARM First Floor Room 121 Health suite fire alarm annouciator is not alarming nurse with neither sound or flashing    not alerting nurse when fire drill nor fire is in place fire hazarad as well as safety issue ticket needs to be escalated.
WATKINS ELEMENTARY SCHOOL 581763 Flooring (Interior Services) front entrance Recommend for DCPS Capital Structural Project. Earlier Note: Floor tiles are coming up as a result of a roof leak. There's about 20 tiles that need to be replaced.
WATKINS ELEMENTARY SCHOOL 675987 Building Structural Front of school building Black slate tile is falling apart from wall out front of school building needs immediate attention safety hazarad. URGENT!!!!!!
WATKINS ELEMENTARY SCHOOL 660316 Building Structural Front of the school building Structural Issue:
? Wall

Assignment Description:
Tile coming apart on front of building needs immediate attention
WATKINS ELEMENTARY SCHOOL 680263 Building Structural Gymnasium 1st floor Room 190 Rubber lining on the track for the gymnasium wall partition in center of the floor is worn  preventing the divider to close .
WATKINS ELEMENTARY SCHOOL 637006 Lighting Gymnasium Room 190 Lighting Issue:
? Interior Lights
? Above 8 feet
? Room(s)/Auditorium/Gymnasium
? null

Assignment Description:
LEDs light blown
WATKINS ELEMENTARY SCHOOL 631445 Roof Library 250 Roof Issue:
? Water Leak
? Rooftop

Assignment Description:
leak coming in the library ceiling.
WATKINS ELEMENTARY SCHOOL 669919 Environmental Loading dock rear of school on Cst side S.E Environmental Issue:
? Hazmat
? Hazmat Cleanup

Assignment Description:
Trash compactor has no source of power technicians have been out numerous of times to fix compactor and still doesn't work. Situation is becoming a ongoing problem and request to have compactors removed and replaced with regular dumpsters before trash get unbearable causing a rodents issues  ticket needs to be escalated ASAP. Urgent!!!!!!!
WATKINS ELEMENTARY SCHOOL 659938 Power Mechanical Room 350  outside left door Power Issue:
? Partial Outage
? The emergency lights are working

Assignment Description:
Repair or replace Emergency generator motor rotor locked out, the generator is in alarm state, it?s located in the mechanical room 350 outside left door.
WATKINS ELEMENTARY SCHOOL 652126 Ceiling Nurse Office Rm121 Ceiling Issue:
? Replace Tiles

Assignment Description:
Leaking from outside nursing office ceiling
WATKINS ELEMENTARY SCHOOL 670854 Power Outside trash compactor Power Issue:
? Complete Outage
? The emergency lights are not working

Assignment Description:
Emergency assistance need for trash compactor no power is on to operate compactor as trash continues to pile up in school ticket needs to be escalated ASAP URGENT!!!!!!
WATKINS ELEMENTARY SCHOOL 587370 Roof (Exterior Services) Rm 140 Roof leaking causing water from the roof to travel and enter classroom 140 through the window seal causing puddles to form. Leak needs to be fixed and roof needs to be repaired.

POC: Robert Kinney (202) 698-6390
WATKINS ELEMENTARY SCHOOL 670887 WATER FOUNTAIN See Description for details Leaking water fountain:
Water fountain near the splash park is damaged and is spraying water
WATKINS ELEMENTARY SCHOOL 681500 PEST CONTROL Thru out building Mass trapping URGENT!!!!!

Showing 1 reaction